Plan Review Notes
Plan Review Notes For Permit 06100831
Permit Number 06100831
Review Stop E
Sequence Number 3
Notes
Date Text
2007-01-09 07:34:30** UNSAT **
  
 1) NOTE: PLEASE SEE THE CODES SECTION REFERENCE ON
 RISER FOR 310.15B6 DOES NOT APPLY FOR FEEDERS WHICH ARE
 120/208V SYSTEMS. PLEASE SEE THE SECTION AS GIVEN IS
 FOR 120/240V ONLY.
  
 2) NOTE: PLEASE KNOW THE VOLTAGE DROP INDICATED FOR THE
 4TH FLOOR UNIT SHOWN AT 4% IS STILL IN QUESTION. PLEASE
 KNOW AS PER THE CONVERSATION WITH THE ENGINEER THE VD
 WAS LOWER AND IT WAS THE UNDERSTANDING OF THIS OFFICE
 THE CORRECTED VD WAS GOING TO BE SHOWN FOR THIS?
 PLEASE SEE FBC 13-413.1.ABC.1.1.
  
 3) NOTE: PLEASE KNOW THE VALUE FOR THE COMPLETE SCOPE
 OF WORK WAS ADJUSTED FOR ALL UNITS EVEN THOUGH THE
 CURRENT CONTRACTOR IS COMPLETING WORK. PLEASE KNOW THAT
 THE PREVIOUS CONTRACTOR DID NOT HAVE PERMITS OR PLANS
 TO RE-PULL FEEDERS TO THE UNITS ALREADY DONE NOR DID
 THE CONTRACTOR PULL IN THE RIGHT SIZE EQUIPMENT
 GROUNDING CONDUCTOR.
 PLEASE KNOW BASED ON THE STOP WORK /RED-TAG CORRECTION
 NOTICE GIVEN AND THE ADDITIONAL VALUE ADDED FOR SCOPE
 THE ADDITIONAL FEE IS THAT OF $5081.70.
 *** PLEASE KNOW THIS IS WRITTENNOTICE TO THE NEW
 CONTRACTOR THAT AS THIS CONTRACTOR IS TAKING OVER THE
 PROJECT FOR THE NEW UNITS, THIS NEW CONTRACTOR WILL
 ALSO BE RESPONSIBLE FOR ALL THE OTHER UNITS WHICH
 FEEDERS WERE PULLED IN WITHOUT PERMITS. IT IS THE
 RECOMMENDATION OF THIS OFFICE TO VERIFY ALL PREVIOUS
 WORK BE REVIEWED FOR CODE COMPLIANCE AND INSTALLATION
 OF SAID CONDUCTORS WHICH MAY HAVE BEEN DAMAGED IN THE
 INSTALLATION PROCESS.
  
 4) NOTE: PLEASE VERIFY LOADS SHOWN ON PANELS E, F& G
 SPECIFICALLY TO THE LOADS SHOWN ON THE METER CENTERS,
 THEN PLEASE VERIFY LOAD ON METER CENTERS 3 AND 4.
 PLEASE SEE LOAD AFTER ALL DE-RATING IS BEING SHOWN IS A
 MAXIMUM OF500AMPS WHICH THE RATING OF THE MAIN FUSES
 FEEDING METER CENTER. THE METER CENTER IS RATED AT 600
 AMPS; HOWEVER THE MAIN OVER CURRENT PROTECTION IS THAT
 OF 500AMPS WHICH LEAVES NO ROOM FOR EXPANSION OF FUTURE
 LOADS OF ANY KIND.
 90.8, 220, 240, ETC.
 FBC 106.1.2 ADMIN SECITON FOR ADDITIONAL INFORMATION.
  
 5) NOTE: PLEASE KNOW AS THIS WAS ONLY UNDER PLAN REVIEW
 BEFORE THE DATE OF DECEMBER 8TH, 2006, THE CODE
 SECTIONS ON PLANS ALL NEED TO BE REVISED TO SECTIONS
 OUT OF THE 2005 NEC NFPA-70. PLEASE KNOW AS OF DATE
 GIVEN, THE STATE OF FLORIDA ADOPTED THE NEW 2005
 EDITION AND SINCE THIS SCOPE OF WORK WAS NOT APPLIED
 FOR PERMIT UNTIL AFTER THAT DATE THE ITEMS AS NOTED AND
 ALL DESIGNS ARE REQUIRED TO BE UNDER THE NEW CODE.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]