Notes
Date Text
2007-11-02 16:45:15** PLANS WERE REMOVED FROM INCOMING. PLANS ROUTED TO
 BUILDING REVIEWER AFTER ELECTRICAL REVIEW WSA
 COMPLETED. PLANS WILL BE PLACED ON THE COMM BOARD AFTER
 BUILDING REVIEW.
2007-11-02 16:44:10 
 ** DENIED 4TH REVIEW **
  
 *** PLEASE SEE AS THE ENERGY CALCULATIONS WERE NOT
 SUBMITTED ON THE PREVIOUS REVIEW AS STATED IN NOTE # 2
 DATED 6/4/07 A REVIEW ON THE ENERGY CALCULATIONS WERE
 NOT ABLE TO BE DONE UNTIL THIS REVIEW.
 REVIEW OF OTHER PREVIOUS CODE COMMENTS WAS DONE.
  
 1) NOTE: PLEASE SEE THE ENERGY CALCULATIONS AS
 SUBMITTED ARE IN NEED OF COMPLIANCE WITH THE FBC
 CHAPTER 13.
 PLEASE SEE THE VERSION AS NOW SUBMITTED IS INCORRECT
 FOR THE PERMIT APPLIED DATE. THIS PROJECT WAS SUBMITTED
 UNDER THE 2004 FBC BEFORE THE DECEMBER 8TH, 2006
 CHANGES THEREFORE THE VERSION AS ADOPTED SHOULD BE
 2.11.
 13-415.1.A, 13- 400.3.A
 PLEASE SEE THAT THE INFORMATION ON THE INPUT DATA
 REPORT DOES NOT CORRELATE WITH LIGHTING AS SHOWN ON
 PLANS. ANY REFERENCE TO THE INPUT DATA REPORT ON THE
 COMMENT AS NOTED WILL BE ABBREVIATED AS IDR.
 PLEASE SEE THE AMOUNT OF FIXTURES AND WATTAGES OF
 FIXTURES ON THE IDR DO NOT MATCH WITH THE FIXTURES ON
 PLANS.
 FOR EXAMPLE: PLEASE SEE THE EXTERIOR LIGHTING FIXTURES
 WHICH ON PLANS ACTUALLY SHOW MORE FIXTURES THAN IN
 CALCULATIONS. SEE THAT FIXTURE *C* IS ACTUALLY
 MISSING.
 PLEASE SEE THE INTERIOR LIGHTING AS THERE IS FIXTURES
 ON PLANS WHICH ARE NOT IN THE IDR. FOR EXAMPLE:
 FIXTURES H, H1, J, L ARE NOT IN THE IDR. FIXTURE H, IS
 SHOWN AS 1005 WATTS ON THE LIGHTING FIXTURE SCHEDULE
 WHICH APPEARS TO BE A MISPRINT. PLEASE SEE THE IDR AS
 THESE FIXTURES ABOVE WHICH ARE 75W AND 100W FIXTURES
 ARE NOT LISTED AT ALL.
 PLEASE SEE THE NUMBER OF FIXTURES IN ROOMS AND OTHER
 AREAS ARE MISSING. FOR EXAMPLE: WHERE ARE THE FIXTURES
 *H* IN THE IDR?
  
 ** THESE ARE SOME EXAMPLES GIVEN.
 PLEASE COORDINATE ALL LIGHTING ON PLANS AND FIXTURE
 SCHEDULE WITH THE ENERGY CALCULATIONS AND THE INPUT
 DATA REPORTS.
 ** PLEASE SEE THE OWNER AGENT WILL NEED TO SIGN THE
 CERTIFICATION SHEET ALSO.
  
 2) NOTE: PLEASE KNOW AS THE ENERGY CALCULATIONS WERE
 NOT SUBMITTED PREVIOUSLY FS 553.80(2)(B) DOES NOT APPLY
 AT THIS TIME. PLEASE BE SURE TO COORDINATE.
 ** PLEASE KNOW THAT ONE SET OF ELECTRICAL PLANS AND ONE
 SET OF ENERGY CALCULATIONS ARE BEING RETAINED BY THIS
 OFFICE.
 WHEN RESUBMITTING PLANS PLEASE BE SURE TO INCLUDE ONE
 NEW ELECTRICAL SET IN THE THIRD SET OF PLANS.
 ** IF ANY ELECTRICAL SHEETS ARE BEING REPLACED IN OTHER
 TWO SETS DUE TO NOTES ABOVE, PLEASE REMOVE OLD/VOIDED
 SHEETS AND INSERT NEW SHEETS INTO SETS.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  