2007-09-09 12:56:26 | 2007-09-09 12:56:26 |
| REVIEW COMPLETED, NOTES BELOW. |
| |
| ** DENIED REVISIONS ** |
| |
| 1) NOTE: PLEASE SEE SHEET E0-2.2 WHICH INDICATES |
| CONDUITS FOR LIGHTING IN THE RIGHT OF WAY ON THE PLANS |
| FOR THIS BUILDING. THIS IS TO BE INCLUDED ON SEPARATE |
| PLANS AND UNDER SEPARATE PERMITS WHICH IS NOT A PART OF |
| THIS BUILDING OR LEGAL PROPERTY. |
| |
| 2) NOTE: PLEASE SEE *PROVISO* AND *DENIAL* COMMENTS |
| FROM JULY 27TH, 2007 WHICH HAVE NOT BEEN ADDRESSED. AS |
| SOME OF THE REVISED SHEETS SUBMITTED DO HAVE A FEW OF |
| THESE ITEMS DONE, MOST HAVE NOT. |
| PLEASE SEE THE ATTACHED NOTES FOR THAT DATE. |
| THESE NEED TO BE ADDRESSED AND INCORPORATED INTO PLAN |
| SETS AS SOON AS POSSIBLE TO ALLEVIATE CONFUSION AND |
| REVISIONS BEING MIXED AND/OR MISSED ALONG THE WAY. FBC |
| ADMIN SECTION. 106.1.2,106.3.1 ETC |
| |
| 3) NOTE: PLEASE SEE NUMEROUS SHEETS HAVE BEEN REVISED |
| WITH CIRCUITING, LOADS INCREASING, ADDED POWER |
| LOCATIONS, ADDED RECEPTACLES ETC HOWEVER NOT REVISED |
| PANEL SCHEDULES OR LOAD CALCULATIONS WERE SUBMITTED. |
| PLEASE SEE THE PANEL SCHEDULES AND LOADS ON FILE DO NOT |
| CONTAIN MANY OF THE NEW CIRCUITS NOW SHOWN. |
| PLEASE SEE THE PANEL SCHEDULES DO NOT CONTAIN THE |
| INCREASE IN LOADS BY THE ADDED DEVICES ETC. |
| PLEASE COORDINATE AND REVISE LOAD CALCULATIONS FOR |
| AFFECTED PANELS. PLEASE REVISE PANEL SCHEDULES |
| ACCORDINGLY. |
| PLEASE SEE SHEET E1-5.1 ROOM A5.406 AS SOME RECEPTACLES |
| WERE REVISED AND DO NOT CONTAIN CIRCUITING. |
| PLEASE SEE THIS SAME SHEET AS RECEPTACLES ADDED TO |
| CIRCUIT(S) 5LA3-5, 5LA3-34 DO NOT CORRELATE WITH LOADS |
| AND PANEL SCHEDULES. THIS IS TYPICAL OF NUMEROUS |
| CIRCUITS, LOADS, SHEETS AND PANELS. |
| FBC 106.3.5.1.2, 106.1.2 |
| NEC 408.4, 220 ETC |
| |
| 4) NOTE: PLEASE SEE THERE ARE SEVERAL LOCATIONS ON |
| SHEETS WHERE THE FURNITURE LAYOUTS HAVE NOW BEEN |
| REMOVED. ?? |
| |
| 5) NOTE: AS NOTED AND AGREED BY THE CONTRACTOR, OWNER |
| AND AS SHOWN ON ORIGINAL PLANS, THE LOW VOLTAGE SYSTEMS |
| ARE TO BE UNDER A SEPARATE PERMIT AND ARE NOT PART OF |
| THE BASE BUILDING PLANS AND PERMITTING. |
| PLEASE SUBMIT THREE COMPLETE SETS WITH PERMIT |
| APPLICATION, APPROPRIATE VALUE AND FEES FOR THE SCOPE |
| OF WORK. |
| ** PLEASE BE SURE TO SPECIFY THE TYPE OF CABLING, |
| CONDUIT INSTALLATION ETC. |
| |
| 6) NOTE: PLEASE EXPLAIN TITLE BLOCKS WITH |
| IDENTIFICATION OF REVISIONS. THE SHEETS ARE LABELED AS |
| REV # 11, YET THE DESCRIPTION INDICATES THIS IS |
| REVISION #3? |
| THIS IS UNCLEAR. |
| ALTHOUGH NOT REQUIRED, PLEASE KNOW A SUBMITTAL OF A |
| LETTER ON REVISIONS TAKING PLACE ALONG THE PROCESS OF |
| THE JOB WOULD HELP TO PERHAPS ALLEVIATE ANY CONFUSION |
| AND DELAYS IN PROJECT. |
| |
| ** AS STATED ON PREVIOUS REVIEWS: IF THERE ARE ANY |
| QUESTIONS, PLEASE DO NOT HESITATE IN CONTACTING THIS |
| OFFICE. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
2007-09-08 21:29:06 | 2007-09-08 21:29:06 |
| |
| REVIEW COMMENCED. |
2007-09-05 19:19:08 | 2007-09-05 19:19:08 |
| 1-ROLL IN ELECTRICAL FOR REVIEW: |