Plan Review Notes
Plan Review Notes For Permit 06100891
Permit Number 06100891
Review Stop M
Sequence Number 2
Notes
Date Text
2007-03-01 14:47:53-----------------2ND REVIEW--------------
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER
 RESPONSES:
  
 COMMENT #1: THE REQUIREMENTS OF FBC,M 307.2.1 AND
 307.2.2 HAVE BEEN SATISFIED. HOWEVER, THE ISSUE OF
 AUXILIARY AND SECONDARY DRAIN SYSTEMS (FBC,M 307.2.3)
 HAS NOT BEEN ADEQUATELY ADDRESSED. THERE ARE NO
 PROVISIONS FOR THE RTU'S, WHICH HAVE THE POTENTIAL TO
 OVERFLOW INTO THE BUILDING SHOULD THE PRIMARY DRAIN
 CEASE TO FUNCTION. THERE IS ALSO NO INDICATION THAT THE
 FLOOR IN STORAGE ROOMS 117 AND 129 ARE DESIGNED IN SUCH
 A WAY AS TO ENSURE THAT CONDENSATE OVERFLOW WILL BE
 DIRECTED ONLY IN THE DIRECTION OF THE FLOOR DRAIN, THUS
 PREVENTING CONDENSATE OVERFLOW FROM DAMAGING ANY
 BUILDING COMPONENTS. THE INSTALLATION OF A WATER LEVEL
 DETECTION DEVICE IN THE PRIMARY PAN OF THE AHUS AND THE
 RTUS WOULD BE IN COMPLIANCE WITH FBC,M 307.2.3(2).
  
 COMMENT #2: PLEASE INDICATE ON PLANS THAT THE RTU AND
 ACCU ROOF ATTACHMENTS HAVE BEEN DESIGNED TO MEET THE
 140MPH WIND LOAD REQUIREMENTS OF FBC CHAPTER 16.
  
 COMMENT #3: OK
  
 COMMENT #4: ADDRESSED IN COMMENT #2.
  
 COMMENT #5: OK