2007-08-01 13:22:22 | 1. THE CARBON MONOXIDE SENSORS DISPLAYED ON THE |
| MEHANICAL SHEETS ARE TO BE INSTALLED PER MANUFACTURER'S |
| REQUIREMENTS. WHAT SET POINTS ARE THE CARBON MONOXIDE |
| DETECTORS GOING TO BE SET AT. THESE DEVICES WILL NEED |
| TO BE TESTED WITH CALIBRATION GAS AFTER INSTALLATION. |
| PLEASE PROVIDE PRODUCT APPROVALS AND CUT SHEETS FOR |
| THESE DEVICES. PLEASE PROVIDE DETAILS ON CARBON |
| MONOXIDE SYSTEM. THE INSTALLATION LOCATIONS FOR THESE |
| DEVICES SHALL NOT EXCEED MAXIMUM COVERAGE AREAS OR |
| SPACING REQURIEMENTS. |
| |
| 2. ALL ELECTRICAL REVISIONS TO COMPLY WITH NFPA 70, THE |
| NATIONAL ELECTRICAL CODE. |
| |
| 3. THE INSTALLATION OF THE CHAIN LINK FENCE FOR THE |
| FUTURE GENERATOR AND ANY PARKING SPACES SHALL NOT |
| INTERFERE WITH ANY EXIT ACCESS TO STAIR # 4. |
| |
| 4. THE OPERATION OF EMERGENCY LIGHTING EQUIPMENT EVEN |
| IF THEY ARE EQUIPPED WITH OCCUPANCY SENSORS SHALL |
| COMPLY WITH THE OPERATIONAL REQUIREMENTS OF CHAPTER |
| SEVEN OF THE LIFE SAFETY CODE. |
| |
| 5. NO EMERGENCY PHOTOMETRICS DISPLAYED IN FIRE COMMAND |
| CENTER ON PAGE E-8-1.1. |
| |
| 6. PLEASE BE ADVISED THAT LARGE BATHROOMS MUST BE |
| EQUIPPED WITH EMERGENCY LIGHTING. LARGE RESTROOMS CAN |
| BE EXTREMELY DARK WHEREBY ACCESS TO THE INGRESS/EGRESS |
| DOOR FROM THE ROOM CAN BE IMPOSSIBLE. |
| |
| |