2007-02-16 14:27:51 | PLEASE PROVIDE FOLLOWING INFO: |
| |
| 1. STANDARD NOTES OF CITY OF WPB ARE MINIMUM STANDARDS. |
| YOU CAN UPGRADE CITY'S STANDARDS BUT, STILL WE WOULD |
| LIKE YOU TO SAY ON THE DRAWING THAT YOU WILL MEET |
| MINIMUM CITY'S STANDARDS FOR SIDEWALK WIDTH , ITS |
| SLOPE, DRIVEWAY, PARKING, HANDICAP PARKING, PAINT ETC. |
| PER CITY CODES OR BETTER APPROVED BY THE CITY., MUST |
| MEET PER ADA,,ETC., |
| 2.DUMPSTER LOCATION MUST BE ACCESSIBLE FOR PICKUP |
| TRUCK. |
| 3. PLEASE PROVIDE A COPY OF SFWMD PERMIT OR MODIFIED |
| PERMIT, |
| 4. YOU SAID IN YOUR RESPONSE THAT YOU SENT STORM WATER |
| CALCULATION TO WINDEL PALMER. WINDEL PALMER DOES NOT |
| REVIEW STORM WATER. EITHER MYSELF OR STEVE SARLEY |
| REVIEW STORM WATER. I TALKED TO STEVE SARLEY HE DOES |
| NOT HAVE STORM WATER CALCULATION FOR THIS PROJECT. |
| PLEASE PROVIDE STORM WATER CALCULATIONS FOR WATER |
| QUALITY. WHAT CRITERIA YOU ASSUMEDFOR RUNOFF CAL.,, |
| LIKE 1" OVER ENTIRE SITE OR2.5"CRITERIA, ? |
| PERVIOUS AREA, LIKE GREEN, LAKES, ETC,IMPERVIOUS AREA |
| CAL., |
| 5. WHAT IS THE SITE AREA, YOU ARE DEVELOPING FOR THIS |
| PROJECT ONLY ? SO, WE CAN CHECK PERVIOUS, IMPERVIOUS |
| CAL. |
| 6. PLEASE SHOW DETAIL OF THE CONTROL STRUCTURES WITH |
| ELEVATIONS, NOTCHES, BLEEDING ELEVATION, ETC DID YOU |
| USE EXFILTRATION TRENCH ? |
| 7. POLLUTION PREVENTION DETAILS,HEIGHT OF THE SILT |
| FENCE, CLOTHES USED FOR SILT ETC., PLANS SHOWING SILT |
| FENCE AROUND THE SITE |
| |
| PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR |
| PERMITTING PROCESS |
| |
| RASIK CHOKSHI805-6723 |