2006-12-05 11:32:46*****DENIED*****
  
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.CONSTRUCTION AND (OR) DEMOLITION OPERATIONS IN THE
 WORK SITE AREA SHALL NOT INTERFERE OR HINDER ACCESS OR
 EGRESS FROM OTHER AREA AREAS OF THE BUILDING.
  
 3.IF THE FIRE ALARM SYSTEM IS MODIFIED DUE TO THE
 SCOPE OF THE WORK, SEPARATE PERMIT AND PLANS ARE
 REQUIRED.
  
 4.REFERENCE SHALL BE MADE TO WEST PALM BEACH FIRE
 RESCUE (WPBFR) DEPARTMENT ON SHEET A-1.0 GENERAL DEMO
 NOTE #10.
  
 5.AS PER WPBFR, DUCT DETECTORS SHALL INITIATE A
 GENERAL FIRE ALARM.AMEND GENERAL FIRE ALARM NOTE #17,
 SHEET E-2.2.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCEESS, INCLUDE A
 RESPONSE LETTER INDICATING HOW/WHERE EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW