Plan Review Notes For Permit 06100821 |
Permit Number |
06100821 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2007-01-29 12:43:16 | BUILDING REVIEW THIRD CHECKLIST: | | | | 1-CLARIFY WHAT 'S THE RELATIONSHIP BETWEEN VALMONT | | STRUCTURES SPECIFICATIONS (PAGE 7 OF ENGINEERED PACKAGE | | SUBMITTED) AND ENGINEERED DRAWING E-1.SEE SIZE OF | | ANCHORS ETC.CLARIFY/REVISE AS REQUIRED. | | | | 2-VALMONT STRUCTURES SPECIFICATIONS PAGE 7: | | EFFECTIVE PROJECTED AREA (EPA)DOESN'T WORK FOR | | 140MPH.SEE DIMENSIONAL AND LOAD DATA. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|