Plan Review Notes
Plan Review Notes For Permit 06100891
Permit Number 06100891
Review Stop E
Sequence Number 2
Notes
Date Text
2007-02-05 12:39:23******* UNSAT 2ND REVIEW ******
  
 *** PLEASE SEE THERE ARE ITEMS FROM THE PREVIOUS REVIEW
 WHICH STILL NEED TO BE ADDRESSED ALONG WITH NEW
 COMMENTS BASED ON CHANGES IN PLANS AND NEW INFORMATION
 AND/OR CHANGES MADE TO PLANS.
  
 **** IMPORTANT****
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 THE PREVIOUS REVIEW WITH A *NO*, *OK* OR *NO/OK*.
  
 A) A, NO WILL CONTAIN A FURTHER EXPLANATION AS TO WHY
 THE COMMENT MAY NOT HAVE BEEN FULLY ADDRESSED WITH THE
 PREVIOUS REVIEW NOTE BELOW WITH **PREVIOUS REVIEW NOTE
 #1**
  
 B) A, OK, WILL HAVE NO COMMENTS EXCEPT PERHAPS A
 REFERENCE TO SEE ** NEW NOTES*. THE PREVIOUS REVIEW
 NOTE WILL BE REMOVED.
  
 C) A, NO/OK, WILL HAVE FURTHER EXPLANATION AS PART OF
 THE COMMENT MAY HAVE BEEN ADDRESSED, HOWEVER NOT ALL.
 THE PREVIOUS REVIEW NOTE WILL BE NOTED **PREVIOUS
 REVIEW NOTE #1**
  
 D) NEW NOTES WILL BE ADDED TO THE END AND LABELED **
 NEW NOTES **
  
  
  
  
  
 ** PLEASE SEE SOME OF THE COMMENTS BELOW DO NO PERTAIN
 TO JLRD ENGINEERING AND ARE BEING NOTED AT THIS TIME.
  
 1) NOTE: OK, ADDRESS IS TO BE REVISED IN OUR SYSTEM
  
 2) NOTE: NO, PLEASE SEE SHEET 2OF 2 DOES NOT CONTAIN
 THE SAME SIGNATURE AS SHEETS 1 OR 3 AND IS ALSO NOT
 DATED. PLEASE SEE THE SIGNATURE IS COMPLETELY
 DIFFERENT.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SEE SOME SURVEY/ SITE SHEETS ARE NOT SIGNED AND
 SEALED. SEEMS SOME WERE MISSED. FS 472.025
  
 3) NOTE: NO, PLEASE SEE MOST WAS DONE, HOWEVER PLEASE
 SEE THERE IS ONE OR TWO SHEETS WHICH ONLY CONTAIN A
 SIGNATURE AND ARE NOT SEALED.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1 **
 PLEASE SEE "C" SHEETS, ARE ALSO NOT SIGNED, DATED OR
 SEALED. PLEASE SEE COMMENTS FROM ENGINEERING REVIEWER.
 FS 481/471
  
 4) NOTE: NO, PLEASE SEE ATTACHED TEXT PULLED FROM THE
 FAC.
 *61G1-16.002 DESCRIPTION OF SEAL.
 (1) THE SEAL SHALL CONTAIN THE NAME OF ONLY ONE
 ARCHITECT OR INTERIOR DESIGNER AND THE REGISTRATION
 NUMBER; THE SEAL OF THE ARCHITECT SHALL BE CIRCULAR,
 AND THE SEAL OF THE INTERIOR DESIGNER SHALL BE
 HEXAGONAL. BOTH SEALS SHALL BE APPROXIMATELY 2" IN
 DIAMETER WITH TWO CIRCULAR LINES BETWEEN WHICH LINES
 SHALL APPEAR, AT THE TOP, THE WORDS ?STATE OF FLORIDA?
 AND AT THE BOTTOM THE WORDS ?REGISTERED ARCHITECT? OR
 ?LICENSED INTERIOR DESIGNER,? WHICHEVER IS APPLICABLE.
 (2) ANY INDIVIDUAL WHO IS BOTH A REGISTERED ARCHITECT
 AND A LICENSED INTERIOR DESIGNER MUST USE A SEAL WHICH
 CONTAINS BOTH THE ARCHITECT AND INTERIOR DESIGN
 REGISTRATION NUMBERS, IN SUCH A MANNER:
  
 THIS MAY HAVE ONLY BEEN COMMENTED ON BY THIS REVIEWER,
 HOWEVER IT IS STILL REQUIRED EVEN IF COMMENT IS NOT
 MADE BY ANY OTHER TRADE.
  
  
 * PREVIOUS REVIEW NOTE REVIEW #1*
 PLEASE SEE MINIMUM SIZE SEAL REQUIRED FOR LANDSCAPE
 ARCHITECT PER FAC 61G1-16.002. *THIS IS ONLY NOTED BY
 THIS REVIEWER*
  
 5) NOTE: OK, HOWEVER SEE COMMENTS FOR PERFORMANCE
 CALCULATIONS.
  
 6) NOTE: OK.
  
 7) NOTE: OK.
  
 8) NOTE: OK.
  
 9) NOTE: OK.
  
 10) NOTE: NO/OK, PLEASE SEE PARTS OF THIS COMMENT HAVE
 BEEN ADDRESSED HOWEVER FURTHER INFORMATION IS STILL
 NEEDED.
 PLEASE SEE SOME OF THE NOTES FROM THE PREVIOUS REVIEW
 STILL ALSO APPLY.
 PLEASE PROVIDE ALL MAXIMUM OVER RIDE TIMES FOR DEVICES
 AS SET-FORTH IN THE FBC. PLEASE SEE THAT OC TYPE
 DEVICES ARE A MAXIMUM OF 30MINS AND TIMER TYPE OVER
 RIDES ARE 4HRS (AS STATED).
 PLEASE SEE THAT SWITCH SYMBOLS ON PLANS WHICH CORRELATE
 WITH SYMBOL LEGEND LENDS TO STANDARD DEVICE
 DESIGNATIONS WHICH THESE DEVICES WOULD NOT COORDINATE
 WITH THE PROPOSED SYSTEM. PLEASE SEE THAT THE NEW
 SYSTEM AND LOCATION OF THE OC DEVICES AND CORRECT
 COVERAGE IS STILL IN QUESTION.
 PLEASE SEE SOME ROOMS WHICH DO NOT INDICATE ANY DEVICES
 AND/OR SOME ROOMS WHICH INDICATE TWO *CEILING DEVICES?*
 WHICH SEEM TO BE LOCATED ON A WALL IN THE SAME LOCATION
 OF THE (CONFERENCE ROOM) ETC.
 PLEASE SEE ALL OVER THE OTHER SWITCHES IN LARGE OPEN
 AREAS ARE NOT CLEAR AT THIS TIME.
 PLEASE SEE LIMITS ON THE SPACE AND SQUARE FEET OF
 CONTROL..
 PLEASE SEE THE ALL ENTRANCES TO A SPACE/AREA SHALL
 CONTAIN AN OVER RIDE DEVICE OF SOME TYPE TO CONTROL
 LIGHTING FOR INGRESS INTO SPACE. THIS CONTROL IS
 REQUIRED TO BE READILY ACCESSIBLE AT THOSE ENTRANCES.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SEE 2004 FBC CHAPTER 13.
 A) PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND .1.3.
 B) PLEASE SHOW A DETAILED SYSTEM WHICH IS REQUIRED. C)
 PLEASE PROVIDE SCHEDULING OF SYSTEM.
 D) PLEASE PROVIDE ALL OVER RIDE DEVICES AT THE
 LOCATIONS FOR THE OCCUPANTS TO OVER RIDE SYSTEM, THESE
 DEVICES ARE REQUIRED TO BE LOCATED SO THE OCCUPANT CAN
 VISUALLY SEE THE LIGHTING BEING CONTROLLED.
 E) PLEASE PROVIDE ALL TIMES FOR OVER RIDE DEVICES.
 (30MINS MAX FOR OCC SENSOR TYPE DEVICES AND 4HRS MAX
 FOR TIMER TYPE DEVICES).
 F) PLEASE SEE ALL SPACES, AND ROOMS WHICH CONTAIN FLOOR
 TO CEILING HEIGHT PARTITIONS SHALL ALL CONTAIN OVER
 RIDE DEVICES OF SOME SORT WHICH WILL AUTOMATICALLY SHUT
 OFF LIGHTING ON THOSE AREAS. (OFFICES, STORAGE ROOMS,
 CONFERENCE ROOMS, ETC)
 G) PLEASE SEE 13-415.1.AB.1, 13-415.1.A, IF USING
 METHOD "A", PLEASE SEE AS SUBMITTED ALL ARE SHOWN A
 MANUAL ON/OFF, WHICH WOULD CHANGE TO AUTO.
 PLEASE ALSO SEE 13-415.2
 H) PLEASE SEE AREAS GREATER THAN 10K SQ FT.
 13-415.1.ABC.1.2, PLEASE SEE AREAS LARGER THAN 25K SQ
 FT 13-415.1.ABC.1.1
  
 11) NOTE: OK.
  
 12) NOTE: OK. SEE NEW NOTES.
  
 13) NOTE: NO/OK, PLEASE SEE GFP PROTECTION IS NOW BEING
 SHOWN ON THE HDP WHICH INDICATES A MCB; HOWEVER THE GFP
 PROTECTION IS REQUIRED AT THE SERVICE ENTRANCE MAIN.
 230.95, 240.13.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SEE HDP IS BEING SHOWN ON SCHEDULE WITH "GFI"
 PROTECTION, HOWEVER PLEASE SEE 240.13, 230.95, THIS
 WOULD BE "GF" PROTECTION AS "GFI" IS FOR PERSONNEL
 PROTECTION.
  
 14) NOTE: OK.
  
 15) NOTE: OK.
  
 ** NEW NOTES **
  
 16) NOTE: PLEASE SEE AN EQUIPMENT GROUNDING CONDUCTOR
 IS NOT SHOWN FROM THE NEW MAIN TO THE MCB HDP. 250.6,
 250.24B, 250.110, 250.122
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-02-05 06:58:412007-02-05 06:58:41
 REVIEW IN PROGRESS
2007-02-04 20:02:212007-02-04 20:02:21
 IN ELEC FOR REVIEW