Plan Review Notes
Plan Review Notes For Permit 06100891
Permit Number 06100891
Review Stop P
Sequence Number 2
Notes
Date Text
2007-02-15 18:08:05DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
  
 FROM PREVIOUS REVIEW:
  
 1. OK
  
 2. SHT 2 0F 2 SHALL BE SIGNED, SEALED, AND DATED AS
 REQUIRED BY THE FLORIDA STATUTES AND SECTION 106.1.
 ****RESPONSE NOTED, BUT SHT 202 IS NOT SIGNED, SEALED,
 DATED AS REQUIRED.
  
 3. OK
 4. OK
 5. OK
 6. OK
 7. OK
  
 8. SHT A2.2 DETAIL 2/A2.2 DOES NOT REFLECT THE LOWER
 ROOF PLAN SHOWN ON SHT A1.30. THE LOWER ROOF PLAN
 INDICATES 2 10" DIA. SCUPPERS ON THE EAST ELEVATION.
 THE DETAIL SHOWS 1 RECTANGULAR SCUPPER. PLEASE
 CORRELATE THE DETAIL & ROOF PLAN INFORMATION. SECTION
 106.1.1.
 ****RESPONSE NOTED, BUT ELEVATION 2/A2.2 NOW SHOWS 2
 RECTANGLES.
  
 9.OK
 10. OK
 11. OK
  
 12. SHTS A4.10 & A4.11 SHOW THE FOLLOWING ACCESSIBLE
 REQUIREMENTS:
 FOR THE W/C'S:
 A. OK
 B. OK
 C. OK
 FOR THE STALLS:
 A. OK
 FOR THE URINALS:
 A. OK
 B. OK
 FOR THE LAVS:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 ****RESPONSE NOTED, BUT ALL LAVS SHALL BE 2'10" HIGH
 AND SHALL HAVE A KNEE CLEARANCE OF 2'9". SHOW ON ALL
 LAVS.
 B. OK
 C. OK
 FOR THE SHOWERS:
 A. 11-4.21.2 SIZE & CLEARANCES
 ****RESPONSE NOTED, BUT THE SHOWERS SHALL BE 36"X36".
 SHOWERS ARE SHOWN AS 38"X38".
 B. OK
 C. OK
 D. OK
 E. OK
  
 13. SHT A4.23 FINISH SCHEDULE. INDICATE HOW PAINTED GWB
 COMPLIES WITH THE "HARD" SURFACE REQUIRED IN SECTION
 1210.2. THE REQUIREMENT IS FOR A SMOOTH, HARD,
 NONABSORBENT SURFACE.
 ****RESPONSE NOTED, BUT "EPOXY PAINT" DOES NOT COMPLY
 WITH THE REQUIREMENT.
  
 14. OK
 15. OK
 16. OK
  
 17. SHT P1.1 RWL TO BE 10" @ 10,666SF. TABLE 1106.3. -
 10" @15,566SF TO READ 16,566SF. RECHECK ADDITION.
 SECTION 106.1.1. - 15" @28,862SF TO READ 26,862SF.
 PLEASE RECHECK ADDITION. SECTION 106.1.1. ****RESPONSE
 NOTED, BUT ADDITION NOT CORRECT. PLEASE RECHECK
 ADDITION OF AREA AND VERTICAL WALL CONTRIBUTION, AND
 TOTAL SQUARE FOOTAGE AS IT ACCUMULATES IN THE SYSTEM.
  
 18. OK
 19. OK
 20. OK
 21. OK
  
 22. SHT P2-1 SANITARY RISER 3R/P2-1 NO P1 FIXTURE SHOWN
 & SHOWER IS INDICATED AS A FLOOR DRAIN. PLEASE
 CORRELATE RISER AND FLOOR PLAN. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT NOW A FIXTURE P-1 IS MISSING
 FROM THE RISER DIAGRAM.
  
 23. OK
 24. OK
  
 25. SHT P2-2 STORM RISER DIAGRAM. 15" @ 28,862SF TO
 READ 15" 26,862SF. PLEASE CHECK ADDITION. SECTION
 106.1.1. - 10" @ 15,566SF TO READ 10" 16,566SF. - 8" @
 10,666SF IS REQUIRED TO BE 10" ON THE HORIZONTAL ABOVE
 AND BELOW RISER. TABLE 1106.3.
 ****RESPONSE NOTED, BUT ADDITION STILL INCORRECT.
 PLEASE RECHECK ALL ADDITION IN SYSTEM.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. SUBMITTING ONE SET
 OF PLANS FROM THIS REVIEW SEPARATELY, FOR COMPARISON,
 WILL HELP TO EXPEDITE YOUR PERMIT ALSO. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]