2006-11-04 14:14:06------------------DENIED-------------------
  
 FBC 2004
 FBC,M 2004
  
 1. PLEASE SHOW ALL CONDENSATE DISPOSAL TO BE IN
 COMPLIANCE WITH FBC,M 307.2.1 THROUGH 307.2.3 AND FBC
 1503.6
  
 2. PG M3.1 DETAIL 4: MINIMUM CLEARANCE UNDER ROOFTOP
 EQUIPMENT IS TO BE DETERMINED BY FBC TABLE 1509.7.
 ALSO, PLEASE INDICATE WHETHER ATTACHMENTS ARE IN
 COMPLIANCE WITH THE MINIMUM WIND LOAD REQUIREMENTS OF
 FBC CHAPTER 16.
  
 3. PG M3.1 DETAIL 2: THE MINIMUM ALLOWED WIDTH OF
 SUPPORTS FOR FLEXIBLE DUCT IS 1.5" PER FBC,M
 603.5.6.6(6)
  
 4. PG M3.2 DETAIL 1: NO STRUCTURAL DETAIL FOR CURB
 ATTACHMENT COULD BE LOCATED IN THIS SET OF PLANS.
  
 NOTE: OFFICES 107,109,143 AND 144 ARE NOT DESIGNED TO
 MEET THE BALANCED RETURN EXCEPTIONS OF FBC,M 601.4. A
 FIELD TEST WILL BE REQUIRED AT FINAL INSPECTION TO SHOW
 THESE ROOMS MEET THE MAXIMUM ALLOWABLE PRESSURE
 DIFFERENTIAL OF 0.01" WC (2.5 PASCALS)
  