Plan Review Notes For Permit 06100891 |
Permit Number |
06100891 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-11-04 14:14:06 | ------------------DENIED------------------- | | | | FBC 2004 | | FBC,M 2004 | | | | 1. PLEASE SHOW ALL CONDENSATE DISPOSAL TO BE IN | | COMPLIANCE WITH FBC,M 307.2.1 THROUGH 307.2.3 AND FBC | | 1503.6 | | | | 2. PG M3.1 DETAIL 4: MINIMUM CLEARANCE UNDER ROOFTOP | | EQUIPMENT IS TO BE DETERMINED BY FBC TABLE 1509.7. | | ALSO, PLEASE INDICATE WHETHER ATTACHMENTS ARE IN | | COMPLIANCE WITH THE MINIMUM WIND LOAD REQUIREMENTS OF | | FBC CHAPTER 16. | | | | 3. PG M3.1 DETAIL 2: THE MINIMUM ALLOWED WIDTH OF | | SUPPORTS FOR FLEXIBLE DUCT IS 1.5" PER FBC,M | | 603.5.6.6(6) | | | | 4. PG M3.2 DETAIL 1: NO STRUCTURAL DETAIL FOR CURB | | ATTACHMENT COULD BE LOCATED IN THIS SET OF PLANS. | | | | NOTE: OFFICES 107,109,143 AND 144 ARE NOT DESIGNED TO | | MEET THE BALANCED RETURN EXCEPTIONS OF FBC,M 601.4. A | | FIELD TEST WILL BE REQUIRED AT FINAL INSPECTION TO SHOW | | THESE ROOMS MEET THE MAXIMUM ALLOWABLE PRESSURE | | DIFFERENTIAL OF 0.01" WC (2.5 PASCALS) | | | | REVIEWED BY: | | RONALD J REGUEIRO | | 561.805.6734 | | [email protected] |
|