2006-12-10 09:25:05 | ***** UNSAT ********* |
| |
| |
| 1) NOTE: PLEASE SEE PLANS INDICATE EXISTING FPC, |
| HOWEVER NEW CONTROLLER UNDER SEPARATE PERMIT. THAT |
| PERMIT WAS ONLY TO PLACE CONTROLLER, NOT TO DO ANY |
| ELECTRICAL HOOK UP. PLEASE NOTE ON PLANS AS NEW UNDER |
| "(OTHER PERMIT NUMBER)". |
| |
| 2) NOTE: PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEETS |
| AS WERE SUBMITTED UNDER THE OTHER PERMIT. EACH PERMIT |
| SHALL CONTAIN ALL DOCUMENTS RELEVANT TO INSTALLATION? |
| FIRE PUMP AND FIRE PUMP CONTROLLER. |
| THIS IS NEEDED TO CORRELATE HP RATING, CODE LETTER OF |
| MOTOR FOR MAX LOCKED ROTOR CURRENT ETC. |
| THIS IS ALSO REQUIRED FOR EACH RECORD SET OF PLANS. |
| 110.3, 90.7, ETC |
| FBC 106.1.2 |
| |
| 3) NOTE: PLEASE SEE A 4X FEE WAS ISSUED AT JOBSITE AND |
| HOLD WAS IN SYSTEM, THE ADDITIONAL FEE FOR WORK DONE |
| WITHOUT PERMITS IS $333.00 WHICH IS REQUIRED AT THIS |
| TIME. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |
| |
| |