Plan Review Notes
Plan Review Notes For Permit 06101010
Permit Number 06101010
Review Stop E
Sequence Number 3
Notes
Date Text
2007-02-11 12:27:47*** UNSAT ***
  
  
 1) NOTE: PLEASE SEE NEW PLANS CALL THIS ROOM A TELCO
 ROOM AND NOTED AS EXISTING, HOWEVER RESPONSE LETTER
 MENTIONS IN SEVERAL LOCATIONS THAT THIS IS AN EXISTING
 IT ROOM AND IS AN IT ROOM AND NO CONSTRUCTION OR
 ELECTRICAL CODES ARE MET FOR CONSTRUCTION FOR THIS ROOM
 OR EQUIPMENT PLACED IN THIS LOCATION. PLEASE SEE THE
 NFPA-75AND NEC 645 AS THIS CONSIDERATION IS ALSO
 BASED ON THE LIFE SAFETY ISSUES TO OCCUPANTS OUTSIDE
 THIS ROOM AND AREA AS WELL AS THE OTHER CONSIDERATIONS
 FOR INSIDE SUCH A ROOM.
 PLEASE SEE PREVIOUS NOTES, IF THIS IS AN IT ROOM AND
 FALLS UNDER ANY OF THE CHARACTERISTICS OF AS STATED IN
 CHAPTER 2, THEN PLEASE KNOW REQUIREMENTS FOR BRINGING
 UP TO CODE SHALL APPLY.
 PLEASE SEE FBC 106.1.2, 102.1 AND 104.6 OF THE
 ADMINISTRATIVE SECTION OF THE FBC AS ADOPTED BY THE
 CITY OF WEST PALM BEACH.
  
  
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE NOTE #1 FROM THE PREVIOUS REVIEW. IF THIS
 ROOM IS BEING DESIGNATED AS AN IT ROOM AS SHOWN ON
 PLANS AND ALL EQUIPMENT IN ROOM IS FOR EQUIPMENT AS
 DEFINED FOR AN IT ROOM, THEN PLEASE KNOW EVEN IF THIS
 WAS NOT CONSTRUCTED TO THE NFPA-75 STANDARDS, IT ALSO
 MAY HAVE BEEN CONVERTED AT SOME POINT WITH OR WITHOUT
 CORRECTION INFORMATION OR PERMITTING FOR SUCH USE.
 PLEASE SEE NFPA-75 AND NEC 645, AND APPLY NOTES AND
 CODE ACCORDINGLY.
 PLEASE KNOW, IF THESE DO NOT APPLY AND THIS ROOM IS NOT
 INDEED FOR THE PURPOSE AND USE, AND THEN PLEASE ADJUST
 PLANS ACCORDINGLY.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717