Plan Review Notes
Plan Review Notes For Permit 06100953
Permit Number 06100953
Review Stop E
Sequence Number 1
Notes
Date Text
2006-10-27 10:36:55 
  
 *** UNSAT ***
  
 1) NOTE: PLEASE SEE 2002 NFPA-72 FOR SMOKE DEVICES AND
 PLACEMENT. PLEASE KNOW AS AN OFFICAL INTERPRETATION HAS
 COME FROM NFPA, IF INDEED THE SMOKE DEVICE SHOWN ARE
 DETECTION AND ALRAM DEVICES, THESE SHOULD BE SHOWN AS
 "SA". PLEASE SEE DEFINITIONS IN NFPA-72AS "SD" ARE ONLY
 DETECTION DEVICES AND WUOLD BE PRAT OF AFIRE ALARM
 SYSTEM. THIS IS A CHANGE OF THEPREVIOUS ACCEPTANCE OF
 "SD".
 PLEASE ALSO SEE LOCATION OF A "SA" REQUIRED IN THE
 STUDY ROOM AS THIS WILL BE CONSIDERED AN ADAPTABLE
 SLEEPING ROOM.
 PLEASE SEE SOME LOCATIONS OF THE "SA" DEVICES ARE
 REQUIRED TO BE MOVED TO BE INSTALLED WITHIN 12" OF THE
 HIGHEST POINT IN ANY ROOM FLAT CIELING ETC. PLEASE SEE
 11.8.3.
  
 2) NOTE: PLEASE SEE 310.15B6, 310.16 AS THE MINIMUM
 SIZE FOR THE SEC'S SHALL BE BASED ON THE 300A SERVICE
 AS SHOWN.
 PLEASE CONDUCTORS AS SHONW ARE NOT LARGE ENOUGH.
  
 3) NOTE: PLEASE INDICATE THE SPECIFIC ROOM AND AREAS
 WHIHC THE BRNACH CIRCUIT SFEED. EXAMPLE: BEDRM#2
 LTS/RECETPS, MASTER BDRM RECETPS. BATH #4 , KIT LTS
 ETC.
 310.16,240.4,408.4.
 IT IS KNOWN TO THIS OFFICE DURING CONSTRUCTION THESE
 WILL CHANGE, HOWEVER MIN SHOULD BE INIDCATED AT THIS
 TIME.
  
 4)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND AND CORRELATE WITH LOAD CALCULATIONS.
  
 5) NOTE: PLEASE SEE MISSING KITCHEN COUNTER SPACE
 RECEPTS PER 210.52C1
  
 6) NOTE: PLEASE SEE NOTE #5 PER 210.8A6 AS ALL COUNTER
 SPACE RECEPTS IN KITCHEN(S) SHALL BE INDICATED AS GFI.
  
 7) NOTE: PLEASE SEE CONFLICT ON PLANS FOR MIN AIC
 RATINGS. SHOWS 10K AND 22K. PLEASE VERIFY DISTANCE FROM
 TEH FPL TRANSFORMER AS IT IS KNOWN TO THIS OFFICE THAT
 MANY OF THE OLDER TRANSFORMERS FROM FPL ARE OR HAVE
 BEEN GETTING CHANGED OUT WHICH WILL GIVE A HIGHER
 AVAILABLE FAULT CURRENT AT THE SERVICE. PLEASE VERIFY
 AS MOST OF THE MAINS ARE RATED AT 22K. 110.9. PLEASE
 SEE 240.12 FOR SLECTIVE COORDINATION.
  
 ** PLEASE SEE THERE ARE SOME AREAS ON ELECTRICLA PLANS
 AND PLANS WHICH REFERENCE "PALM BEACH COUNTY"
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  