2006-11-03 18:49:48 | ** UNSAT *** |
| |
| 1) NOTE: PLEASE PROVIDE SIGNED, DATED AND SEALED WIND |
| LOAD CALCULATIONS FOR THE NEW PROPOSED SITE LIGHTING |
| POLES. PLEASE BE SURE THE CALCULATIONS INCLUDE THE EPA |
| FOR THE LIGHTING FIXTURES WHICH WILL BE INSTALLED. |
| PLEASE SEE BLDG REVIEW COMMENTS FOR 140MPH 3 SECOND |
| GUST, 120SUSTAINED. ETC |
| |
| 2) NOTE: PLEASE INCLUDE THE FOLLOWING RELEVANT CODES ON |
| PLANS AND DESIGN. |
| 2002 NFPA-70 (NEC), 2003 NFPA-101, 2002 NFPA-72 (WHEN |
| APPLICABLE). |
| |
| 3) NOTE: PLEASE SEE ELECTRICAL PANEL IS NOT PERMITTED |
| IN OFFICE / STORAGE AREA. PLEASE SEE 240.24D, 408.7, |
| 110.26 ETC. |
| PLEASE RELOCATE. |
| |
| 4) NOTE: PLEASE SEE 250.6 AND 250.24 AS AN "EQUIPMENT |
| GROUNDING CONDUCTOR" IS BEING INDICATED AHEADOF THE |
| MAIN DISCONNECT. |
| PLEASE KNOW, THIS SHALL ONLY BE INSTALLED AFTER THE |
| FIRST MEANS OF DISCONNECT. |
| |
| 5) NOTE: PLEASE CORRELATE THE EQUIPMENT GROUNDING |
| CONDUCTOR ON RISER WITH THAT LISTED ON PANEL SCHEDULE. |
| PLEASE SEE 250.122, |
| FBC 106.1.2 |
| |
| 6) NOTE: PLEASE SEE MISSING CWP AS PART OF THE |
| GROUNDING ELECTRODE SYSTEM. 250.50 |
| |
| 7) NOTE;: PLEASE SEE LOBBY WILL REQUIRED AN EMERGENCY |
| BATTERY BACK UP LT OF SOME SORT TO MEET THE MIN |
| LIGHTING LEVELS REQUIRED PER LS 101 7.8, 7.9 . (COMBO |
| UNITS, MAY BE USED). (ONLY A SUGGESTION. |
| |
| 8) NOTE: PLEASE PROVIDE CLARIFICATION OF ADJACENT |
| OFFICE SPACE , NOTED A CONSTRUCTION OFFICES. IS THIS |
| STILLPART OF THE SAME TENANT? |
| |
| 9) NOTE: PLEASE CLARIFY THE ADJUSTEDSQ FT FOR SPACE. |
| PLEASE SEE PERMIT APPLICATION, ENERGY CALCULATIONS, AND |
| PLANS. |
| PLEASE KNOW IF BLDG IS OVER 5K SQ FT, FBC 2004 CHAPTER |
| WILL APPLY. |
| PLEASE SEE 13-415.1.AB.1 |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |