2006-10-31 07:01:17 | ** UNSAT ** |
| |
| 1) NOTE: PLEASE BE SURE THE FOLLOWING RELEVANT CODES |
| ARE REFLECTED ON SAID PLANS. |
| 2002 NFPA-70, 2002 NFPA-72, 2003 NFPA-101 . |
| FBC 2004 |
| |
| 2) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2 AND .1.3 |
| FOR AUTOMATED LIGHTING CONTROL OF SOME TYPE REQUIRED. |
| IF OCC SENSOR TYPE, PLEASE INDICATE MAX TIME OF 30MINS, |
| IF TIMER TYPE, PLEASE INDICATE THE MAX OF 4HRS. |
| |
| 3) NOTE: PLEASE INDICATE THE MAX WATTAGE(LIGHTING POWER |
| DENSITIES ) PER 13.415.2.ABC.1, (OFFICE, ETC SPACE.) |
| CAN BE SHOWN ON A BLOCK ON PLANS. |
| |
| 4) NOTE: PLEASE CLARIFY THE 2ND TRANSFORMER SHOWN ON |
| TRANSFORMER SCHEDULE, HOWEVER COULD NOT LOCATE THIS ON |
| RISER, ON PANEL SCHEDULE OR ON PLANS.?? |
| UNABLE TO VERIFY AT THIS TIME. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
2006-10-30 08:04:03 | REMOVED FROM INCOMING , IN ELECTRICAL FOR REVIEW. |