 REVIEW COMPLETED, NOTES BELOW.
  
 ** DENIED REVISIONS **
  
 1) NOTE: PLEASE SEE SHEET E0-2.2 WHICH INDICATES
 CONDUITS FOR LIGHTING IN THE RIGHT OF WAY ON THE PLANS
 FOR THIS BUILDING. THIS IS TO BE INCLUDED ON SEPARATE
 PLANS AND UNDER SEPARATE PERMITS WHICH IS NOT A PART OF
 THIS BUILDING OR LEGAL PROPERTY.
  
 2) NOTE: PLEASE SEE *PROVISO* AND *DENIAL* COMMENTS
 FROM JULY 27TH, 2007 WHICH HAVE NOT BEEN ADDRESSED. AS
 SOME OF THE REVISED SHEETS SUBMITTED DO HAVE A FEW OF
 THESE ITEMS DONE, MOST HAVE NOT.
 PLEASE SEE THE ATTACHED NOTES FOR THAT DATE.
 THESE NEED TO BE ADDRESSED AND INCORPORATED INTO PLAN
 SETS AS SOON AS POSSIBLE TO ALLEVIATE CONFUSION AND
 REVISIONS BEING MIXED AND/OR MISSED ALONG THE WAY. FBC
 ADMIN SECTION. 106.1.2,106.3.1 ETC
  
 3) NOTE: PLEASE SEE NUMEROUS SHEETS HAVE BEEN REVISED
 WITH CIRCUITING, LOADS INCREASING, ADDED POWER
 LOCATIONS, ADDED RECEPTACLES ETC HOWEVER NOT REVISED
 PANEL SCHEDULES OR LOAD CALCULATIONS WERE SUBMITTED.
 PLEASE SEE THE PANEL SCHEDULES AND LOADS ON FILE DO NOT
 CONTAIN MANY OF THE NEW CIRCUITS NOW SHOWN.
 PLEASE SEE THE PANEL SCHEDULES DO NOT CONTAIN THE
 INCREASE IN LOADS BY THE ADDED DEVICES ETC.
 PLEASE COORDINATE AND REVISE LOAD CALCULATIONS FOR
 AFFECTED PANELS. PLEASE REVISE PANEL SCHEDULES
 ACCORDINGLY.
 PLEASE SEE SHEET E1-5.1 ROOM A5.406 AS SOME RECEPTACLES
 WERE REVISED AND DO NOT CONTAIN CIRCUITING.
 PLEASE SEE THIS SAME SHEET AS RECEPTACLES ADDED TO
 CIRCUIT(S) 5LA3-5, 5LA3-34 DO NOT CORRELATE WITH LOADS
 AND PANEL SCHEDULES. THIS IS TYPICAL OF NUMEROUS
 CIRCUITS, LOADS, SHEETS AND PANELS.
 FBC 106.3.5.1.2, 106.1.2
 NEC 408.4, 220 ETC
  
 4) NOTE: PLEASE SEE THERE ARE SEVERAL LOCATIONS ON
 SHEETS WHERE THE FURNITURE LAYOUTS HAVE NOW BEEN
 REMOVED. ??
  
 5) NOTE: AS NOTED AND AGREED BY THE CONTRACTOR, OWNER
 AND AS SHOWN ON ORIGINAL PLANS, THE LOW VOLTAGE SYSTEMS
 ARE TO BE UNDER A SEPARATE PERMIT AND ARE NOT PART OF
 THE BASE BUILDING PLANS AND PERMITTING.
 PLEASE SUBMIT THREE COMPLETE SETS WITH PERMIT
 APPLICATION, APPROPRIATE VALUE AND FEES FOR THE SCOPE
 OF WORK.
 ** PLEASE BE SURE TO SPECIFY THE TYPE OF CABLING,
 CONDUIT INSTALLATION ETC.
  
 6) NOTE: PLEASE EXPLAIN TITLE BLOCKS WITH
 IDENTIFICATION OF REVISIONS. THE SHEETS ARE LABELED AS
 REV # 11, YET THE DESCRIPTION INDICATES THIS IS
 REVISION #3?
 THIS IS UNCLEAR.
 ALTHOUGH NOT REQUIRED, PLEASE KNOW A SUBMITTAL OF A
 LETTER ON REVISIONS TAKING PLACE ALONG THE PROCESS OF
 THE JOB WOULD HELP TO PERHAPS ALLEVIATE ANY CONFUSION
 AND DELAYS IN PROJECT.
  
 ** AS STATED ON PREVIOUS REVIEWS: IF THERE ARE ANY
 QUESTIONS, PLEASE DO NOT HESITATE IN CONTACTING THIS
 OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-09-08 21:29:062007-09-08 21:29:06
  
 REVIEW COMMENCED.
2007-09-05 19:19:082007-09-05 19:19:08
 1-ROLL IN ELECTRICAL FOR REVIEW: