Plan Review Notes
Plan Review Notes For Permit 06100891
Permit Number 06100891
Review Stop E
Sequence Number 5
Notes
Date Text
2008-03-08 16:38:02** DENIED 5TH REVIEW**
  
  
 1) NOTE: PLEASE SEE PREVIOUS REVIEW SPECIFICALLY
 REQUESTED FOR A THIRD SET OF ELECTRICAL SHEETS AS ONE
 SET OF ELECTRICAL PLANS AND ENERGY CALCULATIONS WERE
 BEING RETAINED BY THIS OFFICE. PLEASE SEE THAT ONE OF
 THE THREE SETS OF PLANS SUBMITTED ARE MISSING THE THIRD
 SET OF ELECTRICAL PLANS. THE RETAINED PLANS BY THIS
 OFFICE MAY NOT BE USED. IN EITHER CASE AS WAS NOTED ON
 PREVIOUS REVIEW AND NOTES BELOW THERE ARE SHEET(S)
 WHICH WILL BE REQUIRED TO BE CHANGED OUT ALONG WITH NEW
 CALCULATIONS.
 FBC 106.1 REQUIRES TWO COMPLETE SETS OF PLANS AND WHEN
 A THRESHOLD OR SPECIAL INSPECTOR REQUIRES THREE
 COMPLETE SETS.
 ** PLEASE BE SURE TO SUBMIT.
  
 2) NOTE: PLEASE SEE 13-415.1AB.1, 13-415.1.A, 13-415.2,
 13-400.3.A. PLEASE COORDINATE ALL LIGHTING IN THE
 ENERGY CALCULATIONS AND THE INPUT DATA REPORT.
 PREVIOUS REVIEW(S) NOTED TO SEE LIGHTING FIXTURES SUCH
 AS H/H1 WHICH ARE SHOWN AS 1005WATT FIXTURES ON THE
 FIXTURE LEGEND AND NOT THE SAME IN THE IDR.IT WAS
 NOTED BY THIS OFFICE THAT PERHAPS THIS WAS A MISPRINT
 HOWEVER THE PLANS ARE STILL SHOWING THESE FIXTURES ON
 THE FIXTURE LEGEND AS 1005WATTS.
 PLEASE SEE THESE SAME FIXTURES ON THE IDR ARE SHOWN AS
 100W AND 175W. (IDR UNDER LOBBY SHOWS 175W FIXTURES
 WHEN THE FIXTURE LEGEND DOES NOT SHOW ANY 175W FIXTURES
 FOR THE FIXTURES AS NOTED ON PLANS. THE PLANS SHOW H
 AND H1.
 PLEASE SEE OTHER AREAS OF THE IDR SHOW 100W FOR THE
 SAME TYPES OF FIXTURES.
 ** THESE SIMPLY DO NOT CORRELATE.
 PLEASE SEE MISSING F1 FIXTURES FROM FIXTURE LEGEND. THE
 COUNT IS ON THE IDR, AND SEEMS TO BE THE SAME TYPE AS F
 BUT ONLY WITH BATTERY BACK UP HOWEVER AS THIS FIXTURE
 IS NOT LISTED IT CAN NOT BE ASSUMED.
 A MINOR ITEM IS THE IDR IS SHORT ONE 96W FIXTURE. THE
 PLANS SHOW 107 OF THE 96W FIXTURES IN AREAS RTU-1 AND
 RTU-2.
 PLEASE SEE THE EXTERIOR LIGHTING IDR WHICH INDICATES
 SOME FIXTURES BEING REQUIRED BY HEALTH, LIFE SAFETY
 STATUTE OR ORDINANCE. THERE IS NO KNOWN REQUIREMENT BY
 ANY STATUTE, OR ORDINANCE KNOWN TO THIS OFFICE.
 ** PLEASE BE SURE TO SUBMIT THREE SETS AND SEE THE
 FOLLOWING COMMENT. PLEASE ALSO BE SURE THE OWNER AGENT
 IS SIGNED ON CERTIFICATION SHEET.
  
 3) NOTE: PLEASE SEE AS NOTED JUST ABOVE, PLEASE BE SURE
 TO SUBMIT THREE SIGNED, DATED AND SEALED SETS OF ENERGY
 CALCULATIONS. THE STATE STATUE 471.025 AND FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002 REQUIRES ALL TO
 CONTAIN ORIGINAL SIGNATURE, DATE AND RAISED SEAL. MAY
 NOT SUBMIT COLORED PHOTO-COPIES IN LIEU OF ORIGINAL
 SIGNATURE DATE AND RAISED SEAL.
 PLEASE SEE ONLY TWO SETS OF ENERGY CALCULATIONS
 SUBMITTED CONTAINED ORIGINAL SIGNATURES, DATES AND
 RAISED SEALS.
  
 4) NOTE: PLEASE SEE AS STATED ON PREVIOUS REVIEW DUE TO
 THE REVIEWS, SUBMITTED DOCUMENTS ALONG THE WAY THE
 ENERGY CALCULATIONS HAVE NOT BEEN REVIEWED THREE
 CONSECUTIVE TIMES. PLEASE KNOW THAT WITH RESPECT TO FS
 553.80(2)(B) AND REPEAT CODE COMPLIANCE COMMENTS.
 PLEASE KNOW THIS OFFICE WILL BE REQUIRED TO ASSESS THE
 FINE AS REQUIRED BY THE STATE STATUTE OF $50, 400 ON
 THE NEXT REVIEW IF THESE CODE SECTIONS ARE REPEATED.
 ** PLEASE BE SURE TO GO OVER ALL ITEMS AND COORDINATE
 PLANS WITH THE IDR.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  