Plan Review Notes
Plan Review Notes For Permit 06100780
Permit Number 06100780
Review Stop E
Sequence Number 1
Notes
Date Text
2006-10-24 14:30:29******** UNSAT **********
  
 1) NOTE: PLEASE PROVIDE A PANEL SCHEDULE WHICH
 INDICATES ALL OF THE REQUIRED MINIMUM CIRCUITS. PLEASE
 BE SPECIFIC FOR CIRCUITS TO ALL AREAS AND ROOMS. PLEASE
 SEE FOR INSTANCE ONLY ONE CIRCUIT IS BEING SHOWN IN THE
 LOAD CALCULATIONS FOR THE BATH(S)RMS).
 PLEASE INDICATE FOLLOWING : IE: BED RM #2 LTS, MASTER
 BEDRM RECETPS, KITCHEN LTS, ETC ETC.
 PLEASE INDICATE ALL CONDUCTOR SIZES AND CORRELATE WITH
 OCP DEVICES.
 240.4,408.4, 310.16
  
 2) NOTE: PLEASE SEE NOTES ON PLANS STILL MENTIONS AFCI
 PROTECTION ONLY FOR RECEPTS. WE ARE UNDER THE 2002 NEC.
 210.12B
 PLEASE BE SURE TO LIST ALL AS REQUIRED PER CODE ON THE
 SAME PANEL SCHEDULE WHICH IS REQUIRED PER NOTE #1.
  
 3) NOTE: PLEASE SEE 210.8A6 FOR ALL RECEPTS SERVING
 KITCHEN COUNTER SPACE.
  
 4) NOTE: PLEASE SEE 210.52C3/210.8A6 FOR MISSING
 RECEPT.
  
 5) NOTE: PLEASE SEE NOTES ON PLANS WHICH MENTIONS FUSED
 DISCONNECT FOR SERVICE, YET SERVICE DOES NOT INDICATE
 THIS . PLEASE CORRELATE.
 230.70, 230.70.
 PLEASE SEE PLANS ARE MISSING THE LOCATION OF THE
 SERVICE AND PANEL. 230.70,240.24
 CAN NOT BE VERIFIED FOR CODE COMPLIANCE AT THIS TIME.
  
 6) NOTE: PLEASE STATE THE FOLLOWING RELEVANT CODES ON
 PLANS FOR THE DESIGN AT THIS TIME. 2002 NFPA-70, 2002
 NFPA-72.
  
 7) NOTE: PLEASE INDICATE THE REQUIRED DISCONNECT FOR
 THE WATER HEATER 422.31.
  
 8) NOTE: PLEASE SEE FS 713.13(2) AS THE NOTICE OF
 COMMENCMENT WHICH WAS SUBMITTED WITH PERMITTED
 APPLICATION WAS ALREADY EXPIRED WHEN IT WAS SUBMITTED.
 PLEASE SEE SECTION WHICH STATES WORK SHALL COMMENCE
 WIHTIN 90DAYS OF RECORDING SUCH NOC OR THE NOC SHALL
 BECOME VOID AND IS NO LONGER VALID.
 THE RE-RECORDED NOC IS ONLY REQUIRED AT THE TIME OF
 PICKING UP PERMIT ONCE ISSUED.
  
  
  
 *** NOTE: PLEASE SEE FLORIDA STATUTES 481.221(6).
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]