Plan Review Notes
Plan Review Notes For Permit 06100773
Permit Number 06100773
Review Stop B
Sequence Number 3
Notes
Date Text
2007-02-22 09:12:46BUILDING REVIEW THIRD CHECKLIST:
 1- SCOPE OF WORK DESCRIPTION SHOWN ON PERMIT
 APPLICATION DOESN'T MATCH SCOPE OF WORK SHOWN ON PLANS
 SUBMITTED. PERMIT APPLICATION SAYS "INSTALL 5 NEW
 WINDOWS, 1 DOOR, SMALL STUCCO REPAIR AND REPAIR CEMENT
 FOUNDATION".ON THE OTHER HAND PLANS SHOW COMPLETE NEW
 WALLS, REPLACEMENT OF ALL WINDOWS AND DOORS,REPLACING
 WINDOWS FOR DOORS ON SECOND FLOOR, ADDING A NEW LANDING
 AND STAIRWAY FOR NEW DOORS ON SECOND FLOOR. INFORMATION
 ON PERMIT APPLICATION NEEDS TO MATCH PLANS. ALSO,
 REVISE DECLARED PERMIT VALUATION TO REFLECT PROPOSED
 SCOPE OF WORK. INCLUDE ENGINEERING SERVICES. OTHERWISE,
 PERMIT VALUATION WILL BE ESTIMATED AS REQUIRED BY SEC.
 108.3 CITY AMENDMENTS TO FBC 2004.
  
 2- ENGINEER PLANS CALL FOR REPLACEMENT OF WINDOWS ON
 SECOND FOR FOR NEW DOORS. NEED TO PROVIDE COMPLETE
 FRAMING DETAILS FOR NEW DOOR OPENINGS. ALSO, NEED TO
 PROVIDE COMPLETE SECTIONS/DETAILS AND SPECIFICATIONS
 FOR NEW LANDING AND STAIRWAY TO VERIFY COMPLIANCE WITH
 SEC. 1009AND SEC. 1607.7 FBC 2004.
  
 3- PROPOSED STAIRWAY AND LANDING NEED TO BE APPROVED BY
 THE HISTORIC DISTRICT AND ZONING.THIS IS NEW
 INFORMATION AND WAS NOT REVIEWED BY THEM.
  
 4- A) ENGINEER CALCULATIONS FOR WIND PRESSURES DON'T
 MATCH INFORMATION GIVEN ON DRAWING 1.1.CHECK BUILDING
 EXPOSURE AND APPLICABLE ENCLOSURE CLASSIFICATION.
 REVISE AS REQUIRED.
  
 B) ENGINEER TO SIGN AND SEAL EACH SHEET OF ENERGY
 CALCULATIONS AND PROVIDE THE FIRM'S CERTIFICATE OF
 AUTHORIZATION NUMBER AS REQUIRED BY CHAPTER 471 FLORIDA
 STATUTES AND SEC. 61G15-23.002 FLORIDA ADMINISTRATIVE
 CODE.
  
  
 5- THERE IS SOME HAND WRITTEN INFORMATION ON DRAWING
 1.1 ON SUPPLEMENTAL FOOTER CONNECTION DETAIL.
 ALTERATIONS OR HANDWRITTEN INFORMATION IS NOT
 ACCEPTABLE. ALL REVISIONS OR ADDITIONAL INFORMATION
 NEEDS TO BE DONE ON THE ORIGINALDRAWINGS, NOT ON THE
 SIGNED AND SEALED COPIES. REVISE AS REQUIRED.
  
 6- ATTACHMENT/FASTENER SPECIFICATIONS TABLE:
 A) REVISE FASTENER SIZE SPECIFIED FOR SOFFIT WIRE
 LATH ATTACHMENT. SEE ASTM C926 AND ASTM C1063 FOR
 CORRECT SIZE.
  
 B) REVISE FASTENER SPACING FOR ROOF ZONE #3 AS
 REQUIRED BY TABLE 2304.9.1 FBC 2004.
  
 C) PROVIDE ONLY THE INFORMATION THAT APPLIES TO THIS
 JOB.
  
 7- NEED TO SPECIFY SAFETY GLASS FOR WINDOWS W2 AND W5
 AS REQUIRED BY SEC. 2406.3 FBC 2004.
  
 8-FLOOR PLANS CALL FOR W2 WINDOWS ON FIRST FLOOR,
 WHILE EXTERIOR ELEVATION CALLS FOR W5 WINDOWS ON FIRST
 FLOOR.REVISE FLOOR PLANS AND ELEVATIONS TO MATCH.
 SAME COMMENT APPLIES TO SECOND FLOOR.
  
 9- FIRST FLOOR PLAN CALLS FOR NEW 2X4 BEARING WALL
 BETWEEN KITCHEN AND BATH. PROVIDE COMPLETE
 DETAIL/SPECS. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 10- A) PLANS CALL FOR NEW 72"X80" SLIDING GLASS DOOR.
 PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE 9B-72.
 DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING THE
 PRODUCT APPROVAL AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004.
  
 B) PROVIDE COMPLETE FRAMING DETAIL FOR NEW SLIDING
 GLASS DOOR. SEC. 106.1.2 CITY AMENDMENTSTO FBC 2004
  
 11- ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND
 APPROVED IN WRITING AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004.SOME PRODUCT APPROVALS ARE
 MISSING THE REVIEW STAMP. ONLY ONE COPY WAS STAMPED.
 EG; STORM PANELS AND SINGLE HUNG WINDOWS.
  
 12- EXTERIOR WALL OPENING SCHEDULE ON DRAWING 3:
 A) WINDOWS TO COMPLY WITH SEC. 1005 FBC IS THE WRONG
 SEC. SEE FBC 2004 AND REVISE AS REQUIRED.
  
 B) SECOND NOTE CALLS FOR IMPACT RESISTANT WINDOWS.
 PRODUCT APPROVAL SUBMITTED IS FOR NON-IMPACT WINDOWS.
 REVISE AS REQUIRED.
 ALSO, CLARIFY WHY PRODUCT APPROVALS TO BE REVIEWED AND
 SUBMITTED PRIOR TO TIE BEAM INSPECTION .PRODUCT
 APPROVALS NEED TO BE SUBMITTED AT TIME OF PERMIT
 APPLICATION AND THIS IS A WOOD FRAMED HOUSE.
  
 13- ENGINEER TO PROVIDE ENGINEER ANALYSIS SHOWING HOW
 THE SPECIFIED ATTACHMENT OF FRAMED WALL TO FOOTING WILL
 RESIST ALLCALCULATED WIND LOADS. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 14- ENGINEER TO READ ATTACHED COPY OF FLORIDA STATUTE
 553.80(2)(B) REGARDING DESIGN PROFESSIONAL DOCUMENTS
 AND PLAN REVIEW FEES.
  
 15- STORM SHUTTERS:
 A) CLARIFY HOW ARE PANELS INSTALLED WITH 3" EDGE
 DISTANCE AT BOTTOM OF PANEL IS WINDOW FRAMING IS ONLY
 3" MAX. (SEE STRUCTURAL DRAWING #2). REVISE AS
 REQUIRED.
  
 B) PROVIDE 2 COPIES OF INSTALLATION SCHEDULE
  
 16- NOTICE OF COMMENCEMENT IS EXPIRED AFTER 90 DAYS IF
 WORK IS NOT COMMENCED. SEE SEC. 713.13 FLORIDA STATUTE.
 NEED RE-RECORDED NOTICE OF COMMENCEMENT.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER