2006-12-23 14:28:16 | *** UNSAT 2ND REVIEW *** |
| |
| ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW AND SOME |
| NEW NOTES DUE TO PLANS SUBMITTED. |
| |
| 1) NOTE:NO, SAME COMMENT BASED ON PLANS SUBMITTED |
| SCOPE OF WORK FAR EXCEEDS THAT OF THE VALUE ON PERMIT |
| APPLICATION. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE THE VALUATION FOR SCOPE OF WORK APPLIED FOR |
| SHALL BE BASED ON ALL LABOR AND MATERIALS EVENS OF |
| OWNER SUPPLIED. PLEASE SEE THE VALUE SEEMS VERY LOW FOR |
| THIS FOUNDATION AND AMOUNT OF CONCRETE/STEEL ETC WORK |
| SHOWN. PLEASE SEE BUILDING REVIEW NOTES. |
| FBC ADMIN SECT 108.3 |
| |
| 2) NOTE:NO, PLEASE SEE MISSING INFORMATION AS |
| PREVIOUSLY STATED IS STILL NOT SHOWN. |
| PLEASE SEE MISSING PRINTED NAME FOR ENGINEER. |
| PLEASE SEE MISSING PRINTED LICENSE NUMBER |
| PLEASE SEE MISSING CERTIFICATE OF AUTHORIZATION |
| NUMBER. |
| PLEASE ALSO SEE NEW NOTE BELOW. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE MISSING INFORMATION FOR TITLE BLOCKS AS |
| REQUIRED UNDER FLORIDA STATUTES 481.219/471.023 FAC |
| 61G1-16.004, 61G15-23.002 |
| |
| 3) NOTE: OK/NO, IT IS UNCLEAR AS THE PLANS SHOW MORE |
| THAN ONLY FOOTINGS. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE REVIEW COMMENTS UNDER THE MAIN BUILDING |
| PERMITS. |
| PLEASE SUPPLY SLAB PLANS FOR ELECTRICAL CONDUIT |
| INSTALLATION UNDER SLAB. |
| 215.5, 230.70, 230.6, 230.70 ETC. |
| PLEASE BE SURE TO SEE COMMENTS UNDER BLDG REVIEW AS |
| THIS MAY VERY WELL AFFECT THE ELECTRICAL CONDUIT |
| LOCATION. |
| |
| 4) NOTE: OK, HOWEVER NEED ONLY SHOW DETAIL AS THE |
| SERVICE INFORMATION IS NOT BEING REVIEWED. THIS IS OK, |
| HOWEVER DUE TO OTHER COMMENTS, PLANS WILL BE REVISED. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE ALSO SUBMIT GROUNDING ELECTRODE CONNECTION |
| DETAIL AS REQUIRED PER 250.50. (FOOTER STEEL, UNDER |
| GROUND COLD WATER PIPES ETC REQUIRED). THERE ARE NO |
| EXCEPTIONS TO THE REQUIRED ATTACHMENTS OF 250.50. |
| |
| ** NEW NOTES ** |
| |
| 1) NOTE: PLEASE SEE THE SEAL ON SAID PLANS IS NOT |
| LONGER VALID FOR USE IN THE STATE OF FLORIDA. PLEASE |
| SEE RULING 61G15-23.001 WHICH WAS PASSED BY THE FLORIDA |
| BOARD OF PROFESSIONAL ENGINEERS IN FEB 04, IN WHICH THE |
| WORDING O IN THE SEAL "CERTIFICATE" COULD NOT LONGER BE |
| USED AND MUST BE CHANGED TO THE WORDING OF"LICENSE". |
| PLEASE KNOW AN EXTENSION WAS GIVEN ONLY TO THE DATE OF |
| DECEMBER 31ST, 2005. PLEASE OBTAIN NEW SEAL. |
| PLEASE ALSO SEE PLANS APPEAR TO BE SIGNED WITH |
| INITIALS, IF THIS IS INDEED THE LEGAL SIGNATURE OF SAID |
| ENGINEER, PLEASE SUBMIT A SIGNED, DATED, SEALED AND |
| NOTARIZED LETTER FOR VERIFICATION OF LEGAL SIGNATURE. |
| THIS WILL BE PLACED IN OUR SIGNATURE FILE FOR FUTURE |
| REFERENCE. |
| FS 471.025, FAC 61G15-23.002 |
| |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| |
| |
| |