2006-11-21 16:52:31 | BUILDING PLAN REVIEW |
| PERMIT: 06100891 |
| ADD: 2395 NORTHWOOD UNIVERSITY DR. |
| CONT: THE WEITZ CO. |
| TEL: (561309-7386 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1STREVIEW |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2 ) FL S S 713.13 |
| NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT BEFORE A |
| PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS |
| NOT ACTUALLY COMMENCED |
| WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. |
| |
| 3) DISCREPANCY) PLEASE CORRECT THE ADDRESS ON |
| THE PERMIT APPLICATION, THE ACTUAL SITE ADDRESS IS ALSO |
| WRONG ON ALL PLANS, SITE ADDRESS IS 2600 NORTH MILITARY |
| TRAIL. |
| |
| 4A) SP-2 THE MONUMENT SIGN INDICATED ON THIS SHEET WILL |
| REQUIRE A SEPERATE PERMIT. |
| 4B) NOTE: PLEASE CONTACT LILI URSA @ 822-1239 FOR |
| ADDRESSING OF ALL BUILDINGS ON THE NORTHWOOD CAMPUS. MS |
| URSA WILL NEED A CURRENT SITE PLAN OF ALL STRUCTURES |
| AND |
| A CONTACT PERSON & TELEPHONE NUMBER. |
| |
| 5 ) 110.2* W. P. B. ADMINISTRATIVE |
| CODE, INFORMATION THAT IS REQUIRED FOR |
| RECORD KEEPING & FOR CERTIFICATE OF |
| OCCUPANCY: |
| A) THE EDITION OFTHE CODE UNDER WHICH |
| THE PERMIT WAS ISSUED. |
| B) FLOOD ZONE : A8 MINIMUM ELEVATION 16'-6". THE |
| FINISHED FLOOR LEVEL SHALL BE |
| VERIFIED BY A SIGNED AND SEALED ELEVATION CERTIFICATE. |
| C) OCCUPANT LOADS |
| D) OCCUPANCY SEPERATION: NONSEPERATED OR SEPERATED |
| USES |
| |
| 6) FL BLD CODE 1804.2.2 QUESTIONABLE |
| SOILS, WHERE THE BEARING CAPACITY IS |
| NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| WHERE THE BEARING CAPACITY OF THE SOIL |
| IS NOT DEFINITLY KNOWN OR IS IN QUESTION |
| THE BUILDING OFFICIAL MAY REQUIRE EXPLOR |
| ATIONS, TEST OR OTHER ADEQUATE PROOF AS |
| TO THE PERMISSIBLE SAFE BEARING |
| CAPACITY. REQUIRED TEST AND RECOMMENDA- |
| TIONS SUBMITTED TO VERIFY BEARING CAPA- |
| CITY SHALL BE CERTIFIED BY A GEOTECH- |
| NICALREPORT FROM A DESIGN PROFESSIONAL |
| PROPERLY LICENSED IN THE STATE OF |
| FLORIDA. |
| |
| 7)FBC 13-103.1.1.1THE PROFESSIONALS RESPONSIBLE FOR |
| THE DESIGN OF THE |
| BUILDING AND THE ELECTRICAL, |
| LIGHTING, MECHANICAL AND PLUMBING |
| SYSTEMS SHALL EACH SIGN THE ENERGY CODE |
| COMPLIANCE FORM, TO CERTIFY COMPLIANCE. |
| |
| 8) FBC* 105.3RESIDENT INSPECTOR. |
| SUBMIT INSPECTOR RESUME' AND LICENSE |
| DOCUMENTS TO HAROLD PISKURA, DIRECTOR OF |
| THE RESIDENT INSPECTOR PROGRAM.A |
| RESIDENT INSPECTOR PROGRAM IS REQUIRED, |
| ON THIS PROJECT, DUE TO ONE OR MORE OF |
| THE FOLLOWING: |
| - BUILDINGS/ADDITIONS OF TYPE I OR II |
| CONSTRUCTION |
| - ANY MAJOR STRUCTURAL ALTERATIONS |
| - STRUCTURES IN WHICH THE CONCRETE |
| DESIGN IS BASED ON COMPRESSIVE |
| STRENGTH (F'C) IN EXCESS OF 3000 PSI |
| - PILE DRIVING |
| - BUILDINGS OVER 20,000 SQFT IN AREA |
| - BUILDINGS OVER 2 STORIES IN HEIGHT |
| - BUILDING/STRUCTURES OF UNUSUAL DESIGN |
| OR METHODS OF CONSTRUCTION (TILT WALL). |
| |
| 8) WPB ADMIN CODE 106.3* PRODUCT |
| APPROVALS. THOSE PRODUCT WHICH ARE |
| REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. |
| |
| 9) NOTE, 109.3.10* IMPACT OF CONSTRUCTION. |
| ALL CONSTRUCTION ACTIVITY REGULATED BY |
| THIS CODE SHALL BE PERMORMED IN A MANNER |
| SO AS NOT TO ADVERSELY IMPACT THE |
| CONDITION OF ADJACENT PROPERTY, UNLESS |
| SUCH ACTIVITY IS PERMITTED TO AFFECT |
| SAID PROPERTY PURSUANT TO A CONSENT BY |
| THE APPLICABLE PROPERTY OWNER, UNDER |
| TERMS & CONDITIONS AGREEABLE TO THE |
| APPLICABLE PROPERTY OWNER.THIS INCLUDES |
| BUT IS NOT LIMITED TO THE CONTROL OF |
| DUST, NOISE, WATER OR DRAINAGE RUN-OFF, |
| DEBRIS, AND THE STORAGE OF CONSTRUCTION |
| MATERIALS. NEW CONSTRUCTION ACTIVITY |
| SHALL NOT ADVERSELY IMPACT HISTORIC |
| SURFACE WATER DRAINAGE FLOWS SERVING |
| ADJACENT PROPERTIES, & MAY REQUIRE |
| SPECIAL DRAINAGE DESIGN COMPLYING WITH |
| ENGINEERING STANDARDS TO PRESERVE THE |
| POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY, |
| DEVELOPERS, CONTRACTORS, |
| AND OWNERS OF ALL NEW RESIDENTIAL |
| DEVELOPMENT, INCLUDING ADDITIONS, POOLS, |
| PATIOS, DRIVEWAYS, DECKS, OR SIMILAR |
| ITEMS, ON EXISTING PROPERTIES RESULTING |
| IN A DECREASE IN EXCESS OF 800SQ FT OF |
| PERMEABLE LAND AREA ON ANY PARCELL SHALL |
| AS A PERMIT CONDITION, PROVIDE A |
| PROFESSIONALLY PREPARED DRAINAGE PLAN |
| CLEARLY INDICATING COMPLIANCE WITH THIS |
| PARAGRAPH. UPON COMPLETION OF THE |
| IMPROVEMENT, A CERTIFICATE FROM A |
| LICENSED ENGINEER SHALL BE SUBMITTED TO |
| THE INSPECTOR IN ORDER TO RECEIVE |
| APPROVAL OF THE FINAL INSPECTION. |
| |
| 10) 109.3.10.1 HURICANE PROTECTION. |
| IT SHALL BE UNLAWFUL FOR ANY PERSON TO |
| ALLOW CONSTRUCTION RELATED MATERIALS |
| EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR |
| OTHERWISE UNSECURED AT A CONSTRUCTION |
| SITE FROM 24 HRS. AFTER A HURRICANE |
| WATCH HAS BEEN ISSUED UNTIL THE |
| HURRICANE WATCH OR WARNING HAS BEEN |
| LIFTED. ALL SUCH CONSTRUCTION MATERIALS, |
| EQUIPMENT AND DEBRIS SHALL BE EITHER |
| REMOVED FROM THE CONSTRUCTION SITE OR |
| SECURED IN SUCH A MANNER AS TO MINIMIZE |
| THE DANGER OF SUCH CONSTRUCTION |
| MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| DAMAGE TO PERSONS OR PROPERTY FROM HIGH |
| WINDS. |
| ANY PERSONS WHO FAILS TO COMPLY TO |
| REMOVE OR SECURE THE CONSTRUCTION |
| MATERIALS EQUIPMENT AND DEBRIS WITHIN |
| 24 HRS AFTER A HURRICANE WATCH HAS BEEN |
| ISSUED SHALL BE SUBJECT TO A FINE NOT TO |
| EXCEED $500.00. |
| IN ADDITION TO THE ABOVE, A LICENSED |
| CONTRACTOR WHO VIOLATES THIS SECTION |
| SHALL BE SUBJECT TO DISCIPLINE PURSUANT |
| TO SECTION 113 OF THIS CHAPTER. |
| |
| 11)SHEET SP2 THIS SITE PLAN INDICATES THE WALKWAYS |
| AND PAVEMENT THAT ARE AJACENT TO THE NEW BUILDING. THE |
| PLAN FAILS TO INDICATE ALL ACCESSIBLE |
| EXITS (EXIT DISCHARGE) AS REQUIRED IN ACCESSIBLE |
| BUILDINGS: |
| NEW CONSTRUCTION. 11-4.1.3(8)(II) ACCESSIBLE ENTRANCES |
| |
| MUST BE PROVIDED IN A NUMBER AT LEAST EQUIVALENT TO |
| THE |
| |
| NUMBER OF EXITS REQUIRED BY THE APPLICABLE |
| BUILDING/FIRE |
| CODES. SHEET A1.10 INDICATES THE REQUIRED EXITS BUT |
| THE |
| |
| PLANS ARE MISSING THE ACCESSIBLE ROUTE FOR THOSE |
| EXITS. |
| |
| 10) SHEET A1.11 THE GIRLS AND BOYS GANGED RESTROOMS |
| ROOM # 114, 115, 137 & 138ALL HAVE THE SAME ISSUE,IN |
| |
| NEW CONSTRUCTION THE TOLIET STALLS REQUIRE THE LAV TO |
| BE IN |
| THE STALL SEE 11-4.17.3, NEW CONSTRUCTION (IN GRAY), |
| (1) THE |
| STANDARD ACCESSIBLE RESTROOM STALL SHALL CONTAIN AN |
| ACCESSIBLE |
| LAVATORY WITHIN IT, THE SIZE OF SUCH LAVATORY TO BE NOT |
| LESS THAN |
| 19 INCHES WIDE BY 17 INCHES (483 MM BY 432 MM) DEEP, |
| NOMINAL |
| SIZE, AND WALL MOUNTED. THE LAVATORY SHALL BE MOUNTED |
| SO AS NOT |
| TO OVERLAP THE CLEAR FLOOR SPACE AREAS REQUIRED BY |
| SECTION 11-4.17 |
| [SEE FIGURE 11-30 (A) AND FIGURE 11-30 (E)] AND TO |
| COMPLY WITH |
| SECTION 11-4.19 OF THE CODE. SUCH LAVATORIES SHALL BE |
| COUNTED |
| AS PART OF THE REQUIRED FIXTURE COUNT FOR THE |
| BUILDING. |
| |
| (2)THE ACCESSIBLE WATER CLOSET SHALL BE LOCATED IN |
| THE CORNER, |
| DIAGONAL TO THE DOOR. |
| |
| 12)SHEET A4.01 DETAILS 3&4 ENTRYINFORMATION AND |
| RECEPTION COUNTER |
| BOTH NEED TO COMPLY WITH SECTION 11-4.32.4 HEIGTH OF |
| COUNTERS.11-4.32.4 |
| HEIGHT OF TABLES OR COUNTERS. THE TOPS OF ACCESSIBLE |
| TABLES AND COUNTERS |
| SHALL BE FROM 28 INCHES TO 34 INCHES (710 MM TO 865 MM) |
| ABOVE THE FINISH |
| FLOOR OR GROUND. |
| |
| 13)PLANS FOR THE INTERIOR BUILD OUT FOR ROOM 102 |
| EXCHANGE CITY AND |
| ROOM 146FINANCE PARK DO NOT INDICATE ANY INFORMATION |
| AT THIS TIME. |
| THERE IS NO COMMENT ON EGRESS OR ACCESSIBILITY ISSUES |
| AT THIS TIME. |
| |
| 14)SHEETS A1.11 - A1.13 INDICATE VARIOUS WALL |
| ASSEMBLIES BUT |
| FAIL TO PROVIDE A SHEET WITH THE ASSEMBLIES DETAILED? |
| 106.1.2* |
| ADDITIONAL INFORMATION REQUIRED. |
| |
| 15) SHEETS A1.12 & A1.13 BOTH HAVE AN ASSEMBLY |
| OCCUPANCY BUT ARE TRUELY EDUCATIONAL USAGE CHILDREN IN |
| SCHOOL HIGH SCHOOL GRADES AND LOWER. |
| THESE ROOMS STILL NEED AN EMERGENCY ESCAPE WINDOW SINCE |
| THE CODE SPECIFICALLY STATES WINDOWEVEN THOUGH THERE |
| ARE DOORS TO THE EXTERIOR. |
| 1025.4.1 |
| EVERY ROOM OR SPACE GREATER THAN 250 SQUARE FEET (23.2 |
| M 2 ) IN EDUCATIONAL OCCUPANCIES USED FOR CLASSROOM OR |
| OTHER EDUCATIONAL PURPOSES OR NORMALLY SUBJECT TO |
| STUDENT OCCUPANCY AND EVERY ROOM OR SPACE NORMALLY |
| SUBJECT TO CLIENT OCCUPANCY, OTHER THAN BATHROOMS, IN |
| GROUP D OCCUPANCIES SHALL HAVE NOT LESS THAN ONE |
| OUTSIDE WINDOW FOR EMERGENCY RESCUE THAT COMPLIES WITH |
| THE FOLLOWING: |
| 1.SUCH WINDOWS SHALL BE OPENABLE FROM THE INSIDE |
| WITHOUT THE USE OF TOOLS AND SHALL PROVIDE A CLEAR |
| OPENING OF NOT LESS THAN 20 INCHES (508 MM) IN WIDTH, |
| 24 INCHES (610 MM) IN HEIGHT, AND 5.7 SQUARE FEET (0.53 |
| M 2 ) IN AREA. |
| 2.THE BOTTOM OF THE OPENING SHALL BE NOT MORE THAN |
| 44 INCHES (1118 MM) ABOVE THE FLOOR, AND ANY LATCHING |
| DEVICE SHALL BE CAPABLE OF BEING OPERATED FROM NOT MORE |
| THAN 54 INCHES (1372 MM) ABOVE THE FINISHED FLOOR. |
| 1025.1EXCEPTION# 1IS FOR BLDG WITH FIRE SPRINKLER BUT |
| 102.1* WHERE , IN ANY CASE DIFFERENT SECTIONS OF THE |
| CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE |
| APPLICABLE. |
| |
| 16)1609.1.4 PROTECTION OF OPENINGS. |
| IN WIND-BORNE DEBRIS REGIONS, EXTERIOR |
| GLAZING THAT RECEIVES POSITIVE PRESSURE |
| IN THE LOWER 60 FEET (18.3 M) IN |
| BUILDINGS SHALL BE ASSUMED TO BE |
| OPENINGS AND THE BALANCE OF GLAZED |
| OPENINGS IN THE REST OF THE BUILDING |
| SHALL BE ASSUMED TO BE ZERO UNLESS SUCH |
| GLAZING THAT RECEIVES POSITIVE PRESSURE |
| IS IMPACT RESISTANT OR PROTECTED WITH AN |
| IMPACT RESISTANT COVERING MEETING THE |
| REQUIREMENTS OF SSTD 12, ASTM E 1886 AND |
| ASTM E 1996, OR MIAMI-DADE TAS 201, 202 |
| AND 203 REFERENCED THEREIN AS FOLLOWS: |
| 1.GLAZED OPENINGS LOCATED WITHIN 30 |
| FEET (9.1 M) OF GRADE SHALL MEET THE |
| REQUIREMENTS OF THE LARGE MISSILE TEST. |
| 2.GLAZED OPENINGS LOCATED MORE THAN |
| 30 FEET (9.1 M) ABOVE GRADE SHALL MEET |
| THE PROVISIONS OF THE SMALL MISSILE |
| TEST. |
| |
| FL BLD CODE 1609.1.4: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORTS,MISSING REPORTS ARE AS |
| FOLLOWS: |
| 1) FIXED WINDOWS- STOREFRONT |
| 2) OPERTABLE WINDOWS |
| 3) GLAZED DOORS, BOTH SWING AND SLIDE |
| 4) METAL HOLLOW CORE EXTERIOR DOORS & LOUVERS. |
| 5) PRE-ENGINEERED ROOF ACCESS HATCHES |
| 6) MULLIONS VERTICAL & HORIZONTAL |
| 7) EXTERIOR ROLL UP, OR SECTIONAL DOOR |
| 8) SKYLIGHTS |
| 9)PANEL WALL SYSTEMS: SIDING, SOFFITS, EFIS |
| SYSTEMS, LOUVERS |
| 9)ROOFING ASSEMBLIES, |
| 10) PRE-ENGINEERED ROOF STANDS |
| |
| NOTE PLEASE REVIEW COMMENT# 8:)W P B ADMINISTRTIVE |
| CODE 106.3.3* |
| PRODUCT APPROVALS. THOSE PRODUCTS WHICH |
| ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. |
| |
| ADDITIONAL COMMENTS MAY APPEAR ON THE NEXT REVIEW |
| BECAUSE OF THE |
| FIRST ROUND RESPONCES OR ADDITIONAL INFORMATION |
| REQUESTED. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |