Plan Review Notes
Plan Review Notes For Permit 06100574
Permit Number 06100574
Review Stop FIRE
Sequence Number 8
Notes
Date Text
2007-08-01 13:22:221. THE CARBON MONOXIDE SENSORS DISPLAYED ON THE
 MEHANICAL SHEETS ARE TO BE INSTALLED PER MANUFACTURER'S
 REQUIREMENTS. WHAT SET POINTS ARE THE CARBON MONOXIDE
 DETECTORS GOING TO BE SET AT. THESE DEVICES WILL NEED
 TO BE TESTED WITH CALIBRATION GAS AFTER INSTALLATION.
 PLEASE PROVIDE PRODUCT APPROVALS AND CUT SHEETS FOR
 THESE DEVICES. PLEASE PROVIDE DETAILS ON CARBON
 MONOXIDE SYSTEM. THE INSTALLATION LOCATIONS FOR THESE
 DEVICES SHALL NOT EXCEED MAXIMUM COVERAGE AREAS OR
 SPACING REQURIEMENTS.
  
 2. ALL ELECTRICAL REVISIONS TO COMPLY WITH NFPA 70, THE
 NATIONAL ELECTRICAL CODE.
  
 3. THE INSTALLATION OF THE CHAIN LINK FENCE FOR THE
 FUTURE GENERATOR AND ANY PARKING SPACES SHALL NOT
 INTERFERE WITH ANY EXIT ACCESS TO STAIR # 4.
  
 4. THE OPERATION OF EMERGENCY LIGHTING EQUIPMENT EVEN
 IF THEY ARE EQUIPPED WITH OCCUPANCY SENSORS SHALL
 COMPLY WITH THE OPERATIONAL REQUIREMENTS OF CHAPTER
 SEVEN OF THE LIFE SAFETY CODE.
  
 5. NO EMERGENCY PHOTOMETRICS DISPLAYED IN FIRE COMMAND
 CENTER ON PAGE E-8-1.1.
  
 6. PLEASE BE ADVISED THAT LARGE BATHROOMS MUST BE
 EQUIPPED WITH EMERGENCY LIGHTING. LARGE RESTROOMS CAN
 BE EXTREMELY DARK WHEREBY ACCESS TO THE INGRESS/EGRESS
 DOOR FROM THE ROOM CAN BE IMPOSSIBLE.
  
  
 APPROVED PROVISO
  
 MIKE CARSILLO, BATTALION CHIEF
 804-4709 PHONE
 804-4774 FAX