2007-07-26 11:35:29 | |
| ** REVIEW FOR REV #8 AND REV #10. |
| |
| |
| *** PROVISO /UNSAT *** |
| |
| ** PLEASE SEE CONDITIONS ARE STILL GIVEN FOR SOME ITEMS |
| NOT SUBMITTED AND FOR SOME ITEMS ON PLANS FOR |
| COORDINATION ETC. SOME SHEETS ARE STAMPED AND PROVISO |
| NOTES FOLLOW BELOW. |
| |
| ** PLEASE SEE THE FAILURE COMMENTS AT THE END OF |
| *PROVISO* NOTES FOR SHEETS WHICH WERE NOT STAMPED.. |
| |
| |
| |
| |
| 1) NOTE: PLEASE SEE THE OVER ALL SHEET E1-1.0 DOES NOT |
| MATCH WITH NEW LAYOUT FOR MECHANICAL ROOM AT GARAGE AND |
| HALLWAY AREA. |
| PLEASE SEE NOTES ON REVIEW OF PHOTO-METRIC PLANS |
| REVIEW. |
| |
| 2) NOTE: PLEASE SEE E2-2.2 MEN AND WOMEN RESTROOMS ON |
| UPPER LEFT HAND CORNER WHICH STILL SEEM TO INDICATE BY |
| HASHED LINES MORE THAN THE TWO EM LTS. |
| PLEASE SEE SOME OF THESE ARE SHOWN ON OTHER SHEETS AND |
| FOR OTHER BATHROOMS. |
| PLEASE SEE COMMENTS WITH RESPECT TO PHOTO-METRICS. |
| |
| 3) NOTE: PLEASE SEE SHEET E2-4.2 WHICH WILL REMAIN |
| REDLINED AS ROOF-TOP ACCESS AND WHETHER OR NOT STAIRS |
| WILL BE REQUIRED IS STILL IN QUESTION. |
| |
| 4) NOTE: PLEASE KNOW THAT UPDATED POWER PLANS FOR |
| CHANGES AND CORRECTIONS WILL STILL BE NEEDED. |
| |
| 5) NOTE: PLEASE SEE THE UPPER PART OF THE ELECTRICAL |
| RISER DIAGRAM WAS NOT SUBMITTED. THIS SHEET ALONG WITH |
| SOME OTHERS SHOWING THE CHANGES FOR THE GENERATOR ETC |
| WILL STILL BE NEEDED. |
| PLEASE SEE THAT THE SPECIFICATIONS ON THE GENERATOR AND |
| FIELD MODIFICATIONS FOR BI-FUEL ARE STILL NEEDED FOR |
| REVIEW. |
| 700,701, 110.3, 90.7. |
| |
| 6) NOTE: PLEASE SEE PANEL 5LEB TOTAL FOR VA HAS NOT |
| BEEN CORRECTED AS NOTED ON PREVIOUS REVIEW AND REDLINED |
| ON PREVIOUS REVIEWED #8 REVISIONS. |
| THE TOTAL LOAD ON PANEL DOES NOT CORRELATE WITH THE |
| TOTAL ON LOAD SUMMARY OF PANEL. |
| |
| 7) NOTE: PLEASE SEE SHEET E6-1.0 WHICH STILL INDICATES |
| A 825KW GENERATOR. AS THIS GENERATOR AHS CHANGED SIZE |
| SEVERAL TIMES, PLEASE COORDINATE ALL SHEETS WITH |
| REFERENCE TO THIS UNIT. PLEASE SEE COMMENTS ON |
| PHOTO-METRIC SHEETS AS THESE CONTAIN SEVERAL OTHER |
| REFERENCES. |
| |
| 8) NOTE: PLEASE SEE NOTE #6 ABOVE AS THE LOADS ADJUSTED |
| ON 5LEB NEED TO BE CARRIED THROUGH TO ALL OTHER PANELS. |
| 5HEB ETC. |
| FBC 106.3.5.1.2 NEC 220. |
| |
| 9) NOTE: PLEASE SEE SHEET E1-6.0 AS THE LAYOUT FOR THE |
| GENERATORS AND EQUIPMENT DOES NOT CORRELATE WITH |
| PLANS. |
| PLEASE SEE ROOF TOP MECH ROOM AND CONTROLS FOR LIGHTING |
| WHICH HAVE NOT BEEN CORRECTED TO COORDINATE WITH |
| PLANS. |
| |
| 10) NOTE: PLEASE KNOW THE IT ROOM HAS NOT BEEN |
| SUBMITTED FOR PERMITTING TO DATE ALONG WITH ANY LOW |
| VOLTAGE SYSTEMS FOR THE BUILDING. |
| |
| ALL ELECTRICAL SHEETS SUBMITTED WILL BE STAMPED WITH |
| THE EXCEPTION OF PHOTO-METRICS. |
| |
| |
| |
| ** UNSAT ** |
| |
| 1) NOTE: PLEASE SEE THE PHOTO-METRIC PLANS SUBMITTED |
| STILL NEED SOME COORDINATION. |
| PLEASE SEE THERE ARE SEVERAL SHEETS WHERE LIGHTING |
| FIXTURES ARE MISSING ALTHOUGH THEY ARE ACTUALLY ON THE |
| ELECTRICAL LIGHTING PLANS. |
| PLEASE SEE MANY AREAS ARE REDLINED WITH CIRCLES FOR |
| MISSING FIXTURES AND OR MULTIPLE FIXTURES WHEN THE |
| PLANS SHOW LESS OR MORE. |
| PLEASE SEE THAT MANY OF THESE ARE THE EMERGENCY |
| PHOTO-METRIC SHEETS.PLEASE SEE SOME OF THESE SHEETS |
| IN ONE SET ACTUALLY CONTAINS A *CHECK* AS THESE ARE OK, |
| HOWEVER CHANGES ON OTHER SHEETS FOR COORDINATION MAY |
| AFFECT THESE. |
| PLEASE SEE THE FOLLOWING SHEETS FOR EXAMPLE WHICH ARE |
| MISSING FIXTURES, LOCATIONS ARE INCORRECT OR ARE |
| SHOWING FIXTURES NOT ON LIGHTING PLANS. |
| 8-1.1, |
| 8-1.2, |
| 8-1.3, |
| 8-3.2, |
| 8-4.1, |
| 8-4.2, |
| 8-5.2 MISSING FC AVG. FOR STAIRS. |
| 8-6.0 3-GENERATORS SHOWN, 3-400KW GENERATORS. |
| 8-6.3 3-GENERATORS SHOWN, 2-FUTURE AND 1-825KW GEN. |
| 9-1.0 |
| ** PLEASE BE SURE TO COORDINATE THE SHEETS AS THE |
| LEVELS OF LIGHTING MAY CERTAINLY CHANGE WHEN FIXTURES |
| ARE ADDED OR DELETED. |
| PLEASE BE SURE TO SEE ANY ROOMS AND AREAS (MECH |
| ELECTRICAL ROOM IN GARAGE). |
| PLEASE SEE LS 101 7.8 AND 7.9. |
| PLEASE SEE FAC 61G15-33.004 |
| |
| |
| |
| IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |