Notes |
Date |
Text |
2006-10-25 07:23:19 | DENIED; | | 1.PLEASE SIZE PIPES ON RISER DIAGRAM. | | 2.TWO WAY CLEANOUT REQUIRED AT THE BUILDING DRAIN AND | | BUILDING SEWER JUNCTION SEC 708.3.5. | | 3.THE AUTOMATIC CLOTHES WASHER STACK IS NOT PERMITED TO | | RUN THRU THE WET VENT OF THE OF THE BATHROOM GROUP. | | SEC.909.1 | | ONE SANITARY RISER DIAGRAM MARKED IN RED. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|