2007-06-07 15:40:48BUILDING REVIEW 4TH CHECKLIST:
  
 1- INFORMATION SUBMITTED NOW IS MISSING THE
 MANUFACTURER'S COMPLETE SPECS FOR LIGHT POST TO BE
 INSTALLED.DESIGNER OF RECORD TO REVIEW AND APPROVE IN
 WRITING SPECS (NOT SIGNING AND SEALING) AS REQUIRED BY
 SEC. 106.3.3CITY AMENDMENTS TO FBC 2004 AND MAKE SURE
 THE POST IS DESIGNED TO MEET CORRESPONDING WIND LOADS
 TO AVOID FUTURE DENIALS.
  
 2- THERE IS NEWENGINEER ON BOARD AND THE FOLLOWING
 COMMENTS NEED TO BE ADDRESSED:
 A) DESIGN CRITERIA USED FOR WIND LOAD ANALYSIS WAS
 BASED ON ASCE 7-04.ASCE EDITION ADOPTED BY FBC 2004
 IS ASCE 7-02. NEED TO REVISE AS REQUIRED.
 B)DRAWING FOR NEW FOOTING ARE NOT LEGIBLE.
 *** THE FOLLOWING INFORMATION IS REQUIRED BY CHAPTER
 471 FLORIDA STATUTE AND SEC. 61G15-23.002 OF FLOIRDA
 ADMINISTRATIVE CODE.
 C) ALL SHEETS NEED TO BE SIGNED, SEALED AND DATED BY
 THE ENGINEER. ALL SHEETS MUST HAVE ORIGINAL SEAL AND
 SIGNATURE.
 D) ALL SHEETS NEED TO HAVE THE ENGINEER' LICENSE
 NUMBER.
  
 ***NOTE:
 ONE SET OF DRAWINGS WAS RETAINED IN THIS OFFICE FOR
 REFERENCE ON FUTURE SUBMITTALS.
  