Plan Review Notes
Plan Review Notes For Permit 06100891
Permit Number 06100891
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2007-03-06 18:50:10****DENIED*****
  
  
 MOST OF THE COMMENTS TAKEN FROM THE PREVIOUS FIRE PLAN
 REVIEW OF 12/14/2006HAVE BEEN SATISFIED WITH THE
 EXCEPTION OF THE FOLLOWING WHICH STILL NEED TO BE
 ADDRESSED:
  
  
 4.LANDSCAPING SHALL NOT OBSTRUCT OR INTERFERE WITH
 FIRE PROTECTION EQUIPMENT.PROPER CLEARANCES SHALL BE
 MAINTAINED AT ALL TIMES.ADD NOTATION TO SHEET L-1
  
  
 9.SHOW/DISPLAY THE NUMERICAL ADDRESS OF THE BUILDING
 ON THE PROPER ELEVATION.AS PER WEST PALM BEACH CODE,
 NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND 1" IN
 WIDTH CONTRASTING TO THEIR BACKGROUND.ALTHOUGH THE
 NUMERICAL ADDRESS IS ON A MONUMENT SIGN OR MARQUEE,
 HOWEVER, AS PER WPB CODE A NUMERICAL ADDRESS IS STILL
 REQUIRED ON THE BUILDING. DISPLAY ON THE APPROPIATE
 EXTERIOR ELEVATION
  
  
  
 11. PROVIDE LAYOUT OF THE (A.) FIRE SPRINKLER SYSTEM
 AND (B.) FIRE ALARM SYSTEM FOR THE BUILDING.(A.)AS
 PER AMENDMENTS TO THE FLORIDA BUILDING CODE,CHAPTER 1,
 ADMINISTRATION, 2004 EDITION 106.3.5.1.1(5) CITY
 AMENDMENTS, FIRE SPRINKLER SCHEMATIC/LAYOUT REQUIRED
 FOR PLAN REVIEW(B.)PROVIDE A SCHEMATIC/LAYOUT OF
 THE FIRE ALARM SYSTEM INDEPENDENT OF THE ELECTRICAL
 PLANS
  
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A.WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722