2006-11-05 18:34:24 | *** UNSAT *** |
| |
| ** PLEASE SEE SOME OF THE COMMENTS BELOW DO NO PERTAIN |
| TO JLRD ENGINEERING AND ARE BEING NOTED AT THIS TIME. |
| |
| 1) NOTE: PLEASE SEE ADDRESS ON PLANS STATES 2700 NORTH |
| MILITARY TRAIL, YET PLEASE SEE COMMENTS FROM THE |
| ADDRESSING REVIEWER. |
| PLEASE KNOW ONCE AN ADDRESS IS OBTAINED AND FINALIZED |
| PLEASE BE SURE TO PLACE ON ALL TITLE BLOCKS AS |
| REQUIRED. |
| FAC 61G1-16.004, 61G15-23.002 |
| |
| 2) NOTE: PLEASE SEE SOME SURVEY/ SITE SHEETS ARE NOT |
| SIGNED AND SEALED. SEEMS SOME WERE MISSED. FS 472.025 |
| |
| 3) NOTE: PLEASE SEE "C" SHEETS, ARE ALSO NOT SIGNED, |
| DATED OR SEALED. PLEASE SEE COMMENTS FROM ENGINEERING |
| REVIEWER. FS 481/471 |
| |
| 4) NOTE: PLEASE SEE MINIMUM SIZE SEAL REQUIRED FOR |
| LANDSCAPE ARCHITECT PER FAC 61G1-16.002. *THIS IS ONLY |
| NOTED BY THIS REVIEWER* |
| |
| 5) NOTE: PLEASE SEE ENERGY CALCULATIONS SUBMITTED WILL |
| BE REQUIRED TO BE SIGNED, DATED AND SEALED BY THE |
| RESPONSIBLE DESIGNER ONCE REVISED. PLEASE SEE THE SETS |
| SUBMITTED WERE NOT DONE. |
| PLEASE ALSO SEE FUTURE COMMENTS WITH RESPECT TO FBC |
| 2004 CHAPTER 13. |
| |
| 6) NOTE: PLEASE BE SURE ALL OF THE FOLLOWING CODES AT A |
| MINIMUM ARE STATED ON PLANS WHICH ARE RELEVANT TO THE |
| DESIGN OF PLANS SUBMITTED. |
| 2002 NFPA-70, 2002 NFPA-72, 2003 NFPA-101, AND 2004 |
| FBC. |
| |
| 7) NOTE: PLEASE SEE ACCESS TO THE MAIN ELECTRICAL ROOM |
| TO SHUT OFF POWER IN AN EMERGENCY AS SHOWN IS NOT |
| PERMITTED. PLEASE SEE ACCESS TO THE MAIN ELECTRICAL |
| ROOM IS MOST IMPORTANT IF THE FIRE DEPT PERSONNEL ARE |
| IN NEED OF SHUTTING DOWN POWER. |
| PLEASE SEE ONCE OBTAINING ENTRANCE INTO THE BUILDING |
| WHICH COULD BE LOCKED, PLEASE SEE PLANS SHOW A TRAVEL |
| DISTANCE DOWN A HALLWAY, THROUGH ANOTHER POSSIBLE |
| LOCKED DOOR, THROUGH A STORAGE ROOM AND ANOTHER LOCKED |
| DOOR. |
| PLEASE KNOW THE SCENARIO AS SHOWN IS NOT ACCEPTABLE TO |
| THIS AHJ AND IS A LIFE SAFETY ISSUE TO THIS OFFICE. |
| PLEASE SEE 100, 230.70, 230.71. |
| IT IS OF THE UTMOST IMPORTANCE TO PROVIDE ACCESS |
| DIRECTLY FROM THE OUTSIDE WITH A POSSIBLE "KNOX BOX" |
| WILL BE REQUIRED. THIS LOCATION OF A DOOR POSSIBLY AT |
| THE REAR OF BLDG AND "KNOX BOX" LOCATION SHALL BE |
| DETERMINED BY THE FIRE MARSHAL'S OFFICE IN COORDINATION |
| WITH THE ELECTRICAL REVIEW COMMENTS. |
| |
| 8) NOTE: PLEASE PROVIDE WIND LOAD CALCULATIONS FOR |
| LIGHT POLES WITH THE (EPA) EFFECTIVE PROJECTED AREA OF |
| THE LIGHT FIXTURES FIGURED IN WITH THE CALCULATIONS. |
| THESE ARE REQUIRED TO BE DONE AT THIS TIME BY A FLORIDA |
| REGISTERED PE. PLEASE KNOW THIS WILL BE REVIEWED BY THE |
| STRUCTURAL REVIEWER FOR COMPLIANCE WITH THE 140MPH 3SEC |
| GUST/ 120 SUSTAINED WIND LOADS. |
| 9) NOTE: PLEASE PROVIDE VOLTAGE DROP CALCULATIONS FOR |
| THE BRANCH CIRCUITS FOR SITE LIGHTING. |
| PLEASE ALSO PROVIDE FOR A WORST CASE FOR OTHER BRANCH |
| CIRCUITS. |
| 13-413.1.ABC.1.2 |
| |
| 10) NOTE: PLEASE SEE 2004 FBC CHAPTER 13. |
| A) PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND .1.3. |
| B) PLEASE SHOW A DETAILED SYSTEM WHICH IS REQUIRED. C) |
| PLEASE PROVIDE SCHEDULING OF SYSTEM. |
| D) PLEASE PROVIDE ALL OVER RIDE DEVICES AT THE |
| LOCATIONS FOR THE OCCUPANTS TO OVER RIDE SYSTEM, THESE |
| DEVICES ARE REQUIRED TO BE LOCATED SO THE OCCUPANT CAN |
| VISUALLY SEE THE LIGHTING BEING CONTROLLED. |
| E) PLEASE PROVIDE ALL TIMES FOR OVER RIDE DEVICES. |
| (30MINS MAX FOR OCC SENSOR TYPE DEVICES AND 4HRS MAX |
| FOR TIMER TYPE DEVICES). |
| F) PLEASE SEE ALL SPACES, AND ROOMS WHICH CONTAIN FLOOR |
| TO CEILING HEIGHT PARTITIONS SHALL ALL CONTAIN OVER |
| RIDE DEVICES OF SOME SORT WHICH WILL AUTOMATICALLY SHUT |
| OFF LIGHTING ON THOSE AREAS. (OFFICES, STORAGE ROOMS, |
| CONFERENCE ROOMS, ETC) |
| G) PLEASE SEE 13-415.1.AB.1, 13-415.1.A, IF USING |
| METHOD "A", PLEASE SEE AS SUBMITTED ALL ARE SHOWN A |
| MANUAL ON/OFF, WHICH WOULD CHANGE TO AUTO. |
| PLEASE ALSO SEE 13-415.2 |
| H) PLEASE SEE AREAS GREATER THAN 10K SQ FT. |
| 13-415.1.ABC.1.2, PLEASE SEE AREAS LARGER THAN 25K SQ |
| FT 13-415.1.ABC.1.1 |
| |
| 11) NOTE: PLEASE INDICATE THE GROUNDING ELECTRODE |
| ATTACHMENT LOCATIONS FOR THE SD TRANSFORMERS.250.30, |
| 250.20, 250.66 |
| PLEASE SHOW. |
| |
| 12) NOTE: PLEASE EXPLAIN THE ONSITE CUSTOMER OWNED |
| 13.2KV SYSTEM? HOW IS THIS NOT FPL / UTILITY POWER FROM |
| SOMEWHERE ARE DOWN THE LINE? |
| PLEASE CLARIFY. |
| IF INDEED, THIS IS AN ADDITIONAL SD SYSTEM, PLEASE |
| DETAIL THE GROUNDING ELECTRODE. |
| PLEASE SUBMIT THE MANUFACTURE SPEC/CUT SHEETS FOR THIS |
| TRANSFORMER UNIT WHICH INDICATES OCP AND A |
| TRANSFER/SWITCH? IS THIS INSIDE OR OUTSIDE THIS |
| TRANSFORMER? |
| PLEASE SEE THIS TRANSFORMER SEEMS TO ALSO INDICATE A |
| GROUND? IS THIS BONDED AT THIS LOCATION AND THEN BONDED |
| AGAIN AT THE HDP? 250.6, 250.24B. |
| 230.70, 230.76, 230.79, 250.30, ETC |
| PLEASE KNOW AT THIS POINT THERE ARE MANY QUESTIONS ON |
| THIS SYSTEM AS SHOWN? |
| |
| 13) NOTE: PLEASE SEE HDP IS BEING SHOWN ON SCHEDULE |
| WITH "GFI" PROTECTION, HOWEVER PLEASE SEE 240.13, |
| 230.95, THIS WOULD BE "GF" PROTECTION AS "GFI" IS FOR |
| PERSONNEL PROTECTION. |
| |
| 14) NOTE: PLEASE SUBMIT LOAD CALCULATIONS, LOAD |
| SUMMARY. PLEASE SEE NEC 220., 220.3, 220.10, 220.11, |
| 220.13 ETC. |
| PLEASE INDICATE AND SHOW ALL CONTINUOUS LOADS AT 125%, |
| 215.3, 230.42. |
| FBC ADMIN SECT 106.1.2, 106.3.5.1.2 AS ADOPTED BY THE |
| CITY OF WEST PALM BEACH. |
| |
| 15) NOTE: PLEASE INDICATE ALL DEVICE LEVELS FOR ADA |
| REQUIREMENTS IN CHAPTER 11 OF THE 2004 FBC. |
| PLEASE SEE 11-4.28.1, 11-4.28.2, AND 11-4.28.3(4). |
| PLEASE INDICATE THE MINIMUM DECIBEL LEVELS AND THE MIN |
| OF 75 CANDELAS FOR STROBE/VISUAL DEVICES. PLEASE KNOW |
| THIS IS MORE RESTRICTIVE THAN NFPA-72 AND WILL BE |
| REQUIRED. |
| |
| |
| ** PLEASE KNOW AS A "SYSTEM" FOR CHAPTER 13 IS NOT YET |
| SUBMITTED, THERE MAY BE FURTHER COMMENTS. |
| |
| |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
2006-11-05 16:58:25 | IN ELEC FOR REVIEW |