Plan Review Notes
Plan Review Notes For Permit 06100773
Permit Number 06100773
Review Stop B
Sequence Number 4
Notes
Date Text
2007-06-07 09:13:42BUILDING REVIEW 4TH CHECKLIST:
 1- CONTRACTOR DECLARED VALUATION IN THE PERMIT
 APPLICATION IS TOO LOW BASED ON THE PROPOSED SCOPE OF
 WORK.CONTRACTORTO UPDATE VALUATION OR IT WILL BE
 UPDATEDBASED ON ADETAILED COST ESTIMATE WHICH WILL
 BE TIME CONSUMING.SEC. 108.3 OF CITY AMENDMENTS TO
 FBC 2004.
  
 2- THERE WAS ONLY ONE SET OF PLANS SUBMITTED. THERE
 WERE TWO SETS OF PLANS FOR STAIRS SUBMITTED. NEED TO
 PROVIDE 2 SETS OF PLANS FOR EVERYTHING.
  
 3- SHEET A-1:
 A) TYPICAL WALL SECTION: PROVIDE CALCULATIONS
 SHOWING HOW THE ONE HOUR FIRE RATED WALL ,
 FLOOR/CEILING ASSEMBLY AND ROOF CEILING ASSEMBLY ARE
 ACHIEVED BASED ON THE COMPONENTS USED. SEE COMPLETE
 SEC. 721.6.2. FBC 2004 TO SHOW HOW ONE HR FIRE RATING
 IS ACHIEVED.INFORMATION SHOWN ON PLANS SHOW 1/2" TYPE
 'C' G.W.B. FOR WALLS AND 5/8" TYPE 'C' G.W.B. ON
 CEILINGS.ACCORDING TO MATERIALS SPECIFIED ON THIS
 SECTION, THE ASSEMBLIES DON'T PROVIDE THE ONE HOUR
 REQUIRED FIRE RATING FROM THE SIDE EXPOSED TO FIRE.
 ALSO, NEED TO SPECIFY ALL COMPONENTS OF THE ASSEMBLY.
 EXISTING FLOOR OR EXISTING ROOF IS NOT ENOUGH
 INFORMATION TO DETERMINE A COMPLETE FIRE RATED
 ASSEMBLY. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 B) " OPTIONAL UL DESIGN #P528 CEILING AND WALL
 ASSEMBLY 6" BATT INSULATION METAL CHANNELS @ 12" O.C. 1
 LAYER OF 5/8" GYP. BRD. TYPE 'C'"SPECIFIED AT
 BOTTOM OF TYP. WALL SECTION DOESN'T WORK EITHER. FIRST
 OF ALL THIS ASSEMBLY IS FOR A CEILING ASSEMBLY USING
 METAL TRUSSES.
 ON THE OTHER HAND, A CEILING ASSEMBLY CAN'T BE USED
 INTERCHANGEABLE AS A WALL ASSEMBLY AND CEILING
 ASSEMBLY.
  
  
 C) BUILDING CODE INFORMATION.THIS IS NOT R-1
 OCCUPANCY.
  
 D) PROVIDE CALCULATIONS SHOWING HOW THE ROOF DESIGN
 PRESSURES FOR ZONES 1, 2 AND 3 WERRE ACHIEVED.
 INFORMATION SUBMITTED SHOWS:ZONE 1 (FIELD) 32.3 PSF
 ZONE 2 (4' EDGE) -62.8 PSF AND ZONE 3 (4'X4' CORNERS).
 CLARIFY WHY PERIMETER AND CORNER AREAS HAVE THE SAME
 DESIGN PRESSURES AND WHY THE CALCULATED PRESSURES HAVE
 ONLY POSITIVE PRESSURES IN THE FIELD AND NEGATIVE
 PRESSURES ON PERIMETER AND CORNER AREAS.ON THE OTHER
 HAND DESIGN PRESSURESARE TOO LOWSEE REVISED TABLE
 1609.6.2.1(2) OF FBC 2004.
  
 E) FLOOR PLANS CALL FOR EXTERIOR STAIRS TO BE UNDER
 A SEPARATE PERMIT, BUT STAIR PLANS WERE SUBMITTED AND
 ARE PART OF THE CONTRACTORS SCOPE OF WORK DESCRIBED IN
 THE PERMIT APPLICATION.INCLUDE THIS INFORMATION ON
 VALUATION OF PROJECT. CLARIFY/REVISE AS REQUIRED TO
 AVOID CONFLICTS.
  
 4- SHEET A-2 SHOWSINFORMATION FOR NEW ROOF
 UNDERLAYMENT. IT'S NOT CLEAR IF NEW ROOF IS PART OF
 THIS PERMIT OR NOT.OWNER STATED THAT NO ROOF WORK
 WILL BE PERFORMED. ON THE OTHER HAND IF ROOF WORK IS
 REQUIRED, THEN CORRESPONDING PRODUCT APPROVAL IS
 REQUIRED.ALSO, COORDINATE INFORMATION GIVEN ON TYP.
 WALL SECTION.
  
 5- SHEET A-2 SHOWS INFORMATION FOR INTERIOR BEARING
 WALL.SHEET A-1 DOESN'T SHOW WHICH ARE THE INTERIOR
 BEARING WALLS TO BE REPAIRED.
 ALSO, NEED TO KEEP IN MIND THAT TENANT SEPARATION WALLS
 NEED TO BE ONE HOUR FIRE RATED ASSEMBLIES.
  
 6- FOUNDATION NOTES ON SHEET A-2 CALLS FOR 2000 PSF
 SOIL BEARING CAPACITY, WHILE INFORMATION ON SHEET A-1
 CALLS FOR 2500 PSF SOIL BEARING CAPACITY. REVISE AS
 REQUIRED.
  
 7- FLOOR PLANS AND EXTERIOR ELEVATIONS SHOW SOME
 WINDOWS AND DOORS AS EXISTING.THEY ARE NOT EXISTING,
 THEY ARE PART OF THIS SCOPE OF WORK BECAUSE THEY WERE
 INSTALLED WITHOUT PERMIT.
  
 8- STAIRS AND HANDRAILSNED TO COMPLY WITH COMPLETE
 SEC.1009 OF FBC 2004.REVISE TREADS, RISERS,
 OBSTRUCTIONS, HANDRAIL HEIGHT, PROJECTIONS, DIMENSIONS
 ETC.REVISE DRAWINGS AS REQUIRED.
  
 9- HANDRAILS NEED TO COMPLY WITH SEC. 1012 FBC 2004.
  
 10- CLARIFY WHY STAIRS ARE DESIGNED AS ENCLOSED. SEE
 SHEET A-1 OF STAIR DRAWINGS.
  
 11- STAIR DRAWINGS SHOW WINDOWS ON REAR ELEVATION TO BE
 IMPACT GLASS WINDOWS. PROVIDE PRODUCT APPROVALFOR
 IMPACT WINDOWS. SEE ITEM #7 ABOVE.
  
 12-NEED TO PROVIDE NEW RECORDED NOTICE OF
 COMMENCEMENT BECAUSE THE CONTRACTOR WAS CHANGED.
  
 13- THERE ARE 2 DIFFERENT NOA'S SUBMITTED FOR THE
 SINGLE HUNG WINDOWS.ONE IS NOA 02-0723.04 AND THE
 OTHER IS 03-1210.06. PROVIDE ONLY TWO COPIES (REVIEWED
 BY THE ENGINEER OF RECORD) FOR SPECIFIC NOA TO BE
 USED.
  
 ALSO, MAKE SURE DRAWINGS MATCH SPECIFIC PRODUCT
 APPROVAL. EG: INFORMATION SUBMITTED WITH NOA 02-0729.04
 DOES'NT MATCH.
  
 14- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 (REVIEWED AND APPROVED BY THE ENGINEER OF RECORD)
 FOR:
 A)WINDOW MULLIONS.
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS/SECTIONS.
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561) 805-6712