Plan Review Notes
Plan Review Notes For Permit 06100773
Permit Number 06100773
Review Stop B
Sequence Number 2
Notes
Date Text
2006-11-22 16:38:43BUILDING REVIEW 2ND CHECKLIST:
 1- SUBMITTED ENGINEERING PLANSDON'T PROVIDE ALL
 STRUCTURALINFORMATION REQUIRED. SEE RESTORATION
 PROPOSAL LETTER FROM BUILDINGCONTRACTOR. DRAWINGS TO
 INCLUDE:
 * INSTALLATION OF JACKS TO SUPPORT ROOF.
 **CLARIFY WHY THE ROOFNEEDS TO BE SUPPORTED AND
 PROVIDE COMPLETE SPECIFICATIONS FOR STRUCTURAL WORK TO
 BE PERFORMED.
 ***REMOVAL OF 2X6 STUD WALL (NORTH).PROVIDE COMPLETE
 STRUCTURAL SPECS FOR NEW WALL, INCLUDING SHEATHING
 FASTENING SIZE AND SPACING AND STUCCO THICKNESS.
 ****ADDRESS CONCRETE BLOCK CRACKS AND SPECIFIC SPECS
 FOR REPAIRS.
  
 2- ENGINEERED DRAWINGS:
 A) DON'T MATCH KEY PLAN SUBMITTED FOR WINDOW SIZE.
 REVISE EITHER ONE AS REQUIRED TO SHOW ACTUAL
 CONDITIONS.SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 B) CLEARLY IDENTIFY TYPE OF CONSTRUCTION. IS THIS
 TYPE V A OR B?SEE SEC. 602 FBC 2004.
  
 C) REVISE DESIGN CRITERIA REFERENCE. THERE ARE NOT
 SECTIONS R4403.5 ANDR4403.9.
  
 D) NEED TO PROVIDE FIRM'S CERTIFICATE OF
 AUTHORIZATION NUMBER AS REQUIRED BY FLORIDA
 ADMINISTRATIVE CODE SEC. 61G15-23.002.
  
 E) SPECIFY HOW ARE EXISTING JOISTS FASTENED TO NEW
 FOOTING. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 F) SPECIFY HOW MUCH EMBEDMENT IS REQUIRED FOR NEW
 1/2" WEDGE ANCHORS SPECIFIED ON SUPPLEMENTAL FOOTING.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 3- REVISE ENGINEER DESIGN PRESSURES CALCULATIONS:
 A) IMPORTANCE FACTOR AND CATEGORY ARE INCORRECT. SEE
 ASCE-02 FOR CORRECT INFORMATION ACCORDING TO BUILDING
 TYPE.
  
 B) IDENTIFY EACH WINDOW AND DOOR OPENING WITH
 CORRESPONDING DESIGN PRESSURES. ALSO, IDENTIFY IF
 OPENING IS LOCATED AT END OR INTERIOR ZONE. SEC. 1609
 FBC 2004 AND SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 C) NEED TWO COPIES WITH ENGINEER'S ORIGINAL SEAL AND
 SIGNATURE AND DATE AS REQUIRED BY CHAPTER 471 FLORIDA
 STATUTES. ONLY ONE PROVIDED.
  
 D) NEED TO PROVIDEENGINEERING FIRM CERTIFICATE OF
 AUTHORIZATION NUMBER AS REQUIRED BY FLORIDA
 ADMINISTRATIVE CODE SEC. 61G15-23.002.
  
 E) NEED ENGINEER'SNAME AS REQUIRED BY F.A.C. SEC.
 61G15-23.002.
  
 4- STORM SHUTTERS:
 A) PROVIDE KEY PLAN AND COMPLETE INSTALLATION
 SCHEDULE. SEE ATTACHED COPY AND PROVIDE ALL SPECIFIC
 INFORMATION FOR PROPOSED INSTALLATION. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
  
 5- PROVIDE PRODUCT APPROVAL FOR ALL SIMPSON OR USP
 CONNECTORS IF THEY ARE SPECIFIED ON ENGINEERING PLANS.
 ***AND ENGINEER TO REVIEW AND APPROVE THEM AS REQUIRED
 BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 6- OWES $1733.46 FOR 4X FEE FOR WORK WITHOUT PERMIT RED
 TAG.
  
 7- NEED TO APPLY FOR PERMITS FOR THE OTHER TRADES AS
 REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712