Text |
2007-11-05 10:17:43 | PERMIT: 06100891 |
| ADD: 2395 NORTHWOOD UNIVERSITY DR. |
| CONT: THE WEITZ CO. |
| TEL: (561309-7386 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 4THREVIEW |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2 ) FL S S 713.13 |
| NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT BEFORE A |
| PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS |
| NOT ACTUALLY COMMENCED |
| WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. |
| |
| 3-4) COMPLIED. |
| |
| 5) BUILDING PROVISO: 109.3.10* IMPACT OF CONSTRUCTION. |
| ALL CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL |
| BE PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT |
| THE CONDITION OF ADJACENT PROPERTY, UNLESS SUCH |
| ACTIVITY IS PERMITTED TO AFFECT SAID PROPERTY PURSUANT |
| TO A CONSENT BY THE APPLICABLE PROPERTY OWNER, UNDER |
| TERMS & CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY |
| OWNER. THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL |
| OF DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND |
| THE STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION |
| ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE |
| WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY |
| REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH |
| ENGINEERING STANDARDS TO PRESERVE THE |
| POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY, |
| DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW |
| RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS, |
| PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING |
| PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ |
| FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A |
| PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED |
| DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS |
| PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A |
| CERTIFICATION FROM A LICENSED ENGINEER SHALL BE |
| SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL |
| OF THE FINAL INSPECTION. |
| |
| 6) BUILDING PROVISO: 109.3.10.1 HURRICANE PROTECTION. |
| IT SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW |
| CONSTRUCTION RELATED MATERIALS EQUIPMENT AND DEBRIS TO |
| REMAIN LOOSE OR OTHERWISE UNSECURED AT A CONSTRUCTION |
| SITE FROM 24 HRS. AFTER A HURRICANE WATCH HAS BEEN |
| ISSUED UNTIL THE HURRICANE WATCH OR WARNING HAS BEEN |
| LIFTED. ALL SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND |
| DEBRIS SHALL BE EITHER REMOVED FROM THE CONSTRUCTION |
| SITE OR SECURED IN SUCH A MANNER AS TO MINIMIZE THE |
| DANGER OF SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND |
| DEBRIS CAUSING DAMAGE TO PERSONS OR PROPERTY FROM HIGH |
| WINDS. ANY PERSONS WHO FAILS TO COMPLY TO REMOVE OR |
| SECURE THE CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS |
| WITHIN 24 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED |
| SHALL BE SUBJECT TO A FINE NOT TO EXCEED $500.00.IN |
| ADDITION TO THE ABOVE, A LICENSED CONTRACTOR WHO |
| VIOLATES THIS SECTION SHALL BE SUBJECT TO DISCIPLINE |
| PURSUANT TO SECTION 113 OF THIS CHAPTER. |
| |
| 7) BUILDING PROVISO: THE BUILD OUT FOR THE EXCHANGE |
| CITY AND FINANCE PARK WILL BE UNDER A SEPERATE PERMIT. |
| |
| 8) BUILDING PROVISO: PRODUCT APPROVALS, |
| 8(5) PRE-ENGINEERED ROOF HATCH, WILL REQUIRE A LOCAL |
| PRODUCT APPROVAL, WILL NEED TO FILL OUT WEST PALM BEACH |
| FORM FOR SUBMITTAL FOR LOCAL PRODUCT APPROVAL |
| A) WILL REQUIRE THE ACTUAL TESTING REPORT |
| FROM WHERE PRESSURES WERE DERIVED |
| B) WILL ALSO NEED A THIRD PARTY ENGINEER OR |
| AGENCY FOR THIRD PARTY QUALITY ASSURANCE PROGRAM 8(9) |
| ROOFING ASSEMBLIES, NO ROOFING PERMIT APPLIED FOR, THE |
| MIAMI-DADE REPORT # 04-0716.04 FOR STANDING SEAM METAL |
| ROOFING IS OK, |
| THE ISSUE IS THE MODIFIED BITUMEN REPORT FL |
| 644/R2/ 06-0626.05 PAGE 21 OF THE REPORT IS THE SHEET |
| INDICATED AS THE SUB-SYSTEM THAT WILL BE INSTALLED ON |
| THIS PROJECT. THE MAXIMUM DESIGN PRESSURE LISTED IS |
| -52.5 WITH LIMITATION # 7. |
| LIMITATION # 7 INDICATES WHEN THE PRESSURES IN |
| ZONE 2 & 3 ARE GREATER THAN LISTED IN THE REPORT |
| ENHANCED FASTENING MUST OCCUR IN THOUGHS ZONES. THIS |
| REPORT REQUIRES THE RAS 117 CALCULATION TO BE SUBMITTED |
| AND TO BE SIGNED AND SEALED BY EITHER A LICENSED |
| ARCHITECT OR ENGINEER. |
| ROOFING PERMIT WILL REQUIRE SEPERATE REVIEW , FEES AND |
| ASSOCIATED REVIEW. |
| |
| 9)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| REQUIREMENT, THE SPECIFIC |
| REQUIREMENT SHALL BE APPLICABLE. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |