Date |
Text |
2006-10-30 07:50:52 | ******** UNSAT ************ |
| |
| 1) NOTE: PLEASE SEE COVER SHEET WHICH REFLECT ADDRESS |
| OF JOB AT 4100 OKEECHOBEE BLVD AS WELL AS 3111 S |
| DIXIE. |
| |
| PLEASE ALSO SEE THE JURISDICTION IS NOT IN PALM BEACH |
| COUNTY. JOB-SITE LOCATION IN THE CITY OF WEST PALM |
| BEACH. |
| |
| 2) NOTE: PLEASE SEE MISSING INFORMATION REQUIRED ON |
| TITLE BLOCKS FOR ARCHITECTURAL FIRM. PLEASE SEE FAC |
| 61G1-16.004 AND FS 481.219. |
| MISSING CERTIFICATE OF AUTHORIZATION NUMBER/ FIRM |
| LICENSE NUMBER. |
| THIS IS REQUIRED ON ALL SHEETS AND FOR ALL TRADES |
| WHETHER OR NOT COMMENT IS MADE BY OTHER REVIEWER(S). |
| |
| 3) NOTE: PLEASE SEE THE FOLLOWING MINIMUM CODES ARE |
| REQUIRED ON PLANS. 2002 NFPA-70, 2002 NFPA-72, 2003 |
| NFPA-101 . |
| **AS STATED ON PLANS, THE "LATEST EDITION " WHICH IS |
| AVAIABLE IS NOT YET ADOPTED BY THE STATE> (NEC). |
| |
| 4) NOTE; PLEASE SEE AREAS WHICH ARE SHOWN AS COMMON |
| AREA CORRIDORS YET SHOW ELECTRICAL FOR RECEPT AND HVAC |
| BEING FED FROM A TENANT SPACE. PLEASE KNOW, NO COMMON |
| AREAS MAY BE FED FROM FROM AN TENANT OCCUPANCY. 210.25, |
| 90.4. |
| |
| 5) NOTE: PLEASE SEE PANEL SCHEDULE FOR "H2" SHOWS OTHER |
| ELECTRICAL HOWEVER COULD NOT LOCATE WHAT OR WHERE THESE |
| ITEMS ARE?? |
| PLEASE ALSO SEE LOADS ON THIS PANEL IS SHOWN AS XXXXX |
| (BLANK), PLEASE COMPLETE. |
| 220, 215.5, |
| FBC 106.1.2 ADMIN SECT. |
| |
| 6) NOTE: PLEASE SEE RISER AND EXPLAIN HOW FEEDERS FROM |
| FPL ARE ROUTED TO THE GUTTER. RISER SEEMS TO SHOW THE |
| CT/METER ON THE LOAD SIDE OF THE MDP??? |
| PLEASE CLARIFY AND REVISE RISER. AS SHOWN DOES NOT |
| CORRELATE WITH MIN FPL SERVICE STANDARDS OR NEC. 230. |
| |
| 7) NOTE: PLEASE SEE PANEL INDICATE CIRCUITING FOR NEW |
| ROOMS. |
| PLEASE SEE PANEL "G" IS BEING SHOWN BEING SHOWN AS 125A |
| RATED, YET RISER SHOWS A 150A MAIN DISCONNECT FEEDING |
| SAID PANEL. |
| PLEASE SEE 240, 230 ETC |
| |
| 8) NOTE: PLEASE SUBMIT THE AIC RATINGS FOR NEW |
| DISCONNECTS ARE SHOWN ON RISER. PLEASE SEE 110.9, |
| 240.12 |
| |
| 9) NOTE: PLEASE CLARIFY AND SHOW ALL CONTINUOUS LOADS |
| AT 125%. 215.3, 230.42 |
| |
| 10) NOTE: PLEASE BE SURE ALL SEALS ARE RAISED, CLEAR |
| AND VISABLE WITH ALL INFORMATION AS REQUIRED ON SAID |
| SEAL. |
| PLEASE SEE SOME ARE NOT VISABLE EVEN WHEN SHADING WITH |
| PENCIL. |
| FS471.025 |
| PLEASE BE SURE THEY ARE ALSO SIGNED WITH LEGAL |
| SIGNATURE. |
| |
| 11) NOTE: PLEASE SEE FBC 13-101.1.3, METHOD "A" MAY NOT |
| BEUSED. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |