Date |
Text |
2006-10-27 10:36:55 | |
| |
| *** UNSAT *** |
| |
| 1) NOTE: PLEASE SEE 2002 NFPA-72 FOR SMOKE DEVICES AND |
| PLACEMENT. PLEASE KNOW AS AN OFFICAL INTERPRETATION HAS |
| COME FROM NFPA, IF INDEED THE SMOKE DEVICE SHOWN ARE |
| DETECTION AND ALRAM DEVICES, THESE SHOULD BE SHOWN AS |
| "SA". PLEASE SEE DEFINITIONS IN NFPA-72AS "SD" ARE ONLY |
| DETECTION DEVICES AND WUOLD BE PRAT OF AFIRE ALARM |
| SYSTEM. THIS IS A CHANGE OF THEPREVIOUS ACCEPTANCE OF |
| "SD". |
| PLEASE ALSO SEE LOCATION OF A "SA" REQUIRED IN THE |
| STUDY ROOM AS THIS WILL BE CONSIDERED AN ADAPTABLE |
| SLEEPING ROOM. |
| PLEASE SEE SOME LOCATIONS OF THE "SA" DEVICES ARE |
| REQUIRED TO BE MOVED TO BE INSTALLED WITHIN 12" OF THE |
| HIGHEST POINT IN ANY ROOM FLAT CIELING ETC. PLEASE SEE |
| 11.8.3. |
| |
| 2) NOTE: PLEASE SEE 310.15B6, 310.16 AS THE MINIMUM |
| SIZE FOR THE SEC'S SHALL BE BASED ON THE 300A SERVICE |
| AS SHOWN. |
| PLEASE CONDUCTORS AS SHONW ARE NOT LARGE ENOUGH. |
| |
| 3) NOTE: PLEASE INDICATE THE SPECIFIC ROOM AND AREAS |
| WHIHC THE BRNACH CIRCUIT SFEED. EXAMPLE: BEDRM#2 |
| LTS/RECETPS, MASTER BDRM RECETPS. BATH #4 , KIT LTS |
| ETC. |
| 310.16,240.4,408.4. |
| IT IS KNOWN TO THIS OFFICE DURING CONSTRUCTION THESE |
| WILL CHANGE, HOWEVER MIN SHOULD BE INIDCATED AT THIS |
| TIME. |
| |
| 4)NOTE: PLEASE SEE 220.3B4. |
| PLEASE SHOW ALL RECESSED LTS BASED ON |
| MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| BE FIGURED IN W/ 3W/PER SQ FT. |
| PLEASE PROVIDE FIXTURE INFORMATION ON |
| LEGEND AND CORRELATE WITH LOAD CALCULATIONS. |
| |
| 5) NOTE: PLEASE SEE MISSING KITCHEN COUNTER SPACE |
| RECEPTS PER 210.52C1 |
| |
| 6) NOTE: PLEASE SEE NOTE #5 PER 210.8A6 AS ALL COUNTER |
| SPACE RECEPTS IN KITCHEN(S) SHALL BE INDICATED AS GFI. |
| |
| 7) NOTE: PLEASE SEE CONFLICT ON PLANS FOR MIN AIC |
| RATINGS. SHOWS 10K AND 22K. PLEASE VERIFY DISTANCE FROM |
| TEH FPL TRANSFORMER AS IT IS KNOWN TO THIS OFFICE THAT |
| MANY OF THE OLDER TRANSFORMERS FROM FPL ARE OR HAVE |
| BEEN GETTING CHANGED OUT WHICH WILL GIVE A HIGHER |
| AVAILABLE FAULT CURRENT AT THE SERVICE. PLEASE VERIFY |
| AS MOST OF THE MAINS ARE RATED AT 22K. 110.9. PLEASE |
| SEE 240.12 FOR SLECTIVE COORDINATION. |
| |
| ** PLEASE SEE THERE ARE SOME AREAS ON ELECTRICLA PLANS |
| AND PLANS WHICH REFERENCE "PALM BEACH COUNTY" |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |