Plan Review Notes
Plan Review Notes For Permit 06100734
Permit Number 06100734
Review Stop E
Sequence Number 1
Notes
Date Text
2006-10-30 07:50:52******** UNSAT ************
  
 1) NOTE: PLEASE SEE COVER SHEET WHICH REFLECT ADDRESS
 OF JOB AT 4100 OKEECHOBEE BLVD AS WELL AS 3111 S
 DIXIE.
  
 PLEASE ALSO SEE THE JURISDICTION IS NOT IN PALM BEACH
 COUNTY. JOB-SITE LOCATION IN THE CITY OF WEST PALM
 BEACH.
  
 2) NOTE: PLEASE SEE MISSING INFORMATION REQUIRED ON
 TITLE BLOCKS FOR ARCHITECTURAL FIRM. PLEASE SEE FAC
 61G1-16.004 AND FS 481.219.
 MISSING CERTIFICATE OF AUTHORIZATION NUMBER/ FIRM
 LICENSE NUMBER.
 THIS IS REQUIRED ON ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER REVIEWER(S).
  
 3) NOTE: PLEASE SEE THE FOLLOWING MINIMUM CODES ARE
 REQUIRED ON PLANS. 2002 NFPA-70, 2002 NFPA-72, 2003
 NFPA-101 .
 **AS STATED ON PLANS, THE "LATEST EDITION " WHICH IS
 AVAIABLE IS NOT YET ADOPTED BY THE STATE> (NEC).
  
 4) NOTE; PLEASE SEE AREAS WHICH ARE SHOWN AS COMMON
 AREA CORRIDORS YET SHOW ELECTRICAL FOR RECEPT AND HVAC
 BEING FED FROM A TENANT SPACE. PLEASE KNOW, NO COMMON
 AREAS MAY BE FED FROM FROM AN TENANT OCCUPANCY. 210.25,
 90.4.
  
 5) NOTE: PLEASE SEE PANEL SCHEDULE FOR "H2" SHOWS OTHER
 ELECTRICAL HOWEVER COULD NOT LOCATE WHAT OR WHERE THESE
 ITEMS ARE??
 PLEASE ALSO SEE LOADS ON THIS PANEL IS SHOWN AS XXXXX
 (BLANK), PLEASE COMPLETE.
 220, 215.5,
 FBC 106.1.2 ADMIN SECT.
  
 6) NOTE: PLEASE SEE RISER AND EXPLAIN HOW FEEDERS FROM
 FPL ARE ROUTED TO THE GUTTER. RISER SEEMS TO SHOW THE
 CT/METER ON THE LOAD SIDE OF THE MDP???
 PLEASE CLARIFY AND REVISE RISER. AS SHOWN DOES NOT
 CORRELATE WITH MIN FPL SERVICE STANDARDS OR NEC. 230.
  
 7) NOTE: PLEASE SEE PANEL INDICATE CIRCUITING FOR NEW
 ROOMS.
 PLEASE SEE PANEL "G" IS BEING SHOWN BEING SHOWN AS 125A
 RATED, YET RISER SHOWS A 150A MAIN DISCONNECT FEEDING
 SAID PANEL.
 PLEASE SEE 240, 230 ETC
  
 8) NOTE: PLEASE SUBMIT THE AIC RATINGS FOR NEW
 DISCONNECTS ARE SHOWN ON RISER. PLEASE SEE 110.9,
 240.12
  
 9) NOTE: PLEASE CLARIFY AND SHOW ALL CONTINUOUS LOADS
 AT 125%. 215.3, 230.42
  
 10) NOTE: PLEASE BE SURE ALL SEALS ARE RAISED, CLEAR
 AND VISABLE WITH ALL INFORMATION AS REQUIRED ON SAID
 SEAL.
 PLEASE SEE SOME ARE NOT VISABLE EVEN WHEN SHADING WITH
 PENCIL.
 FS471.025
 PLEASE BE SURE THEY ARE ALSO SIGNED WITH LEGAL
 SIGNATURE.
  
 11) NOTE: PLEASE SEE FBC 13-101.1.3, METHOD "A" MAY NOT
 BEUSED.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]