Plan Review Notes
Plan Review Notes For Permit 06100831
Permit Number 06100831
Review Stop E
Sequence Number 2
Notes
Date Text
2006-11-30 19:28:49****** UNSAT2ND REVIEW ******
  
 PLEASE SEE SOME NOTES FROM THE PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING.
  
  
  
 ** PLEASE KNOW, PLANS HAVE ONLY BEEN SUBMITTED FOR
 "PLAN REVIEW" ONLY AND HAVE NOT BEEN SUBMITTED FOR
 PERMIT AT THIS TIME.
  
 1) NOTE:NO, SAME NOTE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE KNOW WHEN FINAL APPLICATION IS MADE FOR
 INSTALLATION AND WIRING FOR FPC, THIS CAN NOT BE DONE
 BY A GC, CGC ETC. THIS MUST BE AN ELECTRICAL CONTRACTOR
 WHO APPLIES.
  
 2) NOTE: NO, SAME NOTE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEETS FOR THE
 NEW METER CENTERS.
 110.3,90.7
 PLEASE SEE OTHER COMMENTS BELOW FOR METER CENTERS.
  
 3) NOTE: OK.
  
 4) NOTE: OK.
  
 5) NOTE: OK, HOWEVER SEE NEW NOTES.
  
 6) NOTE:NO, NOT CLEAR WHAT THIS IS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE RISER SHOWS BUS-DUCT UNDERGROUND TO FPL?
 PLEASE VERIFY THIS. IT IS BEING SHOWN AS EXISTING;
 HOWEVER THIS IS IN QUESTION AT THIS TIME.
 110.3, 90.7.
 IS THIS PERHAPS EITHER A BUS STAB OR DUCT BANK
 EXISTING?
  
 7) NOTE: NO, STILL SHOWN. AS THIS IS BEING INDICATED
 THE MAIN 1 OF 6, PLEASE INDICATE MAIN, HOWEVER NOT IN
 SCOPE ETC.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE REMOVED FIRE PUMP AND ASSOCIATED EQUIPMENT FROM
 RISER WHICH IS NOT IN THIS SCOPE OF WORK.
  
 8) NOTE: OK.
  
 9) NOTE:NO, SAME NOTE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SPECIFY THE CONDUIT TYPE ON ALL RUNS. PLEASE SEE
 SOME CONDUIT FILLS ON NEW PULLS SEEM VERIFY CLOSE,
 PLEASE VERIFY.
 PLEASE SEE TABLES IN CHAPTER 9.
  
 10) NOTE:VOLTAGE DROP PROVIDED, HOWEVER FBC
 13-413.1.ABC.1.1. PLEASE SEE FEEDER WHICH INDICATES 4 %
 ETC AND OTHERS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE VOLTAGE DROP FOR FEEDERS TO THE METER
 CENTERS, AS THE DISTANCES AS SHOWN FOR 4/0'S ETC ARE
 OVER 200FT.
  
 11) NOTE:OK, HOWEVER SEE NOTE ABOVE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE ALSO PROVIDE A WORST CASE VD ON APT/CONDO
 FEEDER(S).
  
 12) NOTE: OK.
  
 13) NOTE: OK.
  
 14) NOTE: OK
  
 15) NOTE:NO? UNCLEAR AT THIS TIME.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE VALUE ON SCOPE OF WORK WHEN APPLICATION IS
 MADE MAY BE ADJUSTED. PLEASE VERIFY AS THE VALUE SEEMS
 LOW. PLEASE KNOW VALUE PANEL FOR EACH UNIT CANE BE
 SUBTRACTED AS THESE WILL BE SEPARATE, HOWEVER ALL NEW
 FEEDERS FOR UNITS, FEEDERS FOR METER CENTERS AND NEW
 METER CENTERS SHALL BE INCLUDED. VALUE SHALL INCLUDE
 ALL LABOR AND MATERIALS EVEN IF ANY EQUIPMENT IS OWNER
 SUPPLIED.
 FBC 108.3.
  
 16) NOTE: OK.
  
 *** NEW NOTE **
  
 1) NOTE: PLEASE SEE FIRE PUMP MAIN/CONTROLLER
 INFORMATION AS SHOWN ON THIS RISER DOES NOT CORRELATE
 WITH THE PUMP CONTROLLER WHICH HAS YET TO BE APPLIED
 FOR.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717