Plan Review Notes
Plan Review Notes For Permit 06100832
Permit Number 06100832
Review Stop E
Sequence Number 4
Notes
Date Text
2007-03-21 18:35:02RISER APPEARS TO SHOW CONDUIT AND SERVICE ENTRANCE
 CONDUCTORS RUN ABOVEAND INSIDE ROOM. IF THIS IS NOT
 UNDERGROUND OR OUTSIDE THE BUILDING, THESE ARE REDLINED
 TO EB ENCASED IN CONCRETE PER 695-6A AND NFPA-20 9.3.1