2006-12-14 20:44:09 | *****DENIED***** |
| |
| |
| |
| 1.ACCESS ROADS SHALL HAVE AN UNOBSTRUCTED WIDTH OF 20 |
| FT AND AN UNOBSTRUCTED VERTICAL CLEARANCE OF 13FT 6IN. |
| THE ROADS SHALL ALSO BE DESIGNED AND MAINTAINED TO |
| SUPPORT 32 TONS OF FIRE APPARATUS. |
| |
| 2. WHERE UNDERGROUND WATER MAINS AND HYDRANTS ARE TO BE |
| PROVIDED, THEY SHALL BE INSTALLED, COMPLETED, AND IN |
| SERVICE PRIOR TO CONSTRUCTION WORK. |
| |
| 3.CONSTRUCTION OPERATIONS SHALL NOT INTERFERE OR |
| HINDER EMERGENCY ACCESS TO THE PROPERTY OR VICINITY |
| THEROF. |
| |
| 4.LANSCAPING SHALL NOT OBSTRUCT OR INTERFERE WITH |
| FIRE PROTECTION EQUIPMENT.PROPER CLEARANCES SHALL BE |
| MAINTAINED AT ALL TIMES. |
| |
| 5.PANIC HARDWARE OR FIRE EXIT PANIC HARDWARE REQUIRED |
| ON ALL EXIT DOORS THAT HAVE AN OCCUPANT LOAD OF 100 OR |
| MORE PERSONS TRAVELING THROUGH THEM. |
| |
| 6.FIRE EXTINGUISHERS TO BE 2A:10 BC RATED. |
| |
| 7.THE FIRE ALARM SYSTEM IN CONJUNCTION WITH THE FIRE |
| SPRINKLER SYSTEM SHALL MEET THE REQUIREMENTS OF BEING |
| MONITORED BY A LICENSED CENTRAL STATION APPROVED FOR |
| CENTRAL STATION SERVICE. |
| |
| 8.KNOX BOX FOR THE BUILDING WILL BE REQUIRED. |
| |
| 9.SHOW/DISPLAY THE NUMERICAL ADDRESS OF THE BUILDING |
| ON THE PROPER ELEVATION.AS PER WEST PALM BEACH CODE, |
| NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND 1" IN |
| WIDTH CONTRASTING TO THEIR BACKGROUND. |
| |
| 10. FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA 80. |
| |
| 11. PROVIDE LAYOUT OF THE FIRE SPRINKLER AND FIRE ALARM |
| SYSTEM FOR THE BUILDING.A SEPARATE PERMIT AND PLAN |
| WILL BE REQUIRED FOR EACH. |
| |
| |
| TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED. |
| |
| |
| CAPT. MICHAEL A.WILLIAMS |
| FIRE PLAN REVIEW |
| 561-805-6722 |