2006-12-14 20:44:09*****DENIED*****
  
  
  
 1.ACCESS ROADS SHALL HAVE AN UNOBSTRUCTED WIDTH OF 20
 FT AND AN UNOBSTRUCTED VERTICAL CLEARANCE OF 13FT 6IN.
 THE ROADS SHALL ALSO BE DESIGNED AND MAINTAINED TO
 SUPPORT 32 TONS OF FIRE APPARATUS.
  
 2. WHERE UNDERGROUND WATER MAINS AND HYDRANTS ARE TO BE
 PROVIDED, THEY SHALL BE INSTALLED, COMPLETED, AND IN
 SERVICE PRIOR TO CONSTRUCTION WORK.
  
 3.CONSTRUCTION OPERATIONS SHALL NOT INTERFERE OR
 HINDER EMERGENCY ACCESS TO THE PROPERTY OR VICINITY
 THEROF.
  
 4.LANSCAPING SHALL NOT OBSTRUCT OR INTERFERE WITH
 FIRE PROTECTION EQUIPMENT.PROPER CLEARANCES SHALL BE
 MAINTAINED AT ALL TIMES.
  
 5.PANIC HARDWARE OR FIRE EXIT PANIC HARDWARE REQUIRED
 ON ALL EXIT DOORS THAT HAVE AN OCCUPANT LOAD OF 100 OR
 MORE PERSONS TRAVELING THROUGH THEM.
  
 6.FIRE EXTINGUISHERS TO BE 2A:10 BC RATED.
  
 7.THE FIRE ALARM SYSTEM IN CONJUNCTION WITH THE FIRE
 SPRINKLER SYSTEM SHALL MEET THE REQUIREMENTS OF BEING
 MONITORED BY A LICENSED CENTRAL STATION APPROVED FOR
 CENTRAL STATION SERVICE.
  
 8.KNOX BOX FOR THE BUILDING WILL BE REQUIRED.
  
 9.SHOW/DISPLAY THE NUMERICAL ADDRESS OF THE BUILDING
 ON THE PROPER ELEVATION.AS PER WEST PALM BEACH CODE,
 NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND 1" IN
 WIDTH CONTRASTING TO THEIR BACKGROUND.
  
 10. FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA 80.
  
 11. PROVIDE LAYOUT OF THE FIRE SPRINKLER AND FIRE ALARM
 SYSTEM FOR THE BUILDING.A SEPARATE PERMIT AND PLAN
 WILL BE REQUIRED FOR EACH.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  