Plan Review Notes
Plan Review Notes For Permit 06100953
Permit Number 06100953
Review Stop B
Sequence Number 1
Notes
Date Text
2006-10-31 08:17:10DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE AND A COPY
 SUBMITTED TO THIS OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE RE-RECORDED IF
 THE DESCRIBED IMPROVEMENT OR CONSTRUCTION IS NOT
 COMMENCED WITHIN 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.BASED ON ICC BUILDING VALUATION DATA THE PERMIT
 VALUE HAS BEEN REVISED TO $477,533.00.ADDITIONAL
 PERMIT FEES ARE DUE.
  
 4.PLEASE DO NOT ATTACH PRODUCT APPROVALS TO PLANS.
  
 5.PRODUCT APPROVALS REQUIRED FOR LINTELS.
  
 6.INCORRECT STATE PRODUCT APROVAL PAGES SUBMITTED FOR
 TOWN AND COUNTRY, PGT EXTERIOR DOOR AND FIXED WINDOW.
  
 PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL SHEETS THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM THE STATE. IF
 THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT AN
 APPLICATION FOR LOCAL PRODUCT APPROVAL OR SITE SPECIFIC
 FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 7.THOSE PRODUCT APPROVALS WHICH ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.WPB AMENDMENT TO FBC 106.3.3.
  
  
 8.SUBMIT TWO SETS OF TRUSS DRAWINGS FOR REVIEW PER
 2004 FBC R-802.10.1TRUSS DRAWING REQUIRED TO BE
 APPROVED PRIOR TO INSTALLATION.
  
 9.R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION SO AS
 TO NOT CREATE A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION WALLS. THE
 GRADE AWAY FROM FOUNDATION WALLS SHALL FALL A MINIMUM
 OF 6 INCHESWITHIN THE FIRST 10 FEET.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. SUBMIT ONE
 COPY OF OLD PAGES FOR REFERENCE . A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DEPARTMENT
 561-805-6672
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved