Plan Review Notes
Plan Review Notes For Permit 06100894
Permit Number 06100894
Review Stop E
Sequence Number 2
Notes
Date Text
2006-12-23 19:11:27**UNSAT 2ND REVIEW **
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW WHICH IS
 STILL IN NEED OF ADDRESSING.
 PLEASE SEE NOTES BELOW ARE TAKEN DIRECTLY FROM PREVIOUS
 REVIEW AND NOTED WITH AN OK, NO WITH FURTHER
 EXPLANATION.
 PLEASE SEE SOME MAY BE NOTED NO/OK WHICH WOULD INDICATE
 COMMENT WAS PARTIALLY ADDRESSED.
  
 1) NOTE: OK.
  
 2) NOTE: OK, HOWEVER SEE WHITE-OUT ON PLANS WHICH IS
 NOT PERMITTED ON PLANS WHETHER OR NOT THEY ARE SIGNED
 AND SEALED BY AN ENGINEER OR ARCHITECT.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2 AND .1.3 FOR
 AUTOMATED LIGHTING CONTROL OF SOME TYPE REQUIRED. IF
 OCC SENSOR TYPE, PLEASE INDICATE MAX TIME OF 30MINS, IF
 TIMER TYPE, PLEASE INDICATE THE MAX OF 4HRS.
  
 3) NOTE:NO, PLEASE SEE THE TABLE/BLOCK AS SHOWN DOES
 NOT CORRELATE. PLEASE SEE THE FIRST THING IS IF USING
 THE SPACE BY SPACE IN TABLE B, THEN PLEASE SEE AREAS
 SHALL BE BROKEN DOWN FOR USE. PLEASE SEE ALL MAY NOT BE
 ONLY SHOWN AS OFFICE, UNLESS ALL IS ONE OPEN OFFICE
 SPACE OR IF ALL ARE INDEED OFFICES.
 PLEASE SEE THE MAX LPD AS SHOWN DOES NOT CORRELATE.
 PLEASE SEE 1.1 TIMES(X) THE SQ FT OF1450 IS NOT 1600.
 (MAY NOT ROUND UP)
 PLEASE SEE THE FIXTURE WATTAGE DOES NOT CORRELATE TO
 THE FIXTURE LEGEND. PLEASE SEE EVEN IF FIXTURES WERE
 58WATTS EACH, 58 TIMES 30 IS 1740 WHICH EXCEEDS THE
 ALLOWANCE EVEN AS SHOWN.
 PLEASE SEE WATTAGE ON EACH FIXTURE IS 64, OR AT LEAST
 BY THE INFORMATION AS SHOWN ON FIXTURE LEGEND WHICH
 WOULD PLACE THE WATTAGE AT 1920.
 PLEASE ADJUST AND SEE TABLE B.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE THE MAX WATTAGE(LIGHTING POWER
 DENSITIES ) PER 13.415.2.ABC.1, (OFFICE, ETC SPACE.)
 CAN BE SHOWN ON A BLOCK ON PLANS.
  
 4) NOTE: OK.
  
 ** NEW NOTE **
  
 1) NOTE: PLEASE CLARIFY IF THE CONTINUOUS LOADS ARE
 SHOWN AT 125%. 215.3, 230.42
 THIS COMMENT WAS NOT MADE ON PREVIOUS REVIEW.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]