Plan Review Notes
Plan Review Notes For Permit 06100574
Permit Number 06100574
Review Stop M
Sequence Number 8
Notes
Date Text
2007-11-06 15:30:42REVIEW #: 8TH
 ACTION: PASSED/DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING PAGES WERE REVIEWED FOR COMPLIANCE,
 STAMPED AND INCORPORATED INTO THE PERMIT SET OF PLANS
 AS REV 12A:
  
 M1-1.0, M1-2.0, M1-2.2, M1-3.0, M1-3.1, M1-4.0, M1-4.1,
 M1-4.2, M1-5.0, M1-5.1, M1-5.2, M1-6.0, M2-3.0, M3-1.0
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 REV. 11 COMMENTS:
  
 1. REVISION 12A WILL BE REVIEWED FOR CODE COMPLIANCE AS
 WELL AS RESPONSES TO PREVIOUS REVIEW COMMENTS FROM
 REVISIONS 10 AND 11.
  
 2. M1-1.1: AT THE FIRE COMMAND CENTER, A 6X6 TRANSFER
 DUCT HAS BEEN RELOCATED. IF THIS ROOM IS STILL ENCLOSED
 BY FIRE-RESISTANCE RATED CONSTRUCTION, THIS OPENING IS
 REQUIRED TO BE PROTECTED BY A FIRE DAMPER IN ACCORDANCE
 WITH FBC,M 607.5. ALSO, THE 50X26 SUPPLY DUCT FROM
 CAHU-1 SHOWS A TEE FITTING OVER ALCOVE A1.104. AT THIS
 LOCATION THERE ARE TWO DUCTS PENETRATING THE RATED WALL
 BUT ONLY ONE DUCT SHOWS OPENING PROTECTIVE FSD
  
 3. OK
  
 4. OK
  
 5. OK
  
 5A. M1-1.2: EF-3 DUCT PENETRATING FLOOR/CEILING
 ASSEMBLY ABOVE ROOM D1.107, IS THIS DUCT ENTERING A
 SHAFT? IF SO, PROVIDE FIRE AND SMOKE DAMPER AS REQUIRED
 BY FBC,M 607.5.5.1.
  
 6. OK, EXCEPT: KEY NOTE #6 INDICATES ONLY THE TWO
 FIRE/SMOKE DAMPERS ON THE SMOKE EXHAUST DUCT AT THE
 ?ATRIUM? ARE TO BE CONTROLLED BY THE SMOKE CONTROL
 SYSTEM. HAS THERE BEEN A RATIONAL ANALYSIS DONE TO
 DETERMINE WHICH DAMPERS SHOULD BE OPENED AND CLOSED
 DURING SMOKE CONTROL MODE? OPENINGS IN SMOKE BARRIERS
 SHALL BE PROTECTED BY AUTOMATIC-CLOSING DEVICES
 ACTUATED BY THE REQUIRED CONTROLS FOR THE MECHANICAL
 SMOKE CONTROL SYSTEM IN ACCORDANCE WITH FBC,M 513.5.2.
 THIS MAY ALSO APPLY TO THE FIRE/SMOKE DAMPERS IN THE
 SMOKE EXHAUST DUCT PENETRATIONS OF THE SHAFT
 ENCLOSURES.
  
 7. OK
  
 8. OK
  
 9. OK
  
 10. OK
  
 11. M1-2.3 WILL BE REVIEWED IN RESPONSE TOPART OF REV
 10 COMMENTS.
  
 12. OK
  
 13. M1-3.2: HOW WILL THE FIRE/SMOKE DAMPERS BE ACCESSED
 FOR SERVICE, MAINTENANCE AND TESTING ABOVE THIS STAIR
 CAP? EVEN WITH 4?9? BETWEEN THE CAP AND THE DECK ABOVE,
 AT LEAST 2 OF THE DAMPERS MAY BE RENDERED INACCESSIBLE
 BY THE ROUTING OF THE DUCTS. ALSO, IF THE STAIR CAP IS
 TO BE USED AS A SERVICE PLATFORM, IT SHALL BE REQUIRED
 TO MEET THE REQUIREMENTS FOR A SERVICE PLATFORM IN
 ACCORDANCE WITH THE FBC.
  
 14. M1-3.2: THERE IS ONE DUCT SHOWN PENETRATING
 PROGRAM/MEETING ROOM C3.306 TO FEED TWO VAV BOXES.
 WHILE THE SIZE OF THE DUCTS FEEDING THE VAV?S IS
 DETEMINED BY THE INLET SIZE ON THE VAV, A SIZE NEEDS TO
 BE PROVIDED FOR THE DUCT PENETRATING THE WALL BEFORE IT
 BRANCHES TO FEED THE TWO VAV?S. PLEASE CLARIFY. FBC,M
 603.1
  
 15. OK
  
 16. OK
  
 17. OK
  
 18. OK
  
 REV. 10 COMMENTS:
  
 1. OK
  
 2. OK
  
 3. M1-1.3 THROUGH M1-5.3: ACCORDING TO MANUFACTURER?S
 INSTALLATION INSTRUCTIONS, THE CO SENSORS ARE GOOD FOR
 APPROXIMATELY 5000 SQ FT OR A 40 FT RADIUS. BASED ON
 THE LAYOUT SHOWN ON PLANS, THERE ARE AREAS NOT
 ADEQUATELY COVERED BY THE SENSORS. SHOW DETECTORS
 LOCATED TO PROVIDE FULL COVERAGE OF THE PARKING GARAGE.
 FBC,M 304.1
  
 4. OK
  
 5. OK PENDING VERIFICATION OF INTAKE LOCATION.
  
 6. OK
  
 7. OK
  
 8. OK
  
 9. OK
  
 10. OK
  
 NEW COMMENTS RELATED TO REV. 12A:
  
 1. M4-4.0: SEQUENCE OF OPERATION NOTE #1, ACTIVATION OF
 THE SMOKE CONTROL SYSTEM SHALL BE IN COMPLIANCE WITH
 FBC 909.12.3.
  
 2. M4-4.0: SEQUENCE OF OPERATION NOTE #2, THIS NOTE IS
 IN CONFLICT WITH THE NOTE ON FLOOR PLANS WHICH
 INDICATES SMOKE DAMPERS ARE TO BE CONTROLLED BY DUCT
 SMOKE DETECTORS. ALSO, ALL SMOKE DAMPERS WHICH ARE
 RELATED TO THE SMOKE CONTROL SYSTEM AND REQUIRED BY THE
 SMOKE CONTROL SYSTEM FOR THE ATRIUM AREA SHALL BE
 CONTROLLED BY THE SMOKE CONTROL SYSTEM. FBC,M 513.5.2
  
 3. M4-4.0: SEQUENCE OF OPERATION NOTES 2 THROUGH 7: A
 RATIONAL ANALYSIS FOR THE DESIGN OF THE SMOKE CONTROL
 SYSTEM SHALL BE PROVIDED TO DETERMINE THE ACTUAL
 REQUIRED SEQUENCE OF OPERATIONS, INCLUDING SMOKE DAMPER
 ACTUATION, RELATED TO THE PROPER OPERATION OF THE SMOKE
 CONTROL SYSTEM IN ACCORDANCE WITH FBC,M 513.4.
  