2006-11-21 16:52:31BUILDING PLAN REVIEW
 PERMIT: 06100891
 ADD: 2395 NORTHWOOD UNIVERSITY DR.
 CONT: THE WEITZ CO.
 TEL: (561309-7386
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) DISCREPANCY) PLEASE CORRECT THE ADDRESS ON
 THE PERMIT APPLICATION, THE ACTUAL SITE ADDRESS IS ALSO
 WRONG ON ALL PLANS, SITE ADDRESS IS 2600 NORTH MILITARY
 TRAIL.
  
 4A) SP-2 THE MONUMENT SIGN INDICATED ON THIS SHEET WILL
 REQUIRE A SEPERATE PERMIT.
 4B) NOTE: PLEASE CONTACT LILI URSA @ 822-1239 FOR
 ADDRESSING OF ALL BUILDINGS ON THE NORTHWOOD CAMPUS. MS
 URSA WILL NEED A CURRENT SITE PLAN OF ALL STRUCTURES
 AND
 A CONTACT PERSON & TELEPHONE NUMBER.
  
 5 ) 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) FLOOD ZONE : A8 MINIMUM ELEVATION 16'-6". THE
 FINISHED FLOOR LEVEL SHALL BE
 VERIFIED BY A SIGNED AND SEALED ELEVATION CERTIFICATE.
 C) OCCUPANT LOADS
 D) OCCUPANCY SEPERATION: NONSEPERATED OR SEPERATED
 USES
  
 6) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 7)FBC 13-103.1.1.1THE PROFESSIONALS RESPONSIBLE FOR
 THE DESIGN OF THE
 BUILDING AND THE ELECTRICAL,
 LIGHTING, MECHANICAL AND PLUMBING
 SYSTEMS SHALL EACH SIGN THE ENERGY CODE
 COMPLIANCE FORM, TO CERTIFY COMPLIANCE.
  
 8) FBC* 105.3RESIDENT INSPECTOR.
 SUBMIT INSPECTOR RESUME' AND LICENSE
 DOCUMENTS TO HAROLD PISKURA, DIRECTOR OF
 THE RESIDENT INSPECTOR PROGRAM.A
 RESIDENT INSPECTOR PROGRAM IS REQUIRED,
 ON THIS PROJECT, DUE TO ONE OR MORE OF
 THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQFT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN
 OR METHODS OF CONSTRUCTION (TILT WALL).
  
 8) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 9) NOTE, 109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERMORMED IN A MANNER
 SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS
 SUCH ACTIVITY IS PERMITTED TO AFFECT
 SAID PROPERTY PURSUANT TO A CONSENT BY
 THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE
 APPLICABLE PROPERTY OWNER.THIS INCLUDES
 BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION
 MATERIALS. NEW CONSTRUCTION ACTIVITY
 SHALL NOT ADVERSELY IMPACT HISTORIC
 SURFACE WATER DRAINAGE FLOWS SERVING
 ADJACENT PROPERTIES, & MAY REQUIRE
 SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS,
 AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR
 ITEMS, ON EXISTING PROPERTIES RESULTING
 IN A DECREASE IN EXCESS OF 800SQ FT OF
 PERMEABLE LAND AREA ON ANY PARCELL SHALL
 AS A PERMIT CONDITION, PROVIDE A
 PROFESSIONALLY PREPARED DRAINAGE PLAN
 CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 10) 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 11)SHEET SP2 THIS SITE PLAN INDICATES THE WALKWAYS
 AND PAVEMENT THAT ARE AJACENT TO THE NEW BUILDING. THE
 PLAN FAILS TO INDICATE ALL ACCESSIBLE
 EXITS (EXIT DISCHARGE) AS REQUIRED IN ACCESSIBLE
 BUILDINGS:
 NEW CONSTRUCTION. 11-4.1.3(8)(II) ACCESSIBLE ENTRANCES
  
 MUST BE PROVIDED IN A NUMBER AT LEAST EQUIVALENT TO
 THE
  
 NUMBER OF EXITS REQUIRED BY THE APPLICABLE
 BUILDING/FIRE
 CODES. SHEET A1.10 INDICATES THE REQUIRED EXITS BUT
 THE
  
 PLANS ARE MISSING THE ACCESSIBLE ROUTE FOR THOSE
 EXITS.
  
 10) SHEET A1.11 THE GIRLS AND BOYS GANGED RESTROOMS
 ROOM # 114, 115, 137 & 138ALL HAVE THE SAME ISSUE,IN
  
 NEW CONSTRUCTION THE TOLIET STALLS REQUIRE THE LAV TO
 BE IN
 THE STALL SEE 11-4.17.3, NEW CONSTRUCTION (IN GRAY),
 (1) THE
 STANDARD ACCESSIBLE RESTROOM STALL SHALL CONTAIN AN
 ACCESSIBLE
 LAVATORY WITHIN IT, THE SIZE OF SUCH LAVATORY TO BE NOT
 LESS THAN
 19 INCHES WIDE BY 17 INCHES (483 MM BY 432 MM) DEEP,
 NOMINAL
 SIZE, AND WALL MOUNTED. THE LAVATORY SHALL BE MOUNTED
 SO AS NOT
 TO OVERLAP THE CLEAR FLOOR SPACE AREAS REQUIRED BY
 SECTION 11-4.17
 [SEE FIGURE 11-30 (A) AND FIGURE 11-30 (E)] AND TO
 COMPLY WITH
 SECTION 11-4.19 OF THE CODE. SUCH LAVATORIES SHALL BE
 COUNTED
 AS PART OF THE REQUIRED FIXTURE COUNT FOR THE
 BUILDING.
  
