Plan Review Notes
Plan Review Notes For Permit 06100832
Permit Number 06100832
Review Stop E
Sequence Number 1
Notes
Date Text
2006-11-02 07:21:11***** UNSAT *********
  
  
 ** PLEASE KNOW, PLANS HAVE ONLY BEEN SUBMITTED FOR
 "PLAN REVIEW" ONLY AND HAVE NOT BEEN SUBMITTED FOR
 PERMIT AT THIS TIME.
  
 1) NOTE: PLEASE KNOW WHEN FINAL APPLICATION IS MADE FOR
 INSTALLATION AND WIRING FOR FPC, THIS CAN NOT BE DONE
 BY A GC, CGC ETC. THIS MUST BE AN ELECTRICAL CONTRACTOR
 WHO APPLIES.
  
 2) NOTE: PLEASE SEE PLANS INDICATE EXISTING FPC,
 HOWEVER NEW CONTROLLER UNDER SEPARATE PERMIT. THAT
 PERMIT WAS ONLY TO PLACE CONTROLLER, NOT TO DO ANY
 ELECTRICAL HOOK UP. PLEASE NOTE ON PLANS AS NEW UNDER
 "(OTHER PERMIT NUMBER)".
  
 3) NOTE: PLEASE CLARIFY THE OCP ON THE FPC AS SHOWN.
 SHOWS 1000A, HOWEVER THIS IS BE TAKEN THAT THIS IS THE
 LRC?? PLEASE INDICATE THE NORMAL/ STANDARD OCP RATING.
 PLEASE VERIFY THIS AS THE SEC'S SHOWN ARE ONLY SIZED AT
 2/0'S WHICH ARE RATED FOR 175A'S ONLY PER 310.16,
 110.14.
 PLEASE VERIFY AND SHOW.
  
 4) NOTE: PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEETS
 AS WERE SUBMITTED UNDER THE OTHER PERMIT. EACH PERMIT
 SHALL CONTAIN ALL DOCUMENTS RELEVANT TO INSTALLATION.?
 FIRE PUMP AND FIRE PUMP CONTROLLER.
 THIS IS NEEDED TO CORRELATE HP RATING, CODE LETTER OF
 MOTOR FOR MAX LOCKED ROTOR CURRENT ETC.
 110.3, 90.7, ETC
 FBC 106.1.2
  
 5) NOTE: PLEASE SEE VALUE ON SCOPE OF WORK WHEN
 APPLICATION IS MADE MAY BE ADJUSTED. PLEASE VERIFY AS
 THE VALUE SEEMS LOW.
 FBC 108.3.
  
 6) NOTE: PLEASE MAKE NOTE OF THE CONDUITS ENTERING THE
 FPC SHALL BE ENCASED IN CONCRETE.
 NFPA-20, NFPA-70
 PLEASE BE SURE THE ABOVE CODES ARE STATED ON PLANS AT A
 MIN.
 PLEASE SEE 695 OF THE NEC AND CHAPTERS 6 AND 7 FOR
 INSTALLATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH