Plan Review Notes For Permit 06100658 |
Permit Number |
06100658 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-10-18 13:57:44 | DENIED BY BUILDING | | | | 1) THE PRODUCT APPROVALS FOR THE TAMKO MODIFIED SYSTEM | | REQUIRES RAS 117 CALCULATIONS FROM AN ARCHITECT, | | ENGINEER OR REGISTERED ROOF CONSULTANT FOR THE REQUIRED | | ENHANCED FASTENING AT THE PERIMETER AND CORNERS. SEE | | PAGE 20 OF THE NOA. SUBMIT CALCULATIONS. | | | | 2) SPECIFY THE ROOF PITCH AND MEAN ROOF HEIGHT FOR THE | | SLOPED ROOF. | | | | 3) THE ELK SHINGLE NOA DOES NOT ALLOW THEM TO BE | | INSTALLED ON ROOFS WITH A MEAN HEIGHT OF MORE THAN 33 | | FEET. SEE LIMITATIONS ON PAGE 2 OF THE NOA. | | | | 4) PLEASE INDICATE THE SQUARE FOOTAGE OF FLAT AND | | SLOPED ROOF SEPARATELY ON THE APPLICATION. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 |
|