2006-12-23 19:11:27 | **UNSAT 2ND REVIEW ** |
| |
| ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW WHICH IS |
| STILL IN NEED OF ADDRESSING. |
| PLEASE SEE NOTES BELOW ARE TAKEN DIRECTLY FROM PREVIOUS |
| REVIEW AND NOTED WITH AN OK, NO WITH FURTHER |
| EXPLANATION. |
| PLEASE SEE SOME MAY BE NOTED NO/OK WHICH WOULD INDICATE |
| COMMENT WAS PARTIALLY ADDRESSED. |
| |
| 1) NOTE: OK. |
| |
| 2) NOTE: OK, HOWEVER SEE WHITE-OUT ON PLANS WHICH IS |
| NOT PERMITTED ON PLANS WHETHER OR NOT THEY ARE SIGNED |
| AND SEALED BY AN ENGINEER OR ARCHITECT. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2 AND .1.3 FOR |
| AUTOMATED LIGHTING CONTROL OF SOME TYPE REQUIRED. IF |
| OCC SENSOR TYPE, PLEASE INDICATE MAX TIME OF 30MINS, IF |
| TIMER TYPE, PLEASE INDICATE THE MAX OF 4HRS. |
| |
| 3) NOTE:NO, PLEASE SEE THE TABLE/BLOCK AS SHOWN DOES |
| NOT CORRELATE. PLEASE SEE THE FIRST THING IS IF USING |
| THE SPACE BY SPACE IN TABLE B, THEN PLEASE SEE AREAS |
| SHALL BE BROKEN DOWN FOR USE. PLEASE SEE ALL MAY NOT BE |
| ONLY SHOWN AS OFFICE, UNLESS ALL IS ONE OPEN OFFICE |
| SPACE OR IF ALL ARE INDEED OFFICES. |
| PLEASE SEE THE MAX LPD AS SHOWN DOES NOT CORRELATE. |
| PLEASE SEE 1.1 TIMES(X) THE SQ FT OF1450 IS NOT 1600. |
| (MAY NOT ROUND UP) |
| PLEASE SEE THE FIXTURE WATTAGE DOES NOT CORRELATE TO |
| THE FIXTURE LEGEND. PLEASE SEE EVEN IF FIXTURES WERE |
| 58WATTS EACH, 58 TIMES 30 IS 1740 WHICH EXCEEDS THE |
| ALLOWANCE EVEN AS SHOWN. |
| PLEASE SEE WATTAGE ON EACH FIXTURE IS 64, OR AT LEAST |
| BY THE INFORMATION AS SHOWN ON FIXTURE LEGEND WHICH |
| WOULD PLACE THE WATTAGE AT 1920. |
| PLEASE ADJUST AND SEE TABLE B. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE INDICATE THE MAX WATTAGE(LIGHTING POWER |
| DENSITIES ) PER 13.415.2.ABC.1, (OFFICE, ETC SPACE.) |
| CAN BE SHOWN ON A BLOCK ON PLANS. |
| |
| 4) NOTE: OK. |
| |
| ** NEW NOTE ** |
| |
| 1) NOTE: PLEASE CLARIFY IF THE CONTINUOUS LOADS ARE |
| SHOWN AT 125%. 215.3, 230.42 |
| THIS COMMENT WAS NOT MADE ON PREVIOUS REVIEW. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| |