2006-11-15 13:40:17BUILDING PLAN REVIEW
 PERMIT: 06100712
 ADD: 6893 ISLA VISTA DR.
 CONT:VANKIRK & SONS INC.
 TEL: (954)755-4402
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW :1ST
 ACTION: DENIED
  
 1) R4101.6.1. THE ENGINEERING DESIGN OF THE SPA SHALL
 BE IN CONFORMANCE WITH ONE OF THE ANSI STANDARDS IN
 THIS SECTION. BUILDING PROVISO:
 TO BE IN PLACE AT C.O.:
  
 2) 13-612.1.ABC.2.3.2 COVERS REQUIRED.
 SPAS AND HEATED SWIMMING POOLS SHALL BE
 EQUIPPED WITH A COVER DESIGNED TO
 MINIMIZE HEAT LOSS.
  
 3)FBC. 106.1.1CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITYAS DETERMINED BY THE BUILDING
 OFFICIAL.THE ENGINEER SEAL IS NOT LEGIBLE. SEE F.A.C.
 61G15-23.002.
  