Date |
Text |
2007-02-15 18:08:05 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| FBC-2004 BUILDING |
| |
| FROM PREVIOUS REVIEW: |
| |
| 1. OK |
| |
| 2. SHT 2 0F 2 SHALL BE SIGNED, SEALED, AND DATED AS |
| REQUIRED BY THE FLORIDA STATUTES AND SECTION 106.1. |
| ****RESPONSE NOTED, BUT SHT 202 IS NOT SIGNED, SEALED, |
| DATED AS REQUIRED. |
| |
| 3. OK |
| 4. OK |
| 5. OK |
| 6. OK |
| 7. OK |
| |
| 8. SHT A2.2 DETAIL 2/A2.2 DOES NOT REFLECT THE LOWER |
| ROOF PLAN SHOWN ON SHT A1.30. THE LOWER ROOF PLAN |
| INDICATES 2 10" DIA. SCUPPERS ON THE EAST ELEVATION. |
| THE DETAIL SHOWS 1 RECTANGULAR SCUPPER. PLEASE |
| CORRELATE THE DETAIL & ROOF PLAN INFORMATION. SECTION |
| 106.1.1. |
| ****RESPONSE NOTED, BUT ELEVATION 2/A2.2 NOW SHOWS 2 |
| RECTANGLES. |
| |
| 9.OK |
| 10. OK |
| 11. OK |
| |
| 12. SHTS A4.10 & A4.11 SHOW THE FOLLOWING ACCESSIBLE |
| REQUIREMENTS: |
| FOR THE W/C'S: |
| A. OK |
| B. OK |
| C. OK |
| FOR THE STALLS: |
| A. OK |
| FOR THE URINALS: |
| A. OK |
| B. OK |
| FOR THE LAVS: |
| A. 11-4.19.2 HEIGHT & CLEARANCES |
| ****RESPONSE NOTED, BUT ALL LAVS SHALL BE 2'10" HIGH |
| AND SHALL HAVE A KNEE CLEARANCE OF 2'9". SHOW ON ALL |
| LAVS. |
| B. OK |
| C. OK |
| FOR THE SHOWERS: |
| A. 11-4.21.2 SIZE & CLEARANCES |
| ****RESPONSE NOTED, BUT THE SHOWERS SHALL BE 36"X36". |
| SHOWERS ARE SHOWN AS 38"X38". |
| B. OK |
| C. OK |
| D. OK |
| E. OK |
| |
| 13. SHT A4.23 FINISH SCHEDULE. INDICATE HOW PAINTED GWB |
| COMPLIES WITH THE "HARD" SURFACE REQUIRED IN SECTION |
| 1210.2. THE REQUIREMENT IS FOR A SMOOTH, HARD, |
| NONABSORBENT SURFACE. |
| ****RESPONSE NOTED, BUT "EPOXY PAINT" DOES NOT COMPLY |
| WITH THE REQUIREMENT. |
| |
| 14. OK |
| 15. OK |
| 16. OK |
| |
| 17. SHT P1.1 RWL TO BE 10" @ 10,666SF. TABLE 1106.3. - |
| 10" @15,566SF TO READ 16,566SF. RECHECK ADDITION. |
| SECTION 106.1.1. - 15" @28,862SF TO READ 26,862SF. |
| PLEASE RECHECK ADDITION. SECTION 106.1.1. ****RESPONSE |
| NOTED, BUT ADDITION NOT CORRECT. PLEASE RECHECK |
| ADDITION OF AREA AND VERTICAL WALL CONTRIBUTION, AND |
| TOTAL SQUARE FOOTAGE AS IT ACCUMULATES IN THE SYSTEM. |
| |
| 18. OK |
| 19. OK |
| 20. OK |
| 21. OK |
| |
| 22. SHT P2-1 SANITARY RISER 3R/P2-1 NO P1 FIXTURE SHOWN |
| & SHOWER IS INDICATED AS A FLOOR DRAIN. PLEASE |
| CORRELATE RISER AND FLOOR PLAN. SECTION 106.1.1. |
| ****RESPONSE NOTED, BUT NOW A FIXTURE P-1 IS MISSING |
| FROM THE RISER DIAGRAM. |
| |
| 23. OK |
| 24. OK |
| |
| 25. SHT P2-2 STORM RISER DIAGRAM. 15" @ 28,862SF TO |
| READ 15" 26,862SF. PLEASE CHECK ADDITION. SECTION |
| 106.1.1. - 10" @ 15,566SF TO READ 10" 16,566SF. - 8" @ |
| 10,666SF IS REQUIRED TO BE 10" ON THE HORIZONTAL ABOVE |
| AND BELOW RISER. TABLE 1106.3. |
| ****RESPONSE NOTED, BUT ADDITION STILL INCORRECT. |
| PLEASE RECHECK ALL ADDITION IN SYSTEM. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. SUBMITTING ONE SET |
| OF PLANS FROM THIS REVIEW SEPARATELY, FOR COMPARISON, |
| WILL HELP TO EXPEDITE YOUR PERMIT ALSO. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |