Plan Review Notes For Permit 06100734 |
Permit Number |
06100734 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-12-05 11:32:46 | *****DENIED***** | | | | | | | | 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 2.CONSTRUCTION AND (OR) DEMOLITION OPERATIONS IN THE | | WORK SITE AREA SHALL NOT INTERFERE OR HINDER ACCESS OR | | EGRESS FROM OTHER AREA AREAS OF THE BUILDING. | | | | 3.IF THE FIRE ALARM SYSTEM IS MODIFIED DUE TO THE | | SCOPE OF THE WORK, SEPARATE PERMIT AND PLANS ARE | | REQUIRED. | | | | 4.REFERENCE SHALL BE MADE TO WEST PALM BEACH FIRE | | RESCUE (WPBFR) DEPARTMENT ON SHEET A-1.0 GENERAL DEMO | | NOTE #10. | | | | 5.AS PER WPBFR, DUCT DETECTORS SHALL INITIATE A | | GENERAL FIRE ALARM.AMEND GENERAL FIRE ALARM NOTE #17, | | SHEET E-2.2. | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCEESS, INCLUDE A | | RESPONSE LETTER INDICATING HOW/WHERE EACH ITEM WAS | | ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|