Plan Review Notes
Plan Review Notes For Permit 06100891
Permit Number 06100891
Review Stop FIRE
Sequence Number 6
Notes
Date Text
2008-05-15 13:19:44****UNSAT*****
  
 PLAN SHEETS C8, C10, L1, A0.10, A2.2, FP.02 THRU FP.05,
 E1.1, E1.2, E1.3, E1.7, E1.8, E1.9, AND E2.1 WERE
 STAMPED, INITIALED, AND DATED;FIRE PLAN REVIEW WILL
 BE APPROVED WITH THE UNDERSTANDING THAT THE FOLLOWING
 CORRECTIONS BE MADE TO SHEET FP.01
  
 1.ADDITIONAL DESIGN REQUIREMENTS #1 BE CHANGED TO
 READ WEST PALM BEACH FIRE RESCUE, NOT PALM BEACH COUNTY
 FIRE RESCUE.
  
 2.ELIMINATE FLOW TEST DATA CONDUCTED BY PALM BEACH
 COUNTY FIRE RESCUE.PLEASE BE ADVISED THAT THE FLOW
 TEST DATA TO BE DETERMINED BY WEST PALM BEACH FIRE
 PREVENTION BUREAU.
  
 PLEASE BE ADVISED THAT THIS IS THE SIXTH TIME THAT THIS
 ITEM BE ADDRESSED !!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW