Plan Review Notes
Plan Review Notes For Permit 06100891
Permit Number 06100891
Review Stop P
Sequence Number 1
Notes
Date Text
2006-12-19 12:58:24DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
  
 1. PER ADDRESSING, THE ADDRESS FOR THE STILES-NICHOLSON
 CENTER IS 2395 NORTHWOOD UNIVERSITY DRIVE. ALL SHEETS
 WITH AN ADDRESS IN THE TITLE BLOCK SHALL BE CORRECTED,
 INCLUDING THE FRONT COVER SHEET. THE ADDRESS SHALL BE
 CORRECTED ON THE APPLICATION FOR PERMIT AS WELL.
  
 2. SHT 2 0F 2 SHALL BE SIGNED, SEALED, AND DATED AS
 REQUIRED BY THE FLORIDA STATUTES AND SECTION 106.1.
  
 3. ALL CIVIL SHEETS SHALL BE SIGNED, SEALED, AND DATED
 AS REQUIRED BY THE FLORIDA STATUTES AND SECTION 106.1.
  
 4. SHT C8 METER ASSEMBLY DETAIL INDICATES A 2" RPZV
 BACKFLOW WITH A 2-1/2" WATER SERVICE. PER TABLE
 603.1(D), ALL SECONDARY BACKFLOWS AND ASSEMBLIES SHALL
 BE AT LEAST THE SAME SIZE AS THE LINE IN WHICH THEY ARE
 INSTALLED. A 2-1/2" BACKFLOW IS REQUIRED.
  
 5. SHTS L1, L2, I1, & I2. THE FIRM NAME, ADDRESS &
 PHONE NUMBER ARE REQUIRED IN THE TITLE BLOCK. FAC
 61G1-16.004(1) & FS 481.306.
  
 6. SHT A0.10 - OCCUPANCY IS INDICATED AS MIXED, A3 & B.
 SUBMIT CALCULATIONS FOR MINIMUM FACILITIES FOR EACH
 OCCUPANCY PER TABLES 1004.1.2 & 403.1. INDICATE THE
 SQUARE FOOTAGE FOR EACH OCCUPANCY. INDICATE COMPLIANCE
 WITH SECTION 403.1.1 POTTY PARITY FOR THE A3
 OCCUPANCY.
  
 7. SHT A1.30 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS. SHOW THE SQUARE FOOT AREA OF
 EACH ROOF DRAIN, WITH 1/2 AREA OF ALL VERTICAL WALLS
 ADDED, AS WELL AS ANY ROOF AREA THAT DRAINS ONTO THE
 ROOF AREAS FROM ABOVE IN THE CALCULATIONS. SECTIONS
 1106 & 1107 WITH ALL SUBSECTIONS.
  
 8. SHT A2.2 DETAIL 2/A2.2 DOES NOT REFLECT THE LOWER
 ROOF PLAN SHOWN ON SHT A1.30. THE LOWER ROOF PLAN
 INDICATES 2 10" DIA. SCUPPERS ON THE EAST ELEVATION.
 THE DETAIL SHOWS 1 RECTANGULAR SCUPPER. PLEASE
 CORRELATE THE DETAIL & ROOF PLAN INFORMATION. SECTION
 106.1.1.
  
 9. SHT A4.01 DETAIL 1. THE ACCESSIBLE STALLS DO NOT
 MEET THE CODE REQUIREMENT FOR NEW STALLS. A LAV IS
 REQUIRED IN THE ACCESSIBLE STALL. PLEASE SEE SECTION
 11-4.17.3 EXCEPTION(1)(2) AND FIG. 11-30(E). (ALSO
 CORRECT STALL CONDITION ON SHEETS A0.10, A1.10, A1.11,
 A1.13, AND ANY RELEVANT PLUMBING SHEETS.
  
 10. SHT A4.01 BOYS (114 - 138) & GIRLS (115 - 137)
 TOILET ROOMS, THE TURNING AREA SHALL BE SHOWN IN THE
 TOILET ROOM, NOT THE ACCESSIBLE STALL. SECTION
 11-4.22.3.
  
 11. SHT A4.01 SHOW THE CLEAR FLOOR SPACE FOR THE
 ACCESSIBLE URINALS IN TOILET ROOMS 114 & 138 PER
 SECTION 11-4.18.3.
  
 12. SHTS A4.10 & A4.11 SHOW THE FOLLOWING ACCESSIBLE
 REQUIREMENTS:
 FOR THE W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.3 HEIGHT
 C. 11-4.16.6 DISPENSERS
 FOR THE STALLS:
 A. 11-4.17.3 SIZE & ARRANGEMENT (EXCEPTION NEW CONST.
 (1)(2)) & FIG. 11-30E.
 FOR THE URINALS:
 A. 11-4.18.3 CLEAR FLOOR SPACE
 B. 11-4.18.4 FLUSH CONTROLS
 FOR THE LAVS:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
 FOR THE SHOWERS:
 A. 11-4.21.2 SIZE & CLEARANCES
 B. 11-4.21.3 SEAT
 C. 11-4.21.4 GRAB BARS
 D. 11-4.21.5 CONTROLS
 E. 11-4.21.6 SHOWER UNIT
  
 13. SHT A4.23 FINISH SCHEDULE. INDICATE HOW PAINTED GWB
 COMPLIES WITH THE "HARD" SURFACE REQUIRED IN SECTION
 1210.2. THE REQUIREMENT IS FOR A SMOOTH, HARD,
 NONABSORBENT SURFACE.
  
 14. SHT P0.1 WATER HEATER "A" DETAIL THERMAL EXPANSION
 CONTROL IS REQUIRED BY SECTION 607.3.2. INDICATE
 METHOD.
  
 15. SHT P0.1 PLUMBING NOTES #5. AIR CHAMBERS ARE NOT
 APPROVED. PLEASE DELETE REFERENCE. SECTION 604.9 &
 PDI-WH 201.
  
 16. SHT P1.1 SANT. LINE TO WASH MACHINE BOX SHALL BE 3"
 PER SECTION 406.3.
  
 17. SHT P1.1 RWL TO BE 10" @ 10,666SF. TABLE 1106.3. -
 10" @15,566SF TO READ 16,566SF. RECHECK ADDITION.
 SECTION 106.1.1. - 15" @28,862SF TO READ 26,862SF.
 PLEASE RECHECK ADDITION. SECTION 106.1.1.
  
 18. SHTSP1.2 & P1.3.8" RWL 10,666SF TO BE 10" ON
 THE HORIZONTAL BLDG DRAIN AND THE HORIZONTAL BRANCH
 DRAIN PRIOR TO A DOWNSTREAM OF RWL. TABLE 1106.3.
  
 19. SHT P2.1 RISER 2R/P2-1 DOES NOT REFLECT THE FLOOR
 PLAN. NO PIPING TO HOSE BIBBS SHOWN AND NO PIPING TO
 THE DRINKING FOUNTAINS SHOWN. PLEASE CORRELATE RISER &
 FLOOR PLAN. INDICATE "REVERSE FOR TOILET ROOMS 114 &
 115. SECTION 106.1.1.
  
 20. DOMESTIC WATER RISER 11R/P2-1 NO WATER SUPPLY
 PIPING SHOWN TO THE WASH MACHINE CONNECTION BOX. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 21. SHT P2-1 SANITARY RISER 10R/P2-1 DRY HORIZONTAL
 VENTS ARE NOT APPROVED PER SECTIONS 905.3 & 905.4. (SEE
 RED LINE EXAMPLE ON SHEET TO CORRECT CODE VIOLATION.
  
 22. SHT P2-1 SANITARY RISER 3R/P2-1 NO P1 FIXTURE SHOWN
 & SHOWER IS INDICATED AS A FLOOR DRAIN. PLEASE
 CORRELATE RISER AND FLOOR PLAN. SECTION 106.1.1.
  
 23. SHT P2-1 WATER RISER 4R/P2-1 WATER HAMMER ARRESTORS
 SHALL BE LOCATED NEAR THE FIXTURE IN AN "EFFECTIVE
 RANGE" NOT IN THE CEILING AS SHOWN. PDI-WH 201 AND
 MANUF. INSTALLATION INSTRUCTIONS.
  
 24. SHT P2-1 SANITARY WASTE RISER DIAGRAM, 1R/ P2-1
 INDICATE ON THE PLANS THAT THE RISER IS "REVERSE FOR
 TOILET ROOMS 114 & 115".
  
 25. SHT P2-2 STORM RISER DIAGRAM. 15" @ 28,862SF TO
 READ 15" 26,862SF. PLEASE CHECK ADDITION. SECTION
 106.1.1. - 10" @ 15,566SF TO READ 10" 16,566SF. - 8" @
 10,666SF IS REQUIRED TO BE 10" ON THE HORIZONTAL ABOVE
 AND BELOW RISER. TABLE 1106.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. SUBMITTING ONE SET
 OF PLANS FROM THIS REVIEW SEPARATELY, FOR COMPARISON,
 WILL HELP TO EXPEDITE YOUR PERMIT ALSO. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved