2007-11-02 16:45:15 | ** PLANS WERE REMOVED FROM INCOMING. PLANS ROUTED TO |
| BUILDING REVIEWER AFTER ELECTRICAL REVIEW WSA |
| COMPLETED. PLANS WILL BE PLACED ON THE COMM BOARD AFTER |
| BUILDING REVIEW. |
2007-11-02 16:44:10 | |
| ** DENIED 4TH REVIEW ** |
| |
| *** PLEASE SEE AS THE ENERGY CALCULATIONS WERE NOT |
| SUBMITTED ON THE PREVIOUS REVIEW AS STATED IN NOTE # 2 |
| DATED 6/4/07 A REVIEW ON THE ENERGY CALCULATIONS WERE |
| NOT ABLE TO BE DONE UNTIL THIS REVIEW. |
| REVIEW OF OTHER PREVIOUS CODE COMMENTS WAS DONE. |
| |
| 1) NOTE: PLEASE SEE THE ENERGY CALCULATIONS AS |
| SUBMITTED ARE IN NEED OF COMPLIANCE WITH THE FBC |
| CHAPTER 13. |
| PLEASE SEE THE VERSION AS NOW SUBMITTED IS INCORRECT |
| FOR THE PERMIT APPLIED DATE. THIS PROJECT WAS SUBMITTED |
| UNDER THE 2004 FBC BEFORE THE DECEMBER 8TH, 2006 |
| CHANGES THEREFORE THE VERSION AS ADOPTED SHOULD BE |
| 2.11. |
| 13-415.1.A, 13- 400.3.A |
| PLEASE SEE THAT THE INFORMATION ON THE INPUT DATA |
| REPORT DOES NOT CORRELATE WITH LIGHTING AS SHOWN ON |
| PLANS. ANY REFERENCE TO THE INPUT DATA REPORT ON THE |
| COMMENT AS NOTED WILL BE ABBREVIATED AS IDR. |
| PLEASE SEE THE AMOUNT OF FIXTURES AND WATTAGES OF |
| FIXTURES ON THE IDR DO NOT MATCH WITH THE FIXTURES ON |
| PLANS. |
| FOR EXAMPLE: PLEASE SEE THE EXTERIOR LIGHTING FIXTURES |
| WHICH ON PLANS ACTUALLY SHOW MORE FIXTURES THAN IN |
| CALCULATIONS. SEE THAT FIXTURE *C* IS ACTUALLY |
| MISSING. |
| PLEASE SEE THE INTERIOR LIGHTING AS THERE IS FIXTURES |
| ON PLANS WHICH ARE NOT IN THE IDR. FOR EXAMPLE: |
| FIXTURES H, H1, J, L ARE NOT IN THE IDR. FIXTURE H, IS |
| SHOWN AS 1005 WATTS ON THE LIGHTING FIXTURE SCHEDULE |
| WHICH APPEARS TO BE A MISPRINT. PLEASE SEE THE IDR AS |
| THESE FIXTURES ABOVE WHICH ARE 75W AND 100W FIXTURES |
| ARE NOT LISTED AT ALL. |
| PLEASE SEE THE NUMBER OF FIXTURES IN ROOMS AND OTHER |
| AREAS ARE MISSING. FOR EXAMPLE: WHERE ARE THE FIXTURES |
| *H* IN THE IDR? |
| |
| ** THESE ARE SOME EXAMPLES GIVEN. |
| PLEASE COORDINATE ALL LIGHTING ON PLANS AND FIXTURE |
| SCHEDULE WITH THE ENERGY CALCULATIONS AND THE INPUT |
| DATA REPORTS. |
| ** PLEASE SEE THE OWNER AGENT WILL NEED TO SIGN THE |
| CERTIFICATION SHEET ALSO. |
| |
| 2) NOTE: PLEASE KNOW AS THE ENERGY CALCULATIONS WERE |
| NOT SUBMITTED PREVIOUSLY FS 553.80(2)(B) DOES NOT APPLY |
| AT THIS TIME. PLEASE BE SURE TO COORDINATE. |
| ** PLEASE KNOW THAT ONE SET OF ELECTRICAL PLANS AND ONE |
| SET OF ENERGY CALCULATIONS ARE BEING RETAINED BY THIS |
| OFFICE. |
| WHEN RESUBMITTING PLANS PLEASE BE SURE TO INCLUDE ONE |
| NEW ELECTRICAL SET IN THE THIRD SET OF PLANS. |
| ** IF ANY ELECTRICAL SHEETS ARE BEING REPLACED IN OTHER |
| TWO SETS DUE TO NOTES ABOVE, PLEASE REMOVE OLD/VOIDED |
| SHEETS AND INSERT NEW SHEETS INTO SETS. |
| |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |