2006-11-02 07:21:11 | ***** UNSAT ********* |
| |
| |
| ** PLEASE KNOW, PLANS HAVE ONLY BEEN SUBMITTED FOR |
| "PLAN REVIEW" ONLY AND HAVE NOT BEEN SUBMITTED FOR |
| PERMIT AT THIS TIME. |
| |
| 1) NOTE: PLEASE KNOW WHEN FINAL APPLICATION IS MADE FOR |
| INSTALLATION AND WIRING FOR FPC, THIS CAN NOT BE DONE |
| BY A GC, CGC ETC. THIS MUST BE AN ELECTRICAL CONTRACTOR |
| WHO APPLIES. |
| |
| 2) NOTE: PLEASE SEE PLANS INDICATE EXISTING FPC, |
| HOWEVER NEW CONTROLLER UNDER SEPARATE PERMIT. THAT |
| PERMIT WAS ONLY TO PLACE CONTROLLER, NOT TO DO ANY |
| ELECTRICAL HOOK UP. PLEASE NOTE ON PLANS AS NEW UNDER |
| "(OTHER PERMIT NUMBER)". |
| |
| 3) NOTE: PLEASE CLARIFY THE OCP ON THE FPC AS SHOWN. |
| SHOWS 1000A, HOWEVER THIS IS BE TAKEN THAT THIS IS THE |
| LRC?? PLEASE INDICATE THE NORMAL/ STANDARD OCP RATING. |
| PLEASE VERIFY THIS AS THE SEC'S SHOWN ARE ONLY SIZED AT |
| 2/0'S WHICH ARE RATED FOR 175A'S ONLY PER 310.16, |
| 110.14. |
| PLEASE VERIFY AND SHOW. |
| |
| 4) NOTE: PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEETS |
| AS WERE SUBMITTED UNDER THE OTHER PERMIT. EACH PERMIT |
| SHALL CONTAIN ALL DOCUMENTS RELEVANT TO INSTALLATION.? |
| FIRE PUMP AND FIRE PUMP CONTROLLER. |
| THIS IS NEEDED TO CORRELATE HP RATING, CODE LETTER OF |
| MOTOR FOR MAX LOCKED ROTOR CURRENT ETC. |
| 110.3, 90.7, ETC |
| FBC 106.1.2 |
| |
| 5) NOTE: PLEASE SEE VALUE ON SCOPE OF WORK WHEN |
| APPLICATION IS MADE MAY BE ADJUSTED. PLEASE VERIFY AS |
| THE VALUE SEEMS LOW. |
| FBC 108.3. |
| |
| 6) NOTE: PLEASE MAKE NOTE OF THE CONDUITS ENTERING THE |
| FPC SHALL BE ENCASED IN CONCRETE. |
| NFPA-20, NFPA-70 |
| PLEASE BE SURE THE ABOVE CODES ARE STATED ON PLANS AT A |
| MIN. |
| PLEASE SEE 695 OF THE NEC AND CHAPTERS 6 AND 7 FOR |
| INSTALLATION. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |