Plan Review Notes For Permit 06100734
Permit Number 06100734
Review Stop M
Sequence Number 1
Notes
Date Text
2006-11-01 12:20:19*** DENIED ***
 1) SEE PLANS PG. AC-2.1, HP-E4 NEW 10X8 FRESH AIR DUCT
 THROU FIRE WALL AT PORTFOLIO MANAGER ROOM #163 , NEEDS
 A FIRE DAMPER, PER 2004 FBC/M 607.5.1.
  
 2) SEE PLANS PG. AC-2.1, NEW 6" FLEX DUCT THROU FIRE
 WALL FROM CORRIDOR #2 TO CORR. #3A NEEDS A FIRE DAMPER,
 PER 2004 FBC/M 607.5.1.
  
 3) SEE ELECTRICAL REVIEW NOTES 1 AND 2, PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.