2006-12-30 16:26:32 | ** UNSAT 2ND REVIEW ** |
| |
| 1) NOTE: PLEASE SEE NOTE #1 FROM THE PREVIOUS REVIEW. |
| IF THIS ROOM IS BEING DESIGNATED AS AN IT ROOM AS SHOWN |
| ON PLANS AND ALL EQUIPMENT IN ROOM IS FOR EQUIPMENT AS |
| DEFINED FOR AN IT ROOM, THEN PLEASE KNOW EVEN IF THIS |
| WAS NOT CONSTRUCTED TO THE NFPA-75 STANDARDS, IT ALSO |
| MAY HAVE BEEN CONVERTED AT SOME POINT WITH OR WITHOUT |
| CORRECTION INFORMATION OR PERMITTING FOR SUCH USE. |
| PLEASE SEE NFPA-75 AND NEC 645, AND APPLY NOTES AND |
| CODE ACCORDINGLY. |
| PLEASE KNOW, IF THESE DO NOT APPLY AND THIS ROOM IS NOT |
| INDEED FOR THE PURPOSE AND USE,THEN PLEASE ADJUST |
| PLANS ACCORDINGLY. |
| |
| ** ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |