Plan Review Notes
Plan Review Notes For Permit 06100592
Permit Number 06100592
Review Stop B
Sequence Number 1
Notes
Date Text
2006-10-29 13:48:19BUILDING PLAN REVIEW
 PERMIT:06100592
 ADD:2139 PBL BLVD
 CONT:KNIGHT ELECTRIC CO. INC.
 TEL: (561)689-2876
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW1ST
 ACTION: DENIED
  
 1) 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 2) THEEFFECTIVE PROJECTED AREA OF THE LIGHT FIXTURE
 ON THE POLE IN REFERENCE TO WIND IS REQUIRED.
  
 3) 61G15-23.002 (2)THE DRAWINGS SUBMITTED REQUIRE THE
 EMBOSSED SEAL OF THE ENGINEER RESPONSIBLE FOR THE
 DESIGN.IF PRACTICING THROUGH A DULY AUTHORIZE
 ENGINEERING BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL AS, THE NAME,
 ADDRESS, AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS ON EACH SHEET.
 NOTE: THE DRAWINGS EVEN STATES THAT THE PLANS ARE NOT
 VALID WITHOUT THE ENBOSSED SEAL.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  