2008-04-07 14:17:39 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| |
| FAC FLORIDA ADMINISTRATIVE CODE |
| FSFLORIDA STATUTE |
| |
| 1-7. BUILDING PROVISOS. |
| |
| 8. SEE PREVIOUS LIST REGARDING LOCAL PRODUCT APPROVAL |
| FOR ROOF HATCH, FAC9B72.PLEASE SEE ATTACHED, A COPY |
| OF THE LOCAL PRODUCT APPROVAL FOR A NYSTROM ROOF HATCH |
| FOR THE RHG3630T MODEL, AS AN EXAMPLE OF THE PAPERWORK |
| WHICH MAY BE SUBMITTED FOR APPLICATION FOR LOCAL |
| PRODUCT APPROVAL.THE PAPERWORK SUBMITTED IS FOR THE |
| RHA SERIES ROOF HATCH.A FLORIDA STATE OR LOCAL |
| PRODUCT APPROVAL FOR THE ROOF HATCH IS REQUIRED PRIOR |
| TO INSTALLATION.IF NOT APPROVED PRIOR TO PERMIT |
| ISSUANCE, THIS WILL BE A PROVISO ITEM. |
| |
| ENHANCED FASTENING AND APPROVED ASSEMBLY INFORMATION |
| FOR THE ROOF WILL BE REQUIRED UNDER SEPARATE PERMIT. |
| |
| 9.IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY, |
| 561-233-5025.THE PLANS MUST BE STAMPED AND THE |
| RECEIPT ATTACHED TO THE APPLICATION. |
| |
| NEW COMMENTS: |
| |
| 10.SEE PREVIOUS LISTS REGARDING THRESHOLD BUILDING |
| REQUIREMENTS.THE THRESHOLD INSPECTION PLAN AND |
| RESIDENT INSPECTOR AGREEMENT ARE TO REMAIN IN THE |
| PACKAGE.THE PRECONSTRUCTION MEETING AND APPROVAL OF |
| THE RESIDENT INSPECTOR MUST BE FACILITATED BY HAROLD |
| PISKURA, INSEPCTION SERVICES, 561-805-6711, PRIOR TO |
| PERMIT ISSUANCE.I SPOKE WITH THE CONTRACTOR ON THE |
| TELEPHONE, AND HE SAID THAT THIS WAS ALREADY DONE, BUT |
| HAROLD PISKURA SAID THAT THIS WAS NOT DONE.PLEASE |
| NOTE THAT FAILURE TO ADDRESS THESE ITEMS WILL RESULT IN |
| PERMIT DELAYS, ESPECIALLY AS THE DESIGNER HAS DECLARED |
| AN ASSEMBLY OCCUPANCY BUILDING (THEREFORE, THIS IS A |
| THRESHOLD JOB, STATUTORY REQUIREMENT FS553.71(7)). |
| |
| 11.A BUILDING REVIEW OF ENERGY CALCS IS REQUIRED |
| EVERY TIME THAT A NEW ENERGY CALC IS SUBMITTED.PLEASE |
| CONFIRM THAT ALL BUILDING COMPONENTS ON THE PLAN ARE |
| INCLUDED IN THE ENERGY CALC SUCH AS DOORS, WINDOWS, |
| INSULATION, HOT WATER HEATER, COFFERED CEILINGS, |
| CORRECT FLOOR AREA, ETC.PLEASE HAVE THE DESIGNER |
| CONFIRM THAT ALL COMPONENTS WERE INCLUDED IN THE ENERGY |
| CALC INPUT DATA REPORT.FAILURE TO DO SO WILL RESULT |
| IN PERMIT ISSUANCE DELAYS. |
| |