2007-02-05 12:39:23 | ******* UNSAT 2ND REVIEW ****** |
| |
| *** PLEASE SEE THERE ARE ITEMS FROM THE PREVIOUS REVIEW |
| WHICH STILL NEED TO BE ADDRESSED ALONG WITH NEW |
| COMMENTS BASED ON CHANGES IN PLANS AND NEW INFORMATION |
| AND/OR CHANGES MADE TO PLANS. |
| |
| **** IMPORTANT**** |
| |
| ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM |
| THE PREVIOUS REVIEW WITH A *NO*, *OK* OR *NO/OK*. |
| |
| A) A, NO WILL CONTAIN A FURTHER EXPLANATION AS TO WHY |
| THE COMMENT MAY NOT HAVE BEEN FULLY ADDRESSED WITH THE |
| PREVIOUS REVIEW NOTE BELOW WITH **PREVIOUS REVIEW NOTE |
| #1** |
| |
| B) A, OK, WILL HAVE NO COMMENTS EXCEPT PERHAPS A |
| REFERENCE TO SEE ** NEW NOTES*. THE PREVIOUS REVIEW |
| NOTE WILL BE REMOVED. |
| |
| C) A, NO/OK, WILL HAVE FURTHER EXPLANATION AS PART OF |
| THE COMMENT MAY HAVE BEEN ADDRESSED, HOWEVER NOT ALL. |
| THE PREVIOUS REVIEW NOTE WILL BE NOTED **PREVIOUS |
| REVIEW NOTE #1** |
| |
| D) NEW NOTES WILL BE ADDED TO THE END AND LABELED ** |
| NEW NOTES ** |
| |
| |
| |
| |
| |
| ** PLEASE SEE SOME OF THE COMMENTS BELOW DO NO PERTAIN |
| TO JLRD ENGINEERING AND ARE BEING NOTED AT THIS TIME. |
| |
| 1) NOTE: OK, ADDRESS IS TO BE REVISED IN OUR SYSTEM |
| |
| 2) NOTE: NO, PLEASE SEE SHEET 2OF 2 DOES NOT CONTAIN |
| THE SAME SIGNATURE AS SHEETS 1 OR 3 AND IS ALSO NOT |
| DATED. PLEASE SEE THE SIGNATURE IS COMPLETELY |
| DIFFERENT. |
| |
| ** PREVIOUS REVIEW NOTE REVIEW #1** |
| PLEASE SEE SOME SURVEY/ SITE SHEETS ARE NOT SIGNED AND |
| SEALED. SEEMS SOME WERE MISSED. FS 472.025 |
| |
| 3) NOTE: NO, PLEASE SEE MOST WAS DONE, HOWEVER PLEASE |
| SEE THERE IS ONE OR TWO SHEETS WHICH ONLY CONTAIN A |
| SIGNATURE AND ARE NOT SEALED. |
| |
| ** PREVIOUS REVIEW NOTE REVIEW #1 ** |
| PLEASE SEE "C" SHEETS, ARE ALSO NOT SIGNED, DATED OR |
| SEALED. PLEASE SEE COMMENTS FROM ENGINEERING REVIEWER. |
| FS 481/471 |
| |
| 4) NOTE: NO, PLEASE SEE ATTACHED TEXT PULLED FROM THE |
| FAC. |
| *61G1-16.002 DESCRIPTION OF SEAL. |
| (1) THE SEAL SHALL CONTAIN THE NAME OF ONLY ONE |
| ARCHITECT OR INTERIOR DESIGNER AND THE REGISTRATION |
| NUMBER; THE SEAL OF THE ARCHITECT SHALL BE CIRCULAR, |
| AND THE SEAL OF THE INTERIOR DESIGNER SHALL BE |
| HEXAGONAL. BOTH SEALS SHALL BE APPROXIMATELY 2" IN |
| DIAMETER WITH TWO CIRCULAR LINES BETWEEN WHICH LINES |
| SHALL APPEAR, AT THE TOP, THE WORDS ?STATE OF FLORIDA? |
| AND AT THE BOTTOM THE WORDS ?REGISTERED ARCHITECT? OR |
| ?LICENSED INTERIOR DESIGNER,? WHICHEVER IS APPLICABLE. |
| (2) ANY INDIVIDUAL WHO IS BOTH A REGISTERED ARCHITECT |
| AND A LICENSED INTERIOR DESIGNER MUST USE A SEAL WHICH |
| CONTAINS BOTH THE ARCHITECT AND INTERIOR DESIGN |
| REGISTRATION NUMBERS, IN SUCH A MANNER: |
| |
| THIS MAY HAVE ONLY BEEN COMMENTED ON BY THIS REVIEWER, |
| HOWEVER IT IS STILL REQUIRED EVEN IF COMMENT IS NOT |
| MADE BY ANY OTHER TRADE. |
| |
| |
| * PREVIOUS REVIEW NOTE REVIEW #1* |
| PLEASE SEE MINIMUM SIZE SEAL REQUIRED FOR LANDSCAPE |
| ARCHITECT PER FAC 61G1-16.002. *THIS IS ONLY NOTED BY |
| THIS REVIEWER* |
| |
| 5) NOTE: OK, HOWEVER SEE COMMENTS FOR PERFORMANCE |
| CALCULATIONS. |
| |
| 6) NOTE: OK. |
| |
| 7) NOTE: OK. |
| |
| 8) NOTE: OK. |
| |
| 9) NOTE: OK. |
| |
| 10) NOTE: NO/OK, PLEASE SEE PARTS OF THIS COMMENT HAVE |
