2006-11-22 16:38:43 | BUILDING REVIEW 2ND CHECKLIST: |
| 1- SUBMITTED ENGINEERING PLANSDON'T PROVIDE ALL |
| STRUCTURALINFORMATION REQUIRED. SEE RESTORATION |
| PROPOSAL LETTER FROM BUILDINGCONTRACTOR. DRAWINGS TO |
| INCLUDE: |
| * INSTALLATION OF JACKS TO SUPPORT ROOF. |
| **CLARIFY WHY THE ROOFNEEDS TO BE SUPPORTED AND |
| PROVIDE COMPLETE SPECIFICATIONS FOR STRUCTURAL WORK TO |
| BE PERFORMED. |
| ***REMOVAL OF 2X6 STUD WALL (NORTH).PROVIDE COMPLETE |
| STRUCTURAL SPECS FOR NEW WALL, INCLUDING SHEATHING |
| FASTENING SIZE AND SPACING AND STUCCO THICKNESS. |
| ****ADDRESS CONCRETE BLOCK CRACKS AND SPECIFIC SPECS |
| FOR REPAIRS. |
| |
| 2- ENGINEERED DRAWINGS: |
| A) DON'T MATCH KEY PLAN SUBMITTED FOR WINDOW SIZE. |
| REVISE EITHER ONE AS REQUIRED TO SHOW ACTUAL |
| CONDITIONS.SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| |
| B) CLEARLY IDENTIFY TYPE OF CONSTRUCTION. IS THIS |
| TYPE V A OR B?SEE SEC. 602 FBC 2004. |
| |
| C) REVISE DESIGN CRITERIA REFERENCE. THERE ARE NOT |
| SECTIONS R4403.5 ANDR4403.9. |
| |
| D) NEED TO PROVIDE FIRM'S CERTIFICATE OF |
| AUTHORIZATION NUMBER AS REQUIRED BY FLORIDA |
| ADMINISTRATIVE CODE SEC. 61G15-23.002. |
| |
| E) SPECIFY HOW ARE EXISTING JOISTS FASTENED TO NEW |
| FOOTING. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| |
| F) SPECIFY HOW MUCH EMBEDMENT IS REQUIRED FOR NEW |
| 1/2" WEDGE ANCHORS SPECIFIED ON SUPPLEMENTAL FOOTING. |
| SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| |
| 3- REVISE ENGINEER DESIGN PRESSURES CALCULATIONS: |
| A) IMPORTANCE FACTOR AND CATEGORY ARE INCORRECT. SEE |
| ASCE-02 FOR CORRECT INFORMATION ACCORDING TO BUILDING |
| TYPE. |
| |
| B) IDENTIFY EACH WINDOW AND DOOR OPENING WITH |
| CORRESPONDING DESIGN PRESSURES. ALSO, IDENTIFY IF |
| OPENING IS LOCATED AT END OR INTERIOR ZONE. SEC. 1609 |
| FBC 2004 AND SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| |
| C) NEED TWO COPIES WITH ENGINEER'S ORIGINAL SEAL AND |
| SIGNATURE AND DATE AS REQUIRED BY CHAPTER 471 FLORIDA |
| STATUTES. ONLY ONE PROVIDED. |
| |
| D) NEED TO PROVIDEENGINEERING FIRM CERTIFICATE OF |
| AUTHORIZATION NUMBER AS REQUIRED BY FLORIDA |
| ADMINISTRATIVE CODE SEC. 61G15-23.002. |
| |
| E) NEED ENGINEER'SNAME AS REQUIRED BY F.A.C. SEC. |
| 61G15-23.002. |
| |
| 4- STORM SHUTTERS: |
| A) PROVIDE KEY PLAN AND COMPLETE INSTALLATION |
| SCHEDULE. SEE ATTACHED COPY AND PROVIDE ALL SPECIFIC |
| INFORMATION FOR PROPOSED INSTALLATION. SEC. 106.1.2 |
| CITY AMENDMENTS TO FBC 2004. |
| |
| 5- PROVIDE PRODUCT APPROVAL FOR ALL SIMPSON OR USP |
| CONNECTORS IF THEY ARE SPECIFIED ON ENGINEERING PLANS. |
| ***AND ENGINEER TO REVIEW AND APPROVE THEM AS REQUIRED |
| BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| |
| 6- OWES $1733.46 FOR 4X FEE FOR WORK WITHOUT PERMIT RED |
| TAG. |
| |
| 7- NEED TO APPLY FOR PERMITS FOR THE OTHER TRADES AS |
| REQUIRED. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561)805-6712 |