2007-03-06 18:50:10 | ****DENIED***** | | | | | | MOST OF THE COMMENTS TAKEN FROM THE PREVIOUS FIRE PLAN | | REVIEW OF 12/14/2006HAVE BEEN SATISFIED WITH THE | | EXCEPTION OF THE FOLLOWING WHICH STILL NEED TO BE | | ADDRESSED: | | | | | | 4.LANDSCAPING SHALL NOT OBSTRUCT OR INTERFERE WITH | | FIRE PROTECTION EQUIPMENT.PROPER CLEARANCES SHALL BE | | MAINTAINED AT ALL TIMES.ADD NOTATION TO SHEET L-1 | | | | | | 9.SHOW/DISPLAY THE NUMERICAL ADDRESS OF THE BUILDING | | ON THE PROPER ELEVATION.AS PER WEST PALM BEACH CODE, | | NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND 1" IN | | WIDTH CONTRASTING TO THEIR BACKGROUND.ALTHOUGH THE | | NUMERICAL ADDRESS IS ON A MONUMENT SIGN OR MARQUEE, | | HOWEVER, AS PER WPB CODE A NUMERICAL ADDRESS IS STILL | | REQUIRED ON THE BUILDING. DISPLAY ON THE APPROPIATE | | EXTERIOR ELEVATION | | | | | | | | 11. PROVIDE LAYOUT OF THE (A.) FIRE SPRINKLER SYSTEM | | AND (B.) FIRE ALARM SYSTEM FOR THE BUILDING.(A.)AS | | PER AMENDMENTS TO THE FLORIDA BUILDING CODE,CHAPTER 1, | | ADMINISTRATION, 2004 EDITION 106.3.5.1.1(5) CITY | | AMENDMENTS, FIRE SPRINKLER SCHEMATIC/LAYOUT REQUIRED | | FOR PLAN REVIEW(B.)PROVIDE A SCHEMATIC/LAYOUT OF | | THE FIRE ALARM SYSTEM INDEPENDENT OF THE ELECTRICAL | | PLANS | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED. | | | | | | CAPT. MICHAEL A.WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|