Plan Review Notes
Plan Review Notes For Permit 06100891
Permit Number 06100891
Review Stop E
Sequence Number 1
Notes
Date Text
2006-11-05 18:34:24*** UNSAT ***
  
 ** PLEASE SEE SOME OF THE COMMENTS BELOW DO NO PERTAIN
 TO JLRD ENGINEERING AND ARE BEING NOTED AT THIS TIME.
  
 1) NOTE: PLEASE SEE ADDRESS ON PLANS STATES 2700 NORTH
 MILITARY TRAIL, YET PLEASE SEE COMMENTS FROM THE
 ADDRESSING REVIEWER.
 PLEASE KNOW ONCE AN ADDRESS IS OBTAINED AND FINALIZED
 PLEASE BE SURE TO PLACE ON ALL TITLE BLOCKS AS
 REQUIRED.
 FAC 61G1-16.004, 61G15-23.002
  
 2) NOTE: PLEASE SEE SOME SURVEY/ SITE SHEETS ARE NOT
 SIGNED AND SEALED. SEEMS SOME WERE MISSED. FS 472.025
  
 3) NOTE: PLEASE SEE "C" SHEETS, ARE ALSO NOT SIGNED,
 DATED OR SEALED. PLEASE SEE COMMENTS FROM ENGINEERING
 REVIEWER. FS 481/471
  
 4) NOTE: PLEASE SEE MINIMUM SIZE SEAL REQUIRED FOR
 LANDSCAPE ARCHITECT PER FAC 61G1-16.002. *THIS IS ONLY
 NOTED BY THIS REVIEWER*
  
 5) NOTE: PLEASE SEE ENERGY CALCULATIONS SUBMITTED WILL
 BE REQUIRED TO BE SIGNED, DATED AND SEALED BY THE
 RESPONSIBLE DESIGNER ONCE REVISED. PLEASE SEE THE SETS
 SUBMITTED WERE NOT DONE.
 PLEASE ALSO SEE FUTURE COMMENTS WITH RESPECT TO FBC
 2004 CHAPTER 13.
  
 6) NOTE: PLEASE BE SURE ALL OF THE FOLLOWING CODES AT A
 MINIMUM ARE STATED ON PLANS WHICH ARE RELEVANT TO THE
 DESIGN OF PLANS SUBMITTED.
 2002 NFPA-70, 2002 NFPA-72, 2003 NFPA-101, AND 2004
 FBC.
  
 7) NOTE: PLEASE SEE ACCESS TO THE MAIN ELECTRICAL ROOM
 TO SHUT OFF POWER IN AN EMERGENCY AS SHOWN IS NOT
 PERMITTED. PLEASE SEE ACCESS TO THE MAIN ELECTRICAL
 ROOM IS MOST IMPORTANT IF THE FIRE DEPT PERSONNEL ARE
 IN NEED OF SHUTTING DOWN POWER.
 PLEASE SEE ONCE OBTAINING ENTRANCE INTO THE BUILDING
 WHICH COULD BE LOCKED, PLEASE SEE PLANS SHOW A TRAVEL
 DISTANCE DOWN A HALLWAY, THROUGH ANOTHER POSSIBLE
 LOCKED DOOR, THROUGH A STORAGE ROOM AND ANOTHER LOCKED
 DOOR.
 PLEASE KNOW THE SCENARIO AS SHOWN IS NOT ACCEPTABLE TO
 THIS AHJ AND IS A LIFE SAFETY ISSUE TO THIS OFFICE.
 PLEASE SEE 100, 230.70, 230.71.
 IT IS OF THE UTMOST IMPORTANCE TO PROVIDE ACCESS
 DIRECTLY FROM THE OUTSIDE WITH A POSSIBLE "KNOX BOX"
 WILL BE REQUIRED. THIS LOCATION OF A DOOR POSSIBLY AT
 THE REAR OF BLDG AND "KNOX BOX" LOCATION SHALL BE
 DETERMINED BY THE FIRE MARSHAL'S OFFICE IN COORDINATION
 WITH THE ELECTRICAL REVIEW COMMENTS.
  
 8) NOTE: PLEASE PROVIDE WIND LOAD CALCULATIONS FOR
 LIGHT POLES WITH THE (EPA) EFFECTIVE PROJECTED AREA OF
 THE LIGHT FIXTURES FIGURED IN WITH THE CALCULATIONS.
 THESE ARE REQUIRED TO BE DONE AT THIS TIME BY A FLORIDA
 REGISTERED PE. PLEASE KNOW THIS WILL BE REVIEWED BY THE
 STRUCTURAL REVIEWER FOR COMPLIANCE WITH THE 140MPH 3SEC
 GUST/ 120 SUSTAINED WIND LOADS.
 9) NOTE: PLEASE PROVIDE VOLTAGE DROP CALCULATIONS FOR
 THE BRANCH CIRCUITS FOR SITE LIGHTING.
 PLEASE ALSO PROVIDE FOR A WORST CASE FOR OTHER BRANCH
 CIRCUITS.
 13-413.1.ABC.1.2
  
 10) NOTE: PLEASE SEE 2004 FBC CHAPTER 13.
 A) PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND .1.3.
 B) PLEASE SHOW A DETAILED SYSTEM WHICH IS REQUIRED. C)
 PLEASE PROVIDE SCHEDULING OF SYSTEM.
 D) PLEASE PROVIDE ALL OVER RIDE DEVICES AT THE
 LOCATIONS FOR THE OCCUPANTS TO OVER RIDE SYSTEM, THESE
 DEVICES ARE REQUIRED TO BE LOCATED SO THE OCCUPANT CAN
 VISUALLY SEE THE LIGHTING BEING CONTROLLED.
 E) PLEASE PROVIDE ALL TIMES FOR OVER RIDE DEVICES.
 (30MINS MAX FOR OCC SENSOR TYPE DEVICES AND 4HRS MAX
 FOR TIMER TYPE DEVICES).
 F) PLEASE SEE ALL SPACES, AND ROOMS WHICH CONTAIN FLOOR
 TO CEILING HEIGHT PARTITIONS SHALL ALL CONTAIN OVER
 RIDE DEVICES OF SOME SORT WHICH WILL AUTOMATICALLY SHUT
 OFF LIGHTING ON THOSE AREAS. (OFFICES, STORAGE ROOMS,
 CONFERENCE ROOMS, ETC)
 G) PLEASE SEE 13-415.1.AB.1, 13-415.1.A, IF USING
 METHOD "A", PLEASE SEE AS SUBMITTED ALL ARE SHOWN A
 MANUAL ON/OFF, WHICH WOULD CHANGE TO AUTO.
 PLEASE ALSO SEE 13-415.2
 H) PLEASE SEE AREAS GREATER THAN 10K SQ FT.
 13-415.1.ABC.1.2, PLEASE SEE AREAS LARGER THAN 25K SQ
 FT 13-415.1.ABC.1.1
  
 11) NOTE: PLEASE INDICATE THE GROUNDING ELECTRODE
 ATTACHMENT LOCATIONS FOR THE SD TRANSFORMERS.250.30,
 250.20, 250.66
 PLEASE SHOW.
  
 12) NOTE: PLEASE EXPLAIN THE ONSITE CUSTOMER OWNED
 13.2KV SYSTEM? HOW IS THIS NOT FPL / UTILITY POWER FROM
 SOMEWHERE ARE DOWN THE LINE?
 PLEASE CLARIFY.
 IF INDEED, THIS IS AN ADDITIONAL SD SYSTEM, PLEASE
 DETAIL THE GROUNDING ELECTRODE.
 PLEASE SUBMIT THE MANUFACTURE SPEC/CUT SHEETS FOR THIS
 TRANSFORMER UNIT WHICH INDICATES OCP AND A
 TRANSFER/SWITCH? IS THIS INSIDE OR OUTSIDE THIS
 TRANSFORMER?
 PLEASE SEE THIS TRANSFORMER SEEMS TO ALSO INDICATE A
 GROUND? IS THIS BONDED AT THIS LOCATION AND THEN BONDED
 AGAIN AT THE HDP? 250.6, 250.24B.
 230.70, 230.76, 230.79, 250.30, ETC
 PLEASE KNOW AT THIS POINT THERE ARE MANY QUESTIONS ON
 THIS SYSTEM AS SHOWN?
  
 13) NOTE: PLEASE SEE HDP IS BEING SHOWN ON SCHEDULE
 WITH "GFI" PROTECTION, HOWEVER PLEASE SEE 240.13,
 230.95, THIS WOULD BE "GF" PROTECTION AS "GFI" IS FOR
 PERSONNEL PROTECTION.
  
 14) NOTE: PLEASE SUBMIT LOAD CALCULATIONS, LOAD
 SUMMARY. PLEASE SEE NEC 220., 220.3, 220.10, 220.11,
 220.13 ETC.
 PLEASE INDICATE AND SHOW ALL CONTINUOUS LOADS AT 125%,
 215.3, 230.42.
 FBC ADMIN SECT 106.1.2, 106.3.5.1.2 AS ADOPTED BY THE
 CITY OF WEST PALM BEACH.
  
 15) NOTE: PLEASE INDICATE ALL DEVICE LEVELS FOR ADA
 REQUIREMENTS IN CHAPTER 11 OF THE 2004 FBC.
 PLEASE SEE 11-4.28.1, 11-4.28.2, AND 11-4.28.3(4).
 PLEASE INDICATE THE MINIMUM DECIBEL LEVELS AND THE MIN
 OF 75 CANDELAS FOR STROBE/VISUAL DEVICES. PLEASE KNOW
 THIS IS MORE RESTRICTIVE THAN NFPA-72 AND WILL BE
 REQUIRED.
  
  
 ** PLEASE KNOW AS A "SYSTEM" FOR CHAPTER 13 IS NOT YET
 SUBMITTED, THERE MAY BE FURTHER COMMENTS.
  
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2006-11-05 16:58:25IN ELEC FOR REVIEW