Plan Review Notes
Plan Review Notes For Permit 06100891
Permit Number 06100891
Review Stop B
Sequence Number 6
Notes
Date Text
2008-04-29 15:55:59PERMIT: 06100891
 ADD: 2395 NORTHWOOD UNIVERSITY DR.
 CONT: THE WEITZ CO.
 TEL: (561309-7386
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 4THREVIEW
 ACTION: DENIED
  
 1-7) COMPLIED.
  
 8) BUILDING PROVISO: PRODUCT APPROVALS,
 8(5) PRE-ENGINEERED ROOF HATCH, WILL REQUIRE A LOCAL
 PRODUCT APPROVAL, WILL NEED TO FILL OUT WEST PALM BEACH
 FORM FOR SUBMITTAL FOR LOCAL PRODUCT APPROVAL
 A) WILL REQUIRE THE ACTUAL TESTING REPORT
 FROM WHERE PRESSURES WERE DERIVED
 B) WILL ALSO NEED A THIRD PARTY ENGINEER OR
 AGENCY FOR THIRD PARTY QUALITY ASSURANCE PROGRAM 8(9)
 ROOFING ASSEMBLIES, NO ROOFING PERMIT APPLIED FOR, THE
 MIAMI-DADE REPORT # 04-0716.04 FOR STANDING SEAM METAL
 ROOFING IS OK,
 THE ISSUE IS THE MODIFIED BITUMEN REPORT FL
 644/R2/ 06-0626.05 PAGE 21 OF THE REPORT IS THE SHEET
 INDICATED AS THE SUB-SYSTEM THAT WILL BE INSTALLED ON
 THIS PROJECT. THE MAXIMUM DESIGN PRESSURE LISTED IS
 -52.5 WITH LIMITATION # 7.
 LIMITATION # 7 INDICATES WHEN THE PRESSURES IN
 ZONE 2 & 3 ARE GREATER THAN LISTED IN THE REPORT
 ENHANCED FASTENING MUST OCCUR IN THOUGHS ZONES. THIS
 REPORT REQUIRES THE RAS 117 CALCULATION TO BE SUBMITTED
 AND TO BE SIGNED AND SEALED BY EITHER A LICENSED
 ARCHITECT OR ENGINEER.
 ROOFING PERMIT WILL REQUIRE SEPERATE REVIEW , FEES AND
 ASSOCIATED REVIEW.
  
 9)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 10)THRESHOLD INSPECTION PLANFL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS. THIS BUILDING IS OVER 5,000 SQ FT AND AN
 OCCUPANT LOAD OF 500, THUS REQUIRING A THRESHOLD
 INSPECTION PLAN.
  
 105.13.1*THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 11) THRESHOLD INSPECTOR:
 WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE.CONTACT HAROLD PISKURA MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM AT (561)805-6711 FOR FURTHER
 INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAILCOMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved