2006-11-17 18:27:36BUILDING REVIEW 2ND CHECKLIST:
  
 ***NOTE: NONE OF THE COMMENTS FROM 1ST CHECKLIST WERE
 ADDRESSED.BELOW COMMENTS ARE COPIED FROM FIRST
 CHECKLIST. NEED TO SPECIFY ROOM WERE EGRESS IS LOCATED
 AND INDICATE IF ACCORDION SHUTTERS WILL HAVE INSIDE
 LOCK. ALSO, NEED TO PROVIDE SOME SORT OF COMPLETE
 INSTALLATION SCHEDULE LIKE THE ATTACHED SAMPLE THAT HAS
 ALL REQUIRED INFORMATION TO PERFORM PLAN REVIEW.
  
 1- CLARIFY HOW ARE SLIDERS COMPLYING WITH EGRESS
 REQUIREMENTS OF SEC. R310.4 2004 FLORIDA RESIDENTIAL
 CODE IF THOSE OPENINGS ARE GOING TO HAVE ACCORDION
 SHUTTERS.ALSO, CLEARLY DEFINE ROOM WHERE SLIDERS ARE
 BECAUSE OPENING CAN'T BE LOCATED IN A ROOM THAT CAN BE
 LOCKED.
  
 2- PROVIDE COMPLETE INSTALLATION SCHEDULE IN ORDER TO
 VERIFY COMPLIANCE WITH PROPOSED INSTALLATION.SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004. SEE ATTACHED COPY
 OF CITY' S INSTALLATION SCHEDULE SAMPLE AND PROVIDE ALL
 REQUIRED INFORMATION TO PROPERLY PERFORM PLAN REVIEW.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712