 (2)THE ACCESSIBLE WATER CLOSET SHALL BE LOCATED IN
 THE CORNER,
 DIAGONAL TO THE DOOR.
  
 12)SHEET A4.01 DETAILS 3&4 ENTRYINFORMATION AND
 RECEPTION COUNTER
 BOTH NEED TO COMPLY WITH SECTION 11-4.32.4 HEIGTH OF
 COUNTERS.11-4.32.4
 HEIGHT OF TABLES OR COUNTERS. THE TOPS OF ACCESSIBLE
 TABLES AND COUNTERS
 SHALL BE FROM 28 INCHES TO 34 INCHES (710 MM TO 865 MM)
 ABOVE THE FINISH
 FLOOR OR GROUND.
  
 13)PLANS FOR THE INTERIOR BUILD OUT FOR ROOM 102
 EXCHANGE CITY AND
 ROOM 146FINANCE PARK DO NOT INDICATE ANY INFORMATION
 AT THIS TIME.
 THERE IS NO COMMENT ON EGRESS OR ACCESSIBILITY ISSUES
 AT THIS TIME.
  
 14)SHEETS A1.11 - A1.13 INDICATE VARIOUS WALL
 ASSEMBLIES BUT
 FAIL TO PROVIDE A SHEET WITH THE ASSEMBLIES DETAILED?
 106.1.2*
 ADDITIONAL INFORMATION REQUIRED.
  
 15) SHEETS A1.12 & A1.13 BOTH HAVE AN ASSEMBLY
 OCCUPANCY BUT ARE TRUELY EDUCATIONAL USAGE CHILDREN IN
 SCHOOL HIGH SCHOOL GRADES AND LOWER.
 THESE ROOMS STILL NEED AN EMERGENCY ESCAPE WINDOW SINCE
 THE CODE SPECIFICALLY STATES WINDOWEVEN THOUGH THERE
 ARE DOORS TO THE EXTERIOR.
 1025.4.1
 EVERY ROOM OR SPACE GREATER THAN 250 SQUARE FEET (23.2
 M 2 ) IN EDUCATIONAL OCCUPANCIES USED FOR CLASSROOM OR
 OTHER EDUCATIONAL PURPOSES OR NORMALLY SUBJECT TO
 STUDENT OCCUPANCY AND EVERY ROOM OR SPACE NORMALLY
 SUBJECT TO CLIENT OCCUPANCY, OTHER THAN BATHROOMS, IN
 GROUP D OCCUPANCIES SHALL HAVE NOT LESS THAN ONE
 OUTSIDE WINDOW FOR EMERGENCY RESCUE THAT COMPLIES WITH
 THE FOLLOWING:
 1.SUCH WINDOWS SHALL BE OPENABLE FROM THE INSIDE
 WITHOUT THE USE OF TOOLS AND SHALL PROVIDE A CLEAR
 OPENING OF NOT LESS THAN 20 INCHES (508 MM) IN WIDTH,
 24 INCHES (610 MM) IN HEIGHT, AND 5.7 SQUARE FEET (0.53
 M 2 ) IN AREA.
 2.THE BOTTOM OF THE OPENING SHALL BE NOT MORE THAN
 44 INCHES (1118 MM) ABOVE THE FLOOR, AND ANY LATCHING
 DEVICE SHALL BE CAPABLE OF BEING OPERATED FROM NOT MORE
 THAN 54 INCHES (1372 MM) ABOVE THE FINISHED FLOOR.
 1025.1EXCEPTION# 1IS FOR BLDG WITH FIRE SPRINKLER BUT
 102.1* WHERE , IN ANY CASE DIFFERENT SECTIONS OF THE
 CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE
 APPLICABLE.
  
 16)1609.1.4 PROTECTION OF OPENINGS.
 IN WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IN THE LOWER 60 FEET (18.3 M) IN
 BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED
 OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IS IMPACT RESISTANT OR PROTECTED WITH AN
 IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND
 ASTM E 1996, OR MIAMI-DADE TAS 201, 202
 AND 203 REFERENCED THEREIN AS FOLLOWS:
 1.GLAZED OPENINGS LOCATED WITHIN 30
 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE
 TEST.
  
 FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 1) FIXED WINDOWS- STOREFRONT
 2) OPERTABLE WINDOWS
 3) GLAZED DOORS, BOTH SWING AND SLIDE
 4) METAL HOLLOW CORE EXTERIOR DOORS & LOUVERS.
 5) PRE-ENGINEERED ROOF ACCESS HATCHES
 6) MULLIONS VERTICAL & HORIZONTAL
 7) EXTERIOR ROLL UP, OR SECTIONAL DOOR
 8) SKYLIGHTS
 9)PANEL WALL SYSTEMS: SIDING, SOFFITS, EFIS
 SYSTEMS, LOUVERS
 9)ROOFING ASSEMBLIES,
 10) PRE-ENGINEERED ROOF STANDS
  
 NOTE PLEASE REVIEW COMMENT# 8:)W P B ADMINISTRTIVE
 CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 ADDITIONAL COMMENTS MAY APPEAR ON THE NEXT REVIEW
 BECAUSE OF THE
 FIRST ROUND RESPONCES OR ADDITIONAL INFORMATION
 REQUESTED.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026