| BEEN ADDRESSED HOWEVER FURTHER INFORMATION IS STILL |
| NEEDED. |
| PLEASE SEE SOME OF THE NOTES FROM THE PREVIOUS REVIEW |
| STILL ALSO APPLY. |
| PLEASE PROVIDE ALL MAXIMUM OVER RIDE TIMES FOR DEVICES |
| AS SET-FORTH IN THE FBC. PLEASE SEE THAT OC TYPE |
| DEVICES ARE A MAXIMUM OF 30MINS AND TIMER TYPE OVER |
| RIDES ARE 4HRS (AS STATED). |
| PLEASE SEE THAT SWITCH SYMBOLS ON PLANS WHICH CORRELATE |
| WITH SYMBOL LEGEND LENDS TO STANDARD DEVICE |
| DESIGNATIONS WHICH THESE DEVICES WOULD NOT COORDINATE |
| WITH THE PROPOSED SYSTEM. PLEASE SEE THAT THE NEW |
| SYSTEM AND LOCATION OF THE OC DEVICES AND CORRECT |
| COVERAGE IS STILL IN QUESTION. |
| PLEASE SEE SOME ROOMS WHICH DO NOT INDICATE ANY DEVICES |
| AND/OR SOME ROOMS WHICH INDICATE TWO *CEILING DEVICES?* |
| WHICH SEEM TO BE LOCATED ON A WALL IN THE SAME LOCATION |
| OF THE (CONFERENCE ROOM) ETC. |
| PLEASE SEE ALL OVER THE OTHER SWITCHES IN LARGE OPEN |
| AREAS ARE NOT CLEAR AT THIS TIME. |
| PLEASE SEE LIMITS ON THE SPACE AND SQUARE FEET OF |
| CONTROL.. |
| PLEASE SEE THE ALL ENTRANCES TO A SPACE/AREA SHALL |
| CONTAIN AN OVER RIDE DEVICE OF SOME TYPE TO CONTROL |
| LIGHTING FOR INGRESS INTO SPACE. THIS CONTROL IS |
| REQUIRED TO BE READILY ACCESSIBLE AT THOSE ENTRANCES. |
| |
| ** PREVIOUS REVIEW NOTE REVIEW #1** |
| PLEASE SEE 2004 FBC CHAPTER 13. |
| A) PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND .1.3. |
| B) PLEASE SHOW A DETAILED SYSTEM WHICH IS REQUIRED. C) |
| PLEASE PROVIDE SCHEDULING OF SYSTEM. |
| D) PLEASE PROVIDE ALL OVER RIDE DEVICES AT THE |
| LOCATIONS FOR THE OCCUPANTS TO OVER RIDE SYSTEM, THESE |
| DEVICES ARE REQUIRED TO BE LOCATED SO THE OCCUPANT CAN |
| VISUALLY SEE THE LIGHTING BEING CONTROLLED. |
| E) PLEASE PROVIDE ALL TIMES FOR OVER RIDE DEVICES. |
| (30MINS MAX FOR OCC SENSOR TYPE DEVICES AND 4HRS MAX |
| FOR TIMER TYPE DEVICES). |
| F) PLEASE SEE ALL SPACES, AND ROOMS WHICH CONTAIN FLOOR |
| TO CEILING HEIGHT PARTITIONS SHALL ALL CONTAIN OVER |
| RIDE DEVICES OF SOME SORT WHICH WILL AUTOMATICALLY SHUT |
| OFF LIGHTING ON THOSE AREAS. (OFFICES, STORAGE ROOMS, |
| CONFERENCE ROOMS, ETC) |
| G) PLEASE SEE 13-415.1.AB.1, 13-415.1.A, IF USING |
| METHOD "A", PLEASE SEE AS SUBMITTED ALL ARE SHOWN A |
| MANUAL ON/OFF, WHICH WOULD CHANGE TO AUTO. |
| PLEASE ALSO SEE 13-415.2 |
| H) PLEASE SEE AREAS GREATER THAN 10K SQ FT. |
| 13-415.1.ABC.1.2, PLEASE SEE AREAS LARGER THAN 25K SQ |
| FT 13-415.1.ABC.1.1 |
| |
| 11) NOTE: OK. |
| |
| 12) NOTE: OK. SEE NEW NOTES. |
| |
| 13) NOTE: NO/OK, PLEASE SEE GFP PROTECTION IS NOW BEING |
| SHOWN ON THE HDP WHICH INDICATES A MCB; HOWEVER THE GFP |
| PROTECTION IS REQUIRED AT THE SERVICE ENTRANCE MAIN. |
| 230.95, 240.13. |
| |
| ** PREVIOUS REVIEW NOTE REVIEW #1** |
| PLEASE SEE HDP IS BEING SHOWN ON SCHEDULE WITH "GFI" |
| PROTECTION, HOWEVER PLEASE SEE 240.13, 230.95, THIS |
| WOULD BE "GF" PROTECTION AS "GFI" IS FOR PERSONNEL |
| PROTECTION. |
| |
| 14) NOTE: OK. |
| |
| 15) NOTE: OK. |
| |
| ** NEW NOTES ** |
| |
| 16) NOTE: PLEASE SEE AN EQUIPMENT GROUNDING CONDUCTOR |
| IS NOT SHOWN FROM THE NEW MAIN TO THE MCB HDP. 250.6, |
| 250.24B, 250.110, 250.122 |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |