Plan Review Notes
Plan Review Notes For Permit 06100894
Permit Number 06100894
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-11-20 12:09:09****UNSAT****
  
  
  
 1.FLORIDA FIRE PREVENTION CODE 2004 EDITION SHALL BE
 REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.SINCE THE SCOPE OF THE WORK WILL REQUIRE
 MODIFICATION OF THE FIRE PROTECTION SYSTEM(S), SEPARATE
 PERMITS AND PLANS WILL BE REQUIRED.
  
 4.AS PER WPB FIRE PREVENTION, DUCT DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM.(MAKE CHANGE TO FIRE
 ALARM NOTE #17, SHEET FA 0.1)
  
 5.CORRECT SPELLING OF "FIRE" ON SHEET FA2.1, KEY NOTE
 #2.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722