2006-11-03 19:42:33 | ** UNSAT ** |
| |
| |
| |
| 1) NOTE; PLEASE SEE THE VALUATION FOR SCOPE OF WORK |
| APPLIED FOR SHALL BE BASED ON ALL LABOR AND MATERIALS |
| EVENS OF OWNER SUPPLIED. PLEASE SEE THE VALUE SEEMS |
| VERY LOW FOR THIS FOUNDATION AND AMOUNT OF |
| CONCRETE/STEELETC WORK SHOWN. PLEASE SEE BUILDING |
| REVIEW NOTES. |
| FBC ADMIN SECT 108.3 |
| |
| 2) NOTE: PLEASE SEE REVIEW COMMENTS UNDER THE MAIN |
| BUILDING PERMITS. |
| PLEASE SUPPLY SLAB PLANS FOR ELECTRICAL CONDUIT |
| INSTALLATION UNDER SLAB. |
| 215.5, 230.70, 230.6, 230.70 ETC. |
| PLEASE BE SURE TO SEE COMMENTS UNDER BLDG REVIEW AS |
| THIS MAY VERY WELL AFFECT THE ELECTRICAL CONDUIT |
| LOCATION. |
| |
| 3) NOTE: PLEASEALSO SUBMIT GROUNDING ELECTRODE |
| CONNECTION DETAIL AS REQUIRED PER 250.50. (FOOTER |
| STEEL, UNDER GROUND COLD WATER PIPES ETC REQUIRED). |
| THERE ARE NO EXCEPTIONS TO THE REQUIRED ATTACHMENTS OF |
| 250.50. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |