Date |
Text |
2008-03-08 16:38:02 | ** DENIED 5TH REVIEW** |
| |
| |
| 1) NOTE: PLEASE SEE PREVIOUS REVIEW SPECIFICALLY |
| REQUESTED FOR A THIRD SET OF ELECTRICAL SHEETS AS ONE |
| SET OF ELECTRICAL PLANS AND ENERGY CALCULATIONS WERE |
| BEING RETAINED BY THIS OFFICE. PLEASE SEE THAT ONE OF |
| THE THREE SETS OF PLANS SUBMITTED ARE MISSING THE THIRD |
| SET OF ELECTRICAL PLANS. THE RETAINED PLANS BY THIS |
| OFFICE MAY NOT BE USED. IN EITHER CASE AS WAS NOTED ON |
| PREVIOUS REVIEW AND NOTES BELOW THERE ARE SHEET(S) |
| WHICH WILL BE REQUIRED TO BE CHANGED OUT ALONG WITH NEW |
| CALCULATIONS. |
| FBC 106.1 REQUIRES TWO COMPLETE SETS OF PLANS AND WHEN |
| A THRESHOLD OR SPECIAL INSPECTOR REQUIRES THREE |
| COMPLETE SETS. |
| ** PLEASE BE SURE TO SUBMIT. |
| |
| 2) NOTE: PLEASE SEE 13-415.1AB.1, 13-415.1.A, 13-415.2, |
| 13-400.3.A. PLEASE COORDINATE ALL LIGHTING IN THE |
| ENERGY CALCULATIONS AND THE INPUT DATA REPORT. |
| PREVIOUS REVIEW(S) NOTED TO SEE LIGHTING FIXTURES SUCH |
| AS H/H1 WHICH ARE SHOWN AS 1005WATT FIXTURES ON THE |
| FIXTURE LEGEND AND NOT THE SAME IN THE IDR.IT WAS |
| NOTED BY THIS OFFICE THAT PERHAPS THIS WAS A MISPRINT |
| HOWEVER THE PLANS ARE STILL SHOWING THESE FIXTURES ON |
| THE FIXTURE LEGEND AS 1005WATTS. |
| PLEASE SEE THESE SAME FIXTURES ON THE IDR ARE SHOWN AS |
| 100W AND 175W. (IDR UNDER LOBBY SHOWS 175W FIXTURES |
| WHEN THE FIXTURE LEGEND DOES NOT SHOW ANY 175W FIXTURES |
| FOR THE FIXTURES AS NOTED ON PLANS. THE PLANS SHOW H |
| AND H1. |
| PLEASE SEE OTHER AREAS OF THE IDR SHOW 100W FOR THE |
| SAME TYPES OF FIXTURES. |
| ** THESE SIMPLY DO NOT CORRELATE. |
| PLEASE SEE MISSING F1 FIXTURES FROM FIXTURE LEGEND. THE |
| COUNT IS ON THE IDR, AND SEEMS TO BE THE SAME TYPE AS F |
| BUT ONLY WITH BATTERY BACK UP HOWEVER AS THIS FIXTURE |
| IS NOT LISTED IT CAN NOT BE ASSUMED. |
| A MINOR ITEM IS THE IDR IS SHORT ONE 96W FIXTURE. THE |
| PLANS SHOW 107 OF THE 96W FIXTURES IN AREAS RTU-1 AND |
| RTU-2. |
| PLEASE SEE THE EXTERIOR LIGHTING IDR WHICH INDICATES |
| SOME FIXTURES BEING REQUIRED BY HEALTH, LIFE SAFETY |
| STATUTE OR ORDINANCE. THERE IS NO KNOWN REQUIREMENT BY |
| ANY STATUTE, OR ORDINANCE KNOWN TO THIS OFFICE. |
| ** PLEASE BE SURE TO SUBMIT THREE SETS AND SEE THE |
| FOLLOWING COMMENT. PLEASE ALSO BE SURE THE OWNER AGENT |
| IS SIGNED ON CERTIFICATION SHEET. |
| |
| 3) NOTE: PLEASE SEE AS NOTED JUST ABOVE, PLEASE BE SURE |
| TO SUBMIT THREE SIGNED, DATED AND SEALED SETS OF ENERGY |
| CALCULATIONS. THE STATE STATUE 471.025 AND FLORIDA |
| ADMINISTRATIVE CODE 61G15-23.002 REQUIRES ALL TO |
| CONTAIN ORIGINAL SIGNATURE, DATE AND RAISED SEAL. MAY |
| NOT SUBMIT COLORED PHOTO-COPIES IN LIEU OF ORIGINAL |
| SIGNATURE DATE AND RAISED SEAL. |
| PLEASE SEE ONLY TWO SETS OF ENERGY CALCULATIONS |
| SUBMITTED CONTAINED ORIGINAL SIGNATURES, DATES AND |
| RAISED SEALS. |
| |
| 4) NOTE: PLEASE SEE AS STATED ON PREVIOUS REVIEW DUE TO |
| THE REVIEWS, SUBMITTED DOCUMENTS ALONG THE WAY THE |
| ENERGY CALCULATIONS HAVE NOT BEEN REVIEWED THREE |
| CONSECUTIVE TIMES. PLEASE KNOW THAT WITH RESPECT TO FS |
| 553.80(2)(B) AND REPEAT CODE COMPLIANCE COMMENTS. |
| PLEASE KNOW THIS OFFICE WILL BE REQUIRED TO ASSESS THE |
| FINE AS REQUIRED BY THE STATE STATUTE OF $50, 400 ON |
| THE NEXT REVIEW IF THESE CODE SECTIONS ARE REPEATED. |
| ** PLEASE BE SURE TO GO OVER ALL ITEMS AND COORDINATE |
| PLANS WITH THE IDR. |
| |
| ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |