Plan Review Notes For Permit 06101016 |
Permit Number |
06101016 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-11-30 07:29:41 | BUILDING PLAN REVIEW | | PERMIT:06101016 | | ADD: 2122 PBL. BLVD | | CONT: MCNEILL SIGNS INC | | TEL: (954)946-3474 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW IST | | ACTION: DENIED | | | | 1)THE INFORMATION ON THE DRAWINGS IN REFERENCE TO | | WIND IS FROM THE 2001 FBC WHICH WAS REPLACE BY THE 2004 | | FBC. ALL PLANS SUBMITTED AFTER OCTOBER, 1, 2004 SHALL | | BE DESIGNED TO THE 2004 FLORIDA BUILDING CODE.THE | | INFORMATION ON THE DRAWINGS ARE UN-ACCEPATABLE. | | | | 2)THE ENGINEER SEAL IS NOT LEGABLE ON THE SHEETS. ALL | | INFORMATION SHALL BE OF SUFFICIENT CLARITY AND SHOW IN | | DETAIL THAT IT WILL CONFORM TO THE RULES AND | | REGULATIONS AS DETERMINED BY THE BUILDING OFFICIAL. | | FBC.106.1.1. | | | | 3) FL S S 713.13 | | NOTICE OF COMMENCEMENT, TO BE FILED | | WITH THE CLERK OF THE COURT BEFORE A | | PERMIT WILL BE ISSUED. NOTE: 713.13(2) | | IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS | | NOT ACTUALLY COMMENCED | | WITHIN 90 DAYS AFTER THE RECORDING | | THEREOF, SUCH NOTICE IS NULL & VOID. | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | 805-6726 | | | | | | |
|