Date |
Text |
2006-12-19 12:58:24 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| FBC-2004 BUILDING |
| |
| 1. PER ADDRESSING, THE ADDRESS FOR THE STILES-NICHOLSON |
| CENTER IS 2395 NORTHWOOD UNIVERSITY DRIVE. ALL SHEETS |
| WITH AN ADDRESS IN THE TITLE BLOCK SHALL BE CORRECTED, |
| INCLUDING THE FRONT COVER SHEET. THE ADDRESS SHALL BE |
| CORRECTED ON THE APPLICATION FOR PERMIT AS WELL. |
| |
| 2. SHT 2 0F 2 SHALL BE SIGNED, SEALED, AND DATED AS |
| REQUIRED BY THE FLORIDA STATUTES AND SECTION 106.1. |
| |
| 3. ALL CIVIL SHEETS SHALL BE SIGNED, SEALED, AND DATED |
| AS REQUIRED BY THE FLORIDA STATUTES AND SECTION 106.1. |
| |
| 4. SHT C8 METER ASSEMBLY DETAIL INDICATES A 2" RPZV |
| BACKFLOW WITH A 2-1/2" WATER SERVICE. PER TABLE |
| 603.1(D), ALL SECONDARY BACKFLOWS AND ASSEMBLIES SHALL |
| BE AT LEAST THE SAME SIZE AS THE LINE IN WHICH THEY ARE |
| INSTALLED. A 2-1/2" BACKFLOW IS REQUIRED. |
| |
| 5. SHTS L1, L2, I1, & I2. THE FIRM NAME, ADDRESS & |
| PHONE NUMBER ARE REQUIRED IN THE TITLE BLOCK. FAC |
| 61G1-16.004(1) & FS 481.306. |
| |
| 6. SHT A0.10 - OCCUPANCY IS INDICATED AS MIXED, A3 & B. |
| SUBMIT CALCULATIONS FOR MINIMUM FACILITIES FOR EACH |
| OCCUPANCY PER TABLES 1004.1.2 & 403.1. INDICATE THE |
| SQUARE FOOTAGE FOR EACH OCCUPANCY. INDICATE COMPLIANCE |
| WITH SECTION 403.1.1 POTTY PARITY FOR THE A3 |
| OCCUPANCY. |
| |
| 7. SHT A1.30 SUBMIT CALCULATIONS FOR PRIMARY AND |
| SECONDARY ROOF DRAINS. SHOW THE SQUARE FOOT AREA OF |
| EACH ROOF DRAIN, WITH 1/2 AREA OF ALL VERTICAL WALLS |
| ADDED, AS WELL AS ANY ROOF AREA THAT DRAINS ONTO THE |
| ROOF AREAS FROM ABOVE IN THE CALCULATIONS. SECTIONS |
| 1106 & 1107 WITH ALL SUBSECTIONS. |
| |
| 8. SHT A2.2 DETAIL 2/A2.2 DOES NOT REFLECT THE LOWER |
| ROOF PLAN SHOWN ON SHT A1.30. THE LOWER ROOF PLAN |
| INDICATES 2 10" DIA. SCUPPERS ON THE EAST ELEVATION. |
| THE DETAIL SHOWS 1 RECTANGULAR SCUPPER. PLEASE |
| CORRELATE THE DETAIL & ROOF PLAN INFORMATION. SECTION |
| 106.1.1. |
| |
| 9. SHT A4.01 DETAIL 1. THE ACCESSIBLE STALLS DO NOT |
| MEET THE CODE REQUIREMENT FOR NEW STALLS. A LAV IS |
| REQUIRED IN THE ACCESSIBLE STALL. PLEASE SEE SECTION |
| 11-4.17.3 EXCEPTION(1)(2) AND FIG. 11-30(E). (ALSO |
| CORRECT STALL CONDITION ON SHEETS A0.10, A1.10, A1.11, |
| A1.13, AND ANY RELEVANT PLUMBING SHEETS. |
| |
| 10. SHT A4.01 BOYS (114 - 138) & GIRLS (115 - 137) |
| TOILET ROOMS, THE TURNING AREA SHALL BE SHOWN IN THE |
| TOILET ROOM, NOT THE ACCESSIBLE STALL. SECTION |
| 11-4.22.3. |
| |
| 11. SHT A4.01 SHOW THE CLEAR FLOOR SPACE FOR THE |
| ACCESSIBLE URINALS IN TOILET ROOMS 114 & 138 PER |
| SECTION 11-4.18.3. |
| |
| 12. SHTS A4.10 & A4.11 SHOW THE FOLLOWING ACCESSIBLE |
| REQUIREMENTS: |
| FOR THE W/C'S: |
| A. 11-4.16.2 CLEAR FLOOR SPACE |
| B. 11-4.16.3 HEIGHT |
| C. 11-4.16.6 DISPENSERS |
| FOR THE STALLS: |
| A. 11-4.17.3 SIZE & ARRANGEMENT (EXCEPTION NEW CONST. |
| (1)(2)) & FIG. 11-30E. |
| FOR THE URINALS: |
| A. 11-4.18.3 CLEAR FLOOR SPACE |
| B. 11-4.18.4 FLUSH CONTROLS |
| FOR THE LAVS: |
| A. 11-4.19.2 HEIGHT & CLEARANCES |
| B. 11-4.19.4 EXPOSED PIPES & SURFACES |
| C. 11-4.19.5 FAUCETS |
| FOR THE SHOWERS: |
| A. 11-4.21.2 SIZE & CLEARANCES |
| B. 11-4.21.3 SEAT |
| C. 11-4.21.4 GRAB BARS |
| D. 11-4.21.5 CONTROLS |
| E. 11-4.21.6 SHOWER UNIT |
| |
| 13. SHT A4.23 FINISH SCHEDULE. INDICATE HOW PAINTED GWB |
| COMPLIES WITH THE "HARD" SURFACE REQUIRED IN SECTION |
| 1210.2. THE REQUIREMENT IS FOR A SMOOTH, HARD, |
| NONABSORBENT SURFACE. |
| |
| 14. SHT P0.1 WATER HEATER "A" DETAIL THERMAL EXPANSION |
| CONTROL IS REQUIRED BY SECTION 607.3.2. INDICATE |
| METHOD. |
| |
| 15. SHT P0.1 PLUMBING NOTES #5. AIR CHAMBERS ARE NOT |
| APPROVED. PLEASE DELETE REFERENCE. SECTION 604.9 & |
| PDI-WH 201. |
| |
| 16. SHT P1.1 SANT. LINE TO WASH MACHINE BOX SHALL BE 3" |
| PER SECTION 406.3. |
| |
| 17. SHT P1.1 RWL TO BE 10" @ 10,666SF. TABLE 1106.3. - |
| 10" @15,566SF TO READ 16,566SF. RECHECK ADDITION. |
| SECTION 106.1.1. - 15" @28,862SF TO READ 26,862SF. |
| PLEASE RECHECK ADDITION. SECTION 106.1.1. |
| |
| 18. SHTSP1.2 & P1.3.8" RWL 10,666SF TO BE 10" ON |
| THE HORIZONTAL BLDG DRAIN AND THE HORIZONTAL BRANCH |
| DRAIN PRIOR TO A DOWNSTREAM OF RWL. TABLE 1106.3. |
| |
| 19. SHT P2.1 RISER 2R/P2-1 DOES NOT REFLECT THE FLOOR |
| PLAN. NO PIPING TO HOSE BIBBS SHOWN AND NO PIPING TO |
| THE DRINKING FOUNTAINS SHOWN. PLEASE CORRELATE RISER & |
| FLOOR PLAN. INDICATE "REVERSE FOR TOILET ROOMS 114 & |
| 115. SECTION 106.1.1. |
| |
| 20. DOMESTIC WATER RISER 11R/P2-1 NO WATER SUPPLY |
| PIPING SHOWN TO THE WASH MACHINE CONNECTION BOX. PLEASE |
| CORRELATE. SECTION 106.1.1. |
| |
| 21. SHT P2-1 SANITARY RISER 10R/P2-1 DRY HORIZONTAL |
| VENTS ARE NOT APPROVED PER SECTIONS 905.3 & 905.4. (SEE |
| RED LINE EXAMPLE ON SHEET TO CORRECT CODE VIOLATION. |
| |
| 22. SHT P2-1 SANITARY RISER 3R/P2-1 NO P1 FIXTURE SHOWN |
| & SHOWER IS INDICATED AS A FLOOR DRAIN. PLEASE |
| CORRELATE RISER AND FLOOR PLAN. SECTION 106.1.1. |
| |
| 23. SHT P2-1 WATER RISER 4R/P2-1 WATER HAMMER ARRESTORS |
| SHALL BE LOCATED NEAR THE FIXTURE IN AN "EFFECTIVE |
| RANGE" NOT IN THE CEILING AS SHOWN. PDI-WH 201 AND |
| MANUF. INSTALLATION INSTRUCTIONS. |
| |
| 24. SHT P2-1 SANITARY WASTE RISER DIAGRAM, 1R/ P2-1 |
| INDICATE ON THE PLANS THAT THE RISER IS "REVERSE FOR |
| TOILET ROOMS 114 & 115". |
| |
| 25. SHT P2-2 STORM RISER DIAGRAM. 15" @ 28,862SF TO |
| READ 15" 26,862SF. PLEASE CHECK ADDITION. SECTION |
| 106.1.1. - 10" @ 15,566SF TO READ 10" 16,566SF. - 8" @ |
| 10,666SF IS REQUIRED TO BE 10" ON THE HORIZONTAL ABOVE |
| AND BELOW RISER. TABLE 1106.3. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. SUBMITTING ONE SET |
| OF PLANS FROM THIS REVIEW SEPARATELY, FOR COMPARISON, |
| WILL HELP TO EXPEDITE YOUR PERMIT ALSO. